Plan Review Details - Permit 17060886
Plan Review Stops For Permit 17060886
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-09 Cont ID  
Sent By shill Date 2017-08-09 Time 07:31 Rev Time 0.00
Received By shill Date 2017-08-09 Time 06:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-26 Cont ID  
Sent By shill Date 2017-06-26 Time 14:03 Rev Time 0.00
Received By shill Date 2017-06-26 Time 12:57 Sent To  
Notes
2017-06-26 14:10:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, THE APPLICATION IS FOR "TEMP TRAILER -
 WORKFORCE HOUSING". IT IS NOT CLEAR HOW "WORKFORCE
 HOUSING" IS RELEVANT TO THIS PERMIT.
  
 THE APPEARS TO BE A TEMPORARY CONSTRUCTION OFFICE
 TRAILER, PLEASE REVISE DESCRIPTION.
  
 2. FBC 107, PROVIDE A SITE PLAN SHOWING PROPOSED
 LOCATION OF PROPOSED MODULAR, INCLUDING DISTANCE TO
 PROPERTY LINES AND DISTANCE TO OTHER STRUCTURES ON THE
 LOT. NOT ENOUGH INFORMATION HAS BEEN PROVIDED TO
 DETERMINE CODE COMPLIANCE OR TO PROVIDE AN ACCURATE
 CORRECTION LIST.
  
 3. PLEASE ADVISE AS TO STATUS OF ENGINEERING PERMIT
 CURRENTLY IN APPLICATION (E17060013). IT IS POSSIBLE
 THAT AN ENGINEERING REVIEW MAY BE REQUIRED FOR THIS
 PERMIT. THIS PERMIT WILL NOT BE ISSUED WITHOUT
 ENGINEERING DEPARTMENT APPROVAL.
  
 4. A TEMPORARY FENCE DETAIL WAS PROVIDED. FENCING IS TO
 BE SUBMITTED UNDER A SEPARATE BUILDING PERMIT AND
 CANNOT BE A PART OF THE TEMPORARY TRAILER PERMIT, FBC
 107.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2017-08-08 Cont ID  
Sent By jleahy Date 2017-08-08 Time 14:11 Rev Time 0.00
Received By jleahy Date 2017-08-08 Time 14:11 Sent To  
Notes
2017-08-08 14:18:34FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SEE SEPARATE PERMIT 17070998 FOR ELECTRICAL SERVICE FO
 THESE TRAILERS.
  
 JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-03 Cont ID  
Sent By jleahy Date 2017-07-03 Time 07:22 Rev Time 0.00
Received By jleahy Date 2017-07-03 Time 07:21 Sent To I
Notes
2017-07-03 07:24:48FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 215.5 DIAGRAMS OF FEEDERS
 A DIAGRAM SHOWING FEEDER DETAILS SHALL BE PROVIDED
 PRIOR TO THE INSTALLATION OF THE FEEDERS.
 SUCH A DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF
 THE BUILDING OR
 OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL
 CALCULATED LOAD BEFORE
 APPLYING DEMAND FACTORS, THE DEMAND FACTORS USED, THE
 CALCULATED LOAD
 AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND TYPE OF
 CONDUCTORS TO BE USED
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-10 Cont ID  
Sent By scaldero Date 2017-08-10 Time 08:14 Rev Time 0.00
Received By scaldero Date 2017-08-10 Time 08:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-26 Cont ID  
Sent By scaldero Date 2017-06-26 Time 15:15 Rev Time 0.00
Received By scaldero Date 2017-06-26 Time 15:12 Sent To  
Notes
2017-06-26 15:15:13PERMIT # 17060886
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION.
  
 2) SITE PLAN NOT PROVIDED.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-11 Cont ID  
Sent By gjohnson Date 2017-08-11 Time 12:44 Rev Time 0.00
Received By gjohnson Date 2017-07-24 Time 11:22 Sent To  
Notes
2017-08-08 11:22:48B11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-03 Cont ID  
Sent By jleahy Date 2017-07-03 Time 07:25 Rev Time 0.00
Received By jleahy Date 2017-06-20 Time 14:03 Sent To  
Notes
2017-06-21 14:03:42B11

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-11 Cont ID  
Sent By gjohnson Date 2017-08-11 Time 12:42 Rev Time 0.00
Received By gjohnson Date 2017-08-11 Time 09:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-27 Cont ID  
Sent By gjohnson Date 2017-06-27 Time 11:32 Rev Time 0.00
Received By gjohnson Date 2017-06-27 Time 11:21 Sent To  
Notes
2017-06-27 11:46:041ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SITE PLAN SHOWING SEWER CONNECTION AND WATER
 SERVICE. PER WPB AMEND TO FBC 107.2.1
  
 2. A BACKFLOW IS REQUIRED ON THE WATER SERVICE. PER FBC
 PL 608.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-08-08 Time   Rev Time 0.00
Received By pgreilic Date 2017-08-08 Time 16:08 Sent To  
Notes
2017-08-08 16:09:02PAUL GREILICH, AICP, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2017-06-30 Time   Rev Time 0.00
Received By pgreilic Date 2017-06-28 Time 15:13 Sent To  
Notes
2017-06-30 09:02:541.) INDICATE LOCATION OF PROPOSED TEMPORARY TRAILER ON
 SITE
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]