Plan Review Details - Permit 17060750
Plan Review Stops For Permit 17060750
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-07-06 Cont ID  
Sent By jleahy Date 2017-07-06 Time