Plan Review Details - Permit 17060752
Plan Review Stops For Permit 17060752
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-27 Cont ID  
Sent By jwitmer Date 2017-07-27 Time 11:16 Rev Time 0.00
Received By jwitmer Date 2017-07-27 Time 09:56 Sent To  
Notes
2017-07-27 10:40:42 
 2014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060752
 ADD: 4334 EASLEY DRIVE
 CONT: GLOBAL TECH INC.
 TEL: 561-997-6433
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JULY 27/ 2017
  
 ACTION: BUILDING PROVISO
  
 1) SHEET FAC-6 INDICATES NEW SHED BUILDINGS 6 X 10 X 8
 FEET, A SIGNED AND SEALED LETTER FROM BERNARD P GANDY,
 P. E. STATES ?THE OWNER HAS ELECTED TO REMOVE THIS SHED
 FROM THE PROJECT IN FAVOR OF RESEARCHING ALTERNATIVES.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-10 Cont ID  
Sent By jwitmer Date 2017-07-10 Time 11:39 Rev Time 0.00
Received By jwitmer Date 2017-07-10 Time 09:19 Sent To  
Notes
2017-07-10 11:39:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060752
 ADD: 4334 EASLEY DRIVE
 CONT: GLOBAL TECH INC.
 TEL: 561-997-6433
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 10/ 2017
 ACTION: DENIED
  
 1) SHEET FAC-6 INDICATES NEW SHED BUILDINGS 6 X 10X8
 FEET BUT NO STATE APPROVED PLANS WERE SUBMITTED ALONG
 WITH THE PLANS. FLORIDA STATUTE 553 PART I/
 MANUFACTURED BUILDINGS. 553.7.9.1.
  
 2) SHEET FAC-6 NOTE #3. INDICATES THE RISK CATEGORY FOR
 THIS SHED IS CATEGORY I WITH AN ASSOCIATED WIND SPEED
 OF 150 MPH/ V ULT. PLEASE REFER TO THE 2014 FBC-B
 FIGURE 1609C. THE CITY OF WEST PALM BEACH FOR THIS
 CATEGORY BUILDING IS IN A 160 MPH VULT WIND ZONE. YOU
 MAY INTERPOLATE BETWEEN CONTOUR LINES.
  
 3) SHEET FAC-9 DETAIL # 3 SHOWS ANCHORING DETAILS
 COPIED ONTO THIS PLAN, BUT NONE OF THE NUMBERED
 NOTATIONS WERE PROVIDED FOR THIS REVIEW, NOR IS THE
 WIND SPEED THIS DETAIL DEPICTED GIVEN? NOR DO WE KNOW
 IF THESE ARE STATE APPROVED PLANS? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
 FLORIDA STATUTE 553 PART I/ MANUFACTURED BUILDINGS.
 553.7.9.1.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-26 Cont ID  
Sent By jpearson Date 2017-07-26 Time 07:58 Rev Time 0.00
Received By jpearson Date 2017-07-26 Time 07:58 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-13 Cont ID  
Sent By jpearson Date 2017-07-13 Time 13:15 Rev Time 0.00
Received By jpearson Date 2017-07-13 Time 13:15 Sent To  
Notes
2017-07-13 13:58:08CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. REVISE PANEL LP-1A SCHEDULE TO REFLECT THE
 ADDITIONAL LOAD, SHOWING TOTAL LOAD FOR EACH PHASE OF
 THE PANEL. FBC 107.2.1; NEC 215.5, 408.30
 2. PANEL LP-1A, CIRCUIT 18 IS LABELED AS "NEW E-1 PUMP
 STATION". IS THIS GPS-1? PLEASE CLARIFY AND/OR CORRECT.
 FBC 107.2.1, 408.4
 3. PROVIDE PANEL LP PANEL SCHEDULE, SHOWING ANY NEW OR
 ALTERED CIRCUITS, AND LOAD ON PANEL. FBC 107.2.1; NEC
 215.5, 408.30
 4. PROVIDE DETAIL OF LOAD TABULATION FOR SWBD-1. IS
 THIS LOAD TABULATION INCLUDE ALL LOADS? PROVIDE
 CLARIFICATION. FBC 107.2.1; NEC 215.5, 220, 408.30
 5. PROVIDE GRINDER PUMP SPEC SHEET. WHAT IS THE CURRENT
 DRAW FOR THIS? WHY DOES THE DETAIL SHOW THAT THE PUMP
 POWER USES A 120 VOLT LINE WIRE WITH THE EQUIPMENT
 GROUNDING CONDUCTOR(EGC)? THE EGC SHOULD NOT HAVE ANY
 CURRENT FLOW ON IT. NEC 110.3, 250.6, 250.26
 6. ONE LINE DIAGRAM SHOW TYPE AC CABLE INSTALLED IN 4"
 CONDUIT TO PUMP RCW-P-5. TYPE AC CABLE IS NOT PERMITTED
 IN WET OR DAMP LOCATIONS OR WHERE EXPOSED TO CORROSIVE
 CONDITIONS. PROVIDE CORRECTION. NEC 320.12
 7. TYPE AC CABLE MENTIONED IN COMMENT #5 SHOWS A #6 EGC
 TO PUMP. EGC IS REQUIRED TO BE SIZED PER NEC 250.122.
 WHAT IS THE OVERCURRENT PROTECTION ON THE MOTOR?
 PROVIDE CORRECTION AND DETAILS OF MOTOR CURRENT
 REQUIREMENTS. NEC 110.3, 250.122, 430.22
 8. PROVIDE DISONNECTS FOR MOTORS WITHIN SIGHT OF MOTOR,
 OR EXPLANATION OF SAFETY PROCEDURES IF THE EXCEPTION TO
 THIS RULE IS INTENDED. NEC 430.102(B)
 9. WIRE SIZE FEEDING RCW-VFD-5 IS DIFFERENT SIZE FROM
 THE WIRE FEEDING PUMP RCW-P-5. THIS DISCREPANCY DOES
 NOT EXIST ON THE OTHER PUMPS. PLEASE CLARIFY AND/OR
 CORRECT. FBC 107.2.1, NEC 310.15(B)(16)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-21 Cont ID  
Sent By pleduc Date 2017-06-21 Time   Rev Time 0.00
Received By pleduc Date 2017-06-20 Time 12:23 Sent To  
Notes
2017-06-20 13:54:54THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ALL WORK AND CONDITIONS SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF NFPA? 820, STANDARD FOR FIRE
 PROTECTION IN WASTEWATER TREATMENT AND COLLECTION
 FACILITIES, 2012 EDITION
  
