Plan Review Details - Permit 17060851
Plan Review Stops For Permit 17060851
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2017-12-28 Time 09:21 Sent To  
Notes
2017-12-28 09:21:47OPENED THIS STOP BY MISTAKE. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-08-25 Cont ID  
Sent By jgomez Date 2017-08-25 Time 15:28 Rev Time 0.00
Received By jgomez Date 2017-08-25 Time 14:33 Sent To  
Notes
2017-08-25 15:04:00BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ENERGY CALCULATIONS: (A)NEED ACTUAL
 ORIENTATION OF THE BUILDING. (B)ALL WALL TYPES TO MATCH
 PLANS. (C)HEATING INFO TO MATCH EQUIPMENT SIZING
 CALCULATIONS. (D)REVISE THE DOORS INFORMATION ON PAGE 3
 OF 5. WHERE ARE THE 16'-0" X 8'-0" INSULATED DOORS?
 2- TRUSS PACKAGE SUBMITTED: (A)REVISE DESIGN LOADS TO
 MATCH DESIGN CRITERIA SPECIFIED BY THE ENGINEER OF
 RECORD ON SHEET 2.1. (B)REVISED TRUSS PACKAGE TO BE
 APPROVED IN WRITING BY THE ENGINEER OF RECORD PRIOR TO
 SUBMITTAL T THIS OFFICE. (C)TRUSS LAYOUT AND ALL
 INDIVIDUAL TRUSS DRAWINGS NEED TO BE SIGNED AND SEALED
 AND HAVE THE TRUSS ENGINEER INFORMATION IN ALL DRAWINGS
 AS REQUIRED BY FAC 61G15-31.003.
2017-08-25 14:33:2108/25/17 MET DAISY. SHE BROUGHT LETTER STATING THAT IS
 OK TO ISSUE PERMIT WITH PROVISO. I TOLD HER REVISION
 FEES WILL APPLY. SHE SAID IS OK. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-17 Cont ID  
Sent By jgomez Date 2017-08-17 Time 15:17 Rev Time 0.00
Received By jgomez Date 2017-08-17 Time 10:25 Sent To  
Notes
2017-08-17 10:40:39NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR AGREES TO SUBMIT REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTION TO AVOID CONFLICTS/DELAYS. REVISION FEES
 WILL APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) ENERGY CALCULATIONS NEED TO BE DONE FOR THE ACTUAL
 ORIENTATION OF THE BUILDING NOT WORST CASE. REVISE ITEM
 #5 AS REQUIRED BY SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE. REPEAT COMMENT. FRONT PAGE SAYS NO WORST
 CASE. NEVERTHELESS, SECOND PAGE SAYS ROTATED 315
 DEGREES AND ORIENTATION SHOWN ON FOLLOWING PAGES IS NOT
 THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS
 REQUIRED. PROVIDE CALCULATIONS FOR THE ACTUAL
 ORIENTATION OF THE BUILDING.
  
 B) REVISE WALL TYPE ON ITEM #9(B) FOR THE ADJACENT
 WALL. PLANS CALL FOR METAL FRAMING ON ONE SIDE AND WOOD
 FRAMING ON THE OTHER SIDE. SEC. 101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE: PLANS AND ENERGY CALCULATIONS NEED TO BE
 COORDINATED. FLOOR PLAN AND GENERAL WALL LEGEND ON
 SHEET 2.1 SPECIFY WOOD FRAMING FOR THE BEARING WALLS L
 AND METAL STUDS FOR NON BEARING WALLS. PLANS AND ENERGY
 CALCULATIONS NEED TO MATCH. REVISE AS REQUIRED.
  
 C) HEATING INFORMATION SHOWN ON ITEM #13 DOESN'T T
 MATCH INFORMATION SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT.
  
 D) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD AS REQUIRED BY SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT.
  
 E) REVISE WALLS AND WINDOWS ORIENTATION SHOWN ON PAGE 3
 OF 5. COORDINATE WITH ITEM #1(A) ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT.
  
 F) REVISE THE DOORS INFORMATION SHOWN ON PAGE 3 OF 5.
 WHERE ARE THE 16'-0" X 8'-0" INSULATED DOORS?. SEE
 PLANS AND PRODUCT APPROVALS SUBMITTED. NOTE: DOORS WITH
 GLAZING NEED TO BE CONSIDERED IN THE WINDOWS AREA AS
 REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED.
 RESPONSE: REPEAT COMMENT.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON ITEM #7 IS REQUIRED WHEN THE
 ENERGY CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT
 FACTOR.
  
 2- ROOF TILE UNDERLAYMENT FL11288-R15 SUBMITTED:
 CLEARLY MARK SPECIFIC UNDERLAYMENT INSTALLATION SHOWING
 THE DESIGN PRESSURES OF PROPOSED INSTALLATION TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: SEE PAGES 5,6 AND 7 OF
 EVALUATION REPORT SUBMITTED. MARK SPECIFIC APPLICATION
 #.
 RESPONSE: REPEAT COMMENT. CLEARLY IDENTIFY WHICH
 ASSEMBLY ON PAGE 5, 6 OR 7 IS GOING TO BE INSTALLED.
 NOTE: MAKE SURE ASSEMBLY IS FOR WOOD DECK. IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN IT CAN NOT BE USED.
 (NOTE: ON 08/22/17 ROOFING CONTRACTOR E-MAILED FRSA
 TABLES SHOWING PROPOSED UNDERLAYMENT INSTALLATION).
  
 3- TRUSS PACKAGE SUBMITTED:
 A) DESIGN LOADS DON'T MATCH DESIGN CRITERIA SPECIFIED
 BY THE ENGINEER OF RECORD. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. TRUSS ENGINEER TO SEE DESIGN
 CRITERIA ON SHEET 2.1 AND REVISE AS REQUIRED.
  
 B) BASED ON ITEM #3(A) ABOVE REVISED TRUSS PACKAGE TO
 BE REVIEWED AND APPROVED IN WRITING BY THE ENGINEER OF
 RECORD PRIOR TO SUBMITTAL T THIS OFFICE. SEC. 107.3.4.2
 CITY AMENDMENTS.
  
 C) TRUSS LAYOUT AND ALL INDIVIDUAL TRUSS DRAWINGS NEED
 TO BE SIGNED AND SEALED AND HAVE THE TRUSS ENGINEER
 INFORMATION IN ALL DRAWINGS AS REQUIRED BY FAC
 61G15-31.003.
 RESPONSE: REPEAT COMMENT.
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY SPECIFYING
 HOW EACH COMMENT IS ADDRESSED TO EXPEDITE THE REVIEW
 PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By jgomez Date 2017-07-19 Time 15:36 Rev Time 0.00
Received By jgomez Date 2017-07-18 Time 17:13 Sent To  
Notes
2017-07-18 18:07:53NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEE IS DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- SQUARE FOOTAGE ON THE PROJECT AREA ON SHEET 2.1 IS
 MISSING THE AREA FOR THE COVERED PATIO. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- PROJECT DATA ON SHEET 2.1 IS MISSING THE ATTIC LIVE
 LOAD AS REQUIRED BY NOTES "B" AND "G" OF TABLE R301.5
 FBC-5TH EDITION (2014).
  
 4- PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING
 TO THE GREAT ROOM. DOOR NEEDS SELF CLOSING DEVICE AS
 REQUIRED BY SEC. R302.5.1 FBC-RESIDENTIAL.
  
 5- REVISE DIMENSION "A" ON COMPONENTS AND CLADDING
 INFORMATION ON SHEET 4.1 AND 5.1. ACCORDING TO NOTE ON
 FIGURE R301.2(7) OF FBC-RESIDENTIAL THE DIMENSION "A"
 IS 4 FEET IN ALL CASES NOT 3 FEET. REVISE AS REQUIRED.
  
 6- REVISE GARAGE DOORS DESIGN PRESSURES SHOWN ON SHEET
 4.1 AND 5.1. ACCORDING TO NOTES ON PLANS SUBMITTED THE
 DESIGN PRESSURES SHOWN ARE BASED ON TABLE R301.2(4)
 FBC-RESIDENTIAL. DESIGN PRESSURES SHOWN DON'T
 CORRESPOND TO THE REQUIRED DESIGN PRESSURES WHEN THE
 PRESSURES ARE MULTIPLIED BY THE 1.21 COEFFICIENT TO
 REPRESENT THE EXPOSURE "C". REVISE AS REQUIRED.
  
 7- DRAWINGS 7.1, 8.1 AND 9.1 NEED THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS
 REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS.
  
 8-ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION # (604700) AS REQUIRED BY SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) ENERGY CALCULATIONS NEED TO BE DONE FOR THE ACTUAL
 ORIENTATION OF THE BUILDING NOT WORST CASE. REVISE ITEM
 #5 AS REQUIRED BY SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 D) REVISE WALL TYPE ON ITEM #9(B) FOR THE ADJACENT
 WALL. PLANS CALL FOR METAL FRAMING ON ONE SIDE AND WOOD
 FRAMING ON THE OTHER SIDE. SEC. 101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E) HEATING INFORMATION SHOWN ON ITEM #13 DOESN'T T
 MATCH INFORMATION SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD AS REQUIRED BY SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
  
 G) REVISE WALLS AND WINDOWS ORIENTATION SHOWN ON PAGE 3
 OF 5. COORDINATE WITH ITEM #8(C) ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) REVISE THE DOORS INFORMATION SHOWN ON PAGE 3 OF 5.
 WHERE ARE THE INSULATED DOORS?. SEE PLANS AND PRODUCT
 APPROVALS SUBMITTED. DOORS WITH GLAZING NEED TO BE
 CONSIDERED IN THE WINDOWS AREA AS REQUIRED BY SEC.
 R405.5.3.3 FBC-ENERGY CONSERVATION. REVISE AS REQUIRED.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON ITEM #7 IS REQUIRED WHEN THE
 ENERGY CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT
 FACTOR.
  
 9- REVISE LOCATION OF CARBON MONOXIDE ALARMS TO COMPLY
 WITH SEC. R315.1 FBC-RESIDENTIAL.
  
 10- REVISE LOCATION OF SMOKE ALARMS TO COMPLY WITH SEC.
 R314.3 FBC-RESIDENTIAL.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12- ROOF TILE UNDERLAYMENT FL11288-R15 SUBMITTED:
 CLEARLY MARK SPECIFIC UNDERLAYMENT INSTALLATION SHOWING
 THE DESIGN PRESSURES OF PROPOSED INSTALLATION TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: SEE PAGES 5,6 AND 7 OF
 EVALUATION REPORT SUBMITTED. MARK SPECIFIC APPLICATION
 #.
  
 13- TRUSS PACKAGE SUBMITTED:
 A) TRUSS LAYOUT DOESN'T MATCH ENGINEER'S OF RECORD ROOF
 FRAMING PLAN. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 B) DESIGN LOADS DON'T MATCH DESIGN CRITERIA SPECIFIED
 BY THE ENGINEER OF RECORD. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C) COMPLETE TRUSS PACKAGE TO BE REVIEWED AND APPROVED
 IN WRITING BY THE ENGINEER OF RECORD PRIOR TO SUBMITTAL
 T THIS OFFICE. SEC. 107.3.4.2 CITY AMENDMENTS.
  
 D) TRUSS LAYOUT AND ALL INDIVIDUAL TRUSS DRAWINGS NEED
 TO BE SIGNED AND SEALED AND HAVE THE TRUSS ENGINEER
 INFORMATION IN ALL DRAWINGS AS REQUIRED BY FAC
 61G15-31.003.
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY SPECIFYING
 HOW EACH COMMENT IS ADDRESSED TO EXPEDITE THE REVIEW
 PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-22 Cont ID  
Sent By jpearson Date 2017-08-22 Time 10:07 Rev Time 0.00
Received By jpearson Date 2017-08-22 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-11 Cont ID  
Sent By jpearson Date 2017-07-11 Time 07:37 Rev Time 0.00
Received By jpearson Date 2017-07-11 Time 07:37 Sent To  
Notes
2017-07-11 08:04:49CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHOW LOCATION OF ELECTRICAL SERVICE ON PLAN. FBC
 107.2.1
 2. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. MASTER CLOSETS SHOW
 RECESS LIGHTS. PROVIDE CORRECTION. NEC 410.16(B), FBC
 RE4003.12
 3. SMOKE/CO ALARMS ARE REQUIRED TO BE IN THE IMMEDIATE
 VICINITY OUTSIDE THE BEDROOMS. THE CURRENT PLACEMENT IN
 BOTH HALLWAYS OUTSIDE THE BEDROOMS APPEARS THAT IT IS
 TOO FAR FROM THE MASTER BEDROOMS. PROVIDE CORRECTION.
 FBC R314.3
 4. NOTE ON PLAN STATES THAT ALL RECEPTACLES SHALL HAVE
 TAMPER RESISTANT PROTECTION PER NEC 406.11. THIS CODE
 SECTION DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES.
 PROVIDE CORRECTION. NEC 406.12; FBC RE4002.14
 5. PROVIDE COMPLIANCE WITH ENERGY CONSERVATION FOR
 LIGHTING: "A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS". A NOTE ON PLAN WILL SUFFICE.
 FBC EC R404.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-07-19 Cont ID  
Sent By gjohnson Date 2017-07-19 Time 17:49 Rev Time 0.00
Received By gjohnson Date 2017-07-19 Time 17:49 Sent To  
Notes
2017-07-19 17:50:14GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-25 Cont ID  
Sent By jgomez Date 2017-08-25 Time 17:06 Rev Time 0.00
Received By jgomez Date 2017-08-25 Time 14:31 Sent To  
Notes
2017-08-25 14:32:2108/25/17 MET DAISY. SHE BROUGHT LETTER STATING THAT IS
 OK TO ISSUE PERMIT WITH PROVISO. I TOLD HER REVISION
 FEES WILL APPLY. SHE SAID IS OK. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-24 Cont ID  
Sent By gjohnson Date 2017-08-24 Time 16:54 Rev Time 0.00
Received By gjohnson Date 2017-08-08 Time 12:54 Sent To  
Notes
2017-08-09 12:54:21R29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-19 Cont ID  
Sent By jgomez Date 2017-07-19 Time 16:04 Rev Time 0.00
Received By jgomez Date 2017-06-19 Time 13:15 Sent To  
Notes
2017-06-20 13:15:24R30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-08-17 Cont ID  
Sent By jgomez Date 2017-08-17 Time 10:55 Rev Time 0.00
Received By jgomez Date 2017-08-17 Time 10:55 Sent To  
Notes
2017-08-17 10:56:00$21.91 PAID. MU-2017-020615

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By jgomez Date 2017-07-19 Time 15:58 Rev Time 0.00
Received By jgomez Date 2017-07-19 Time 15:58 Sent To  
Notes
2017-07-19 15:59:221- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEE IS DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-08-25 Cont ID  
Sent By jgomez Date 2017-08-25 Time 17:04 Rev Time 0.00
Received By jgomez Date 2017-08-25 Time 16:58 Sent To  
Notes
2017-08-25 14:34:27MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS NOT
 JUST THE SUMMARY SHEET. CALCULATIONS TO BE DONE BASED
 ON THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED
 BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
2017-08-25 14:33:5008/25/17 MET DAISY. SHE BROUGHT LETTER STATING THAT IS
 OK TO ISSUE PERMIT WITH PROVISO. I TOLD HER REVISION
 FEES WILL APPLY. SHE SAID IS OK. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-17 Cont ID  
Sent By jgomez Date 2017-08-17 Time 16:46 Rev Time 0.00
Received By jgomez Date 2017-08-17 Time 12:39 Sent To  
Notes
2017-08-17 15:32:48NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR AGREES TO SUBMIT REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTION TO AVOID CONFLICTS/DELAYS. REVISION FEES
 WILL APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS NOT
 JUST THE SUMMARY SHEET. CALCULATIONS TO BE DONE BASED
 ON THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED
 BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. PROVIDE COMPLETE PACKAGE.
 NEED TO VERIFY WITH REVISED ENERGY CALCULATIONS. SEE
 BUILDING REVIEW FOR COMMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY SPECIFYING
 HOW EACH COMMENT IS ADDRESSED TO EXPEDITE THE REVIEW
 PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By jgomez Date 2017-07-19 Time 16:04 Rev Time 0.00
Received By jgomez Date 2017-07-19 Time 07:52 Sent To  
Notes
2017-07-19 16:20:18NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS NOT
 JUST THE SUMMARY SHEET. CALCULATIONS TO BE DONE BASED
 ON THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED
 BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 2- EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE MISSING
 EQUIPMENT INFORMATION. SPECIFY THE COIL MODEL AND THE
 AHRI REFERENCE NUMBER. ALSO, PROVIDE THE MANUFACTURER
 AND MODEL INFORMATION ABOUT THE HEATING EQUIPMENT. SEC.
 R403.6.1 FBC-ENERGY CONSERVATION.
  
 3- A/C PLAN TO SHOW ALL THE EQUIPMENT INFORMATION.
 COORDINATE WITH ITEM #2 ABOVE. SEC. 107.3.5.3(10) CITY
 AMENDMENTS.
  
 4- A/C PLAN TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS.
  
 5- CONDENSING UNIT MOUNTING DETAIL ON SHEET 7.1:
 CLARIFY FASTENING OF THE UNIT TO THE CONCRETE SLAB.
 PROVIDE DETAIL SHOWING HOW THE 3/8" BOLTS ARE ATTACHED
 TO THE BASE OF THE UNIT. SPECIFY HOW MUCH EMBEDMENT
 INTO THE CONCRETE SLAB IS REQUIRED FOR THE 3//8" SLEEVE
 ANCHORS. CLEARLY SPECIFY NUMBER OF FASTENER REQUIRED ON
 EACH SIDE. CLARIFY WHY ONLY SPECIFYING FASTENERS ON TWO
 SIDES OF THE UNIT. PROVIDE CALCULATIONS SHOWING THAT
 FASTENING ON ONLY TWO SIDES IS ADEQUATE TO RESIST THE
 WIND LOADS. SEC. R301.1 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY SPECIFYING
 HOW EACH COMMENT IS ADDRESSED TO EXPEDITE THE REVIEW
 PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-24 Cont ID  
Sent By gjohnson Date 2017-08-24 Time 16:51 Rev Time 0.00
Received By gjohnson Date 2017-08-24 Time 15:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By gjohnson Date 2017-07-12 Time 17:01 Rev Time 0.00
Received By gjohnson Date 2017-07-12 Time 15:16 Sent To  
Notes
2017-07-12 17:10:571ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. 7.1 PLEASE SHOW THE WATER CLOSET IN THE POWDER
 ROOM BATH CONNECTING TO THE BRANCH DRAIN TO LAV IT IS
 SHOWN ON THE BUILDING DRAIN NOW. PER FBC RES P3108.1
  
 2. THE TWOWAY CLEAN OUT AT THE BUILDING DRAIN AND
 BUILDING SEWER JUNCTION SHALL BE 4". PER FBC RES
 P3005.2.9
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2017-08-23 Cont ID  
Sent By jgomez Date 2017-08-23 Time 09:00 Rev Time 0.00
Received By jgomez Date 2017-08-23 Time 09:00 Sent To  
Notes
2017-08-23 09:00:33 
 APPROVED PRODUCT APPROVALS:
 A) ROOFING TILES FL7849-R10.
  
 B) UNDERLAYMENT FL11288-R15 WITH FRSA INSTRUCTIONS
 EMAILED BY ROOFING CONTRACTOR ON 08/22/17.
  
 C) ROOF TILE ADHESIVE FL6332-R7.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2017-08-23 Cont ID  
Sent By jgomez Date 2017-08-17 Time 15:29 Rev Time 0.00
Received By jgomez Date 2017-08-17 Time 15:29 Sent To  
Notes
2017-08-17 15:29:43 
 1- ROOF TILE UNDERLAYMENT FL11288-R15 SUBMITTED:
 CLEARLY MARK SPECIFIC UNDERLAYMENT INSTALLATION SHOWING
 THE DESIGN PRESSURES OF PROPOSED INSTALLATION TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: SEE PAGES 5,6 AND 7 OF
 EVALUATION REPORT SUBMITTED. MARK SPECIFIC APPLICATION
 #.
  
  
 APPROVED PRODUCT APPROVALS:
 A) ROOFING TILES FL7849-R10.
  
 B) UNDERLAYMENT FL11288-R15.
  
 C) ROOF TILE ADHESIVE FL6332-R7.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By jgomez Date 2017-07-19 Time 15:59 Rev Time 0.00
Received By jgomez Date 2017-07-19 Time 15:59 Sent To  
Notes
2017-07-19 16:03:241- ROOF TILE UNDERLAYMENT FL11288-R15 SUBMITTED:
 CLEARLY MARK SPECIFIC UNDERLAYMENT INSTALLATION SHOWING
 THE DESIGN PRESSURES OF PROPOSED INSTALLATION TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: SEE PAGES 5,6 AND 7 OF
 EVALUATION REPORT SUBMITTED. MARK SPECIFIC APPLICATION
 #.
  
  
 APPROVED PRODUCT APPROVALS:
 A) ROOFING TILES FL7849-R10.
  
 B) UNDERLAYMENT FL11288-R15.
  
 C) ROOF TILE ADHESIVE FL6332-R7.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-08-21 Time   Rev Time 0.00
Received By pgreilic Date 2017-08-18 Time 16:42 Sent To  
Notes
2017-08-21 17:05:20PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2017-06-29 Time   Rev Time 0.00
Received By pgreilic Date 2017-06-28 Time 15:14 Sent To  
Notes
2017-06-29 16:29:151.) LABEL HEIGHT OF PROPOSED RESIDENCE. NOTE MAXIMUM
 HEIGHT IS 30 FEET PURSUANT TO SEC. 94-72
  
 PAUL GREILICH, SENIOR PLANNER