Plan Review Details - Permit 17060830
Plan Review Stops For Permit 17060830
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-24 Cont ID  
Sent By pleduc Date 2017-08-24 Time 08:14 Rev Time 0.00
Received By jleahy Date 2017-06-28 Time 08:14 Sent To  
Notes
2017-06-28 08:39:14CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR THE WORK SEEMS LOW, PLEASE PROVIDE A SIGNED
 CONTRACT FOR WORK PROPOSED.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION
 SHALL BE SET BY THE BUILDING OFFICIAL
  
 CGC CAN NOT PULL A PERMIT FOR A FIRE ALARM, WORKING OUT
 OF SCOPE, PLEASE HAVE FIRE ALARM CONTRACTOR SIGN ON TO
 THE PERMIT.
  
 489.113?QUALIFICATIONS FOR PRACTICE; RESTRICTIONS.
 (3)?A CONTRACTOR SHALL SUBCONTRACT ALL ELECTRICAL,
 MECHANICAL, PLUMBING, ROOFING, SHEET METAL, SWIMMING
 POOL,
 AND AIR-CONDITIONING WORK, UNLESS SUCH CONTRACTOR HOLDS
 A STATE CERTIFICATE OR REGISTRATION IN THE RESPECTIVE
 TRADE CATEGORY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-21 Cont ID  
Sent By pleduc Date 2017-06-21 Time   Rev Time 0.00
Received By pleduc Date 2017-06-20 Time 17:00 Sent To E
Notes
2017-06-21 10:56:37PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE IS NO CONTRACTOR NAME SUBMITTED FOR THIS LIFE
 SAFETY SYSTEM.
  
 THE CONTRACTOR SHALL BE A CERTIFIED/LICENSED LIFE
 SAFETY CONTRACTOR WITH THE STATE OF FLORIDA.
  
  
 2) THE VALUE ON THIS PROPOSED INSTALLTION APPEARS TO BE
 LOW.
  
 PLEASE PROVIDE A COPY OF THE CONTRACT WITH THE
 CONTRACTOR INFORMATION.
  
  
  
 A HOLD WAS PLACED ON THIS PERMIT ISSUANCE UNTIL THE
 CONTRACTOR IS SUBMITTED WITH ALL REQUIRED INFORMATION.
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-28 Cont ID  
Sent By jleahy Date 2017-06-28 Time 08:39 Rev Time 0.00
Received By jleahy Date 2017-06-19 Time 10:53 Sent To  
Notes
2017-06-20 10:54:05ROUTED TO FIRE INBOX