 CHAPTER 1 ADMINISTRATION
 1.1 SCOPE.
 1.1.1* GENERAL. THIS STANDARD SHALL ESTABLISH MINIMUM
 REQUIREMENTS FOR PROTECTION AGAINST FIRE AND EXPLOSION
 HAZARDS IN WASTEWATER TREATMENT PLANTS AND ASSOCIATED
 COLLECTION SYSTEMS, INCLUDING THE HAZARD CLASSIFICATION
 OF SPECIFIC AREAS AND PROCESSES.
 1.1.2 THIS STANDARD SHALL APPLY TO THE FOLLOWING:
 (1) COLLECTION SEWERS
 (2) TRUNK SEWERS
 (3) INTERCEPTING SEWERS
 (4) COMBINED SEWERS
 (5) STORM SEWERS
 (6) PUMPING STATIONS
 (7) WASTEWATER TREATMENT PLANTS
 (8) SLUDGE-HANDLING FACILITIES
 (9) CHEMICAL-HANDLING FACILITIES
 (10) TREATMENT FACILITIES
 (11) ANCILLARY STRUCTURES (SEE 3.3.60.1)
  
 1.3 APPLICATION.
 1.3.1* NEW INSTALLATIONS. THE REQUIREMENTS OF THIS
 STANDARD SHALL APPLY TO NEW INSTALLATIONS.
 1.3.1.1 WHEN ADDITIONS OR MODIFICATIONS ARE MADE TO
 EXISTING FACILITIES, THE MODIFICATIONS SHALL REFLECT
 THE REQUIREMENTS OF THIS DOCUMENT.
 1.3.1.2 IN ANY EVENT, THE REQUIREMENTS OF THIS STANDARD
 SHALL BE USED BY OWNERS IN A RISK ASSESSMENT TO
 IDENTIFY THE AREAS OF A TREATMENT PLANT THAT ARE
 VULNERABLE TO FIRE OR OTHER LOSS.
  
  
 1.3.2 TOXICITY AND BIOLOGICAL HAZARDS.
 1.3.2.1 THIS STANDARD SHALL APPLY TO THE FIRE AND
 EXPLOSION HAZARDS OF VARIOUS SUBSTANCES ASSOCIATED WITH
 WASTEWATER TREATMENT AND CONVEYANCE.
  
 1.3.3 FIRE RISK EVALUATION. A FIRE RISK EVALUATION
 SHALL BE INITIATED EARLY IN THE FACILITY DESIGN OR
 ALTERATION TO INTEGRATE THE FIRE PREVENTION AND FIRE
 PROTECTION REQUIREMENTS DESCRIBED IN THIS DOCUMENT.
 1.3.4 VENTILATION PRACTICES. VENTILATION RATES REQUIRED
 BY THIS STANDARD SHALL BE TO MINIMIZE FIRE AND
 EXPLOSION HAZARDS, BECAUSE INSUFFICIENT VENTILATION
 RATES CAN EXPOSE PERSONNEL TO TOXIC AND BIOLOGICAL
 HAZARDS.
  
  
 PLEASE REVIEW AND ENSURE COMPLIANCE WHERE APPLICABLE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-27 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-24 Time 13:51 Sent To  
Notes
2017-07-25 13:51:50RESUB ROUTED TO JPEARSON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-18 Cont ID  
Sent By jroach Date 2017-07-18 Time 14:52 Rev Time 0.00
Received By jroach Date 2017-06-15 Time 14:20 Sent To  
Notes
2017-06-19 14:20:35C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-10 Cont ID  
Sent By jwitmer Date 2017-07-10 Time 11:39 Rev Time 0.00
Received By jwitmer Date 2017-07-10 Time 11:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-07-07 Cont ID  
Sent By ccole Date 2017-07-07 Time 17:40 Rev Time 0.00
Received By ccole Date 2017-07-07 Time 17:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-07-14 Cont ID  
Sent By gjohnson Date 2017-07-14 Time 16:45 Rev Time 0.00
Received By gjohnson Date 2017-07-14 Time 16:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-07-18 Cont ID  
Sent By jroach Date 2017-07-18 Time 15:50 Rev Time 0.00
Received By jroach Date 2017-07-18 Time 15:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By jroach Date 2017-07-18 Time 14:51 Rev Time 0.00
Received By jroach Date 2017-07-18 Time 14:51 Sent To  
Notes
2017-07-18 14:51:40ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.18.2017
 PERMIT NO.: 17060752
 ADDRESS: 4334 EASLEY DRIVE
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. IT APPEARS THAT THERE ARE MULTIPLE LOCATIONS WHERE
 PIPE WORK WILL IMPACT EXISTING TREE PLANTINGS. PLEASE
 CLARIFY IF THIS IS THE CASE. IF SO, A TREE ALTERATION
 PERMIT WILL NEED TO BE OBTAINED FROM THE CITY?S
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved