| 2017-06-21 08:32:54 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17060813 |
| | 6/21/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE COMPANY THAT PREPARED THE AC AND ENERGY |
| | CALCULATIONS- ENERGY HOUSE TECHNOLOGY- CANNOT DRAW THE |
| | AC PLAN FOR THE NEW OFFICE AC SYSTEMS UNLESS THE |
| | COMPANY IS FL. STATE LICENSED AS AN AC OR MECHANICAL |
| | CONTRACTOR, AND IS THE INSTALLING CONTRACTOR ON THE |
| | PROJECT- SECTION 105.3.1 WEST PALM BEACH AMENDMENTS TO |
| | THE FBC. I PERFORMED A LICENSE SEARCH ON THE DPBR |
| | WEBSITE AND NO CONTRACTORS LICENSE EXISTS FOR EITHER |
| | ENERGY HOUSE TECHNOLOGY OR THE COMPANY OWNER BRUCE |
| | TSCHOSIK. THE PLAN SUBMITTED BY ENERGY HOUSE TECHNOLGY |
| | IS INCOMPLETE AND NOT DRAWN TO A MINIMUM 1/8" SCALE- |
| | SECTION 107.2.1.4. ADDITIONAL DEFICIENCIES AND |
| | INFORMATION MISSING FROM THE PLANS INCLUDE: EQUIPMENT |
| | SCHEDULES, AIR DISTRIBUTION SCHEDULE, VENTILATION |
| | CALCULATIONS, LOCATIONS AND INSTALLATION DETAILS FOR |
| | THE AIR HANDLERS AND CONDENSERS, RETURN AIR SYSTEM |
| | DETAILS, DUCTWORK SPECIFICATIONS AND SUPPORT AND |
| | HANGING DETAILS, OUTDOOR AIR DUCT SIZES, O/A OPENING |
| | PROTECTION, O/A SHUTOFF CONTROLS, CONDENSATE DISPOSAL, |
| | REFRIGERANT PIPING SPECIFICATIONS, RF PIPING RUNS AND |
| | PIPE PROTECTIONS, WIND LOAD ENGINEERING FOR |
| | INSTALLATION OF THE EXTERIOR CONDENSERS ETC. |
| | |
| | 2) NO PERMITS EXIST, NOR HAVE ANY PERMIT APPLICATIONS |
| | BEEN SUBMITTED FOR THE PROPOSED PROJECT TO CONVERT THE |
| | EXISTING UNCONDITIONED WAREHOUSE TO OFFICE SPACE. THE |
| | MECHANICAL REVIEW IS STOPPED UNTIL COMPLETE BUILDING |
| | AND MEP PLANS ARE SUBMITTED. PLEASE SEE SECTIONS |
| | C101.4.4 AND C101.4.5 FBC-14 ENERGY CONSERVATION: |
| | SUBMITTED FOR REVIEW ARE ENERGYGAUGE COMPLIANCE REPORTS |
| | USING THE ASHRAE 90.1 -2010 ENERGY COST BUDGET OPTION. |
| | ALL CONSTRUCTS FOR THE BUILDING ENVELOPE AND MEP |
| | SYSTEMS INFORMATION SHOWN ON THE SUBMITTED ASHRAE INPUT |
| | DATA REPORT MUST ALSO BE SHOWN ON THE ARCHITECTURAL AND |
| | MEP PLANS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |