| 2017-06-20 05:10:09 | 1) SUBMIT TWO COPIES OF A HOUSE / FLOOR PLAN SHOWING |
| | THE LOCATION OF THE TANKLESS WATER HEATER AND THE |
| | LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS |
| | IN RELATION TO THE WATER HEATER. THE LOCATION OF THE |
| | WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS FOR |
| | THE TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 3) THE BTU LOAD NOTED ON THE PLANS IS 870,000 BTU'S BUT |
| | MY CALCULATIONS SHOW A BTU LOAD OF 509,000. CLARIFY. |
| | 4) IS THERE A GAS RANGE ON THIS SYSTEM? IF SO, SHOW THE |
| | GAS RANGE ON BOTH SETS OF PLANS AND INCLUDE THE BTU |
| | LOAD IN THE DESIGN OF THE SYSTEM AND IF NEW SUBMIT |
| | MANUF. SPECS. 2014 FBC-FUEL GAS SECS. 402.1, 402.2. |
| | 5) SHOW THE CORRESPONDING EHD NUMBER OF THE CORRUGATED |
| | STAINLESS STEEL TUBING ON THE PLAN FOR EACH PIPE SIZE. |
| | WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | 6) IF THE TOTAL LOAD ON THE SYSTEM IS 870,000 BTU'S |
| | THEN THE ONE INCH CSST ON THE 2 POUND SYSTEM IS |
| | UNDERSIZED PER THE TABLE REFERENCED ON THE PLAN. A ONE |
| | INCH CSST LINE WITH AN EHD OF 31 AT 110 FT. DISTANCE IS |
| | 748,000 BTU'S PER TABLE 402.4 (18). CLARIFY. |
| | 7) SHOW THE LOCATION OF ALL THE NEW & RE-ROUTED GAS |
| | LINES ON THE FLOOR PLAN AND WHERE THE SLEEVES |
| | TERMINATE. COMPLY WITH 2014 FBC-FUEL GAS SECS. 404.14, |
| | 404.14.1, 404.14.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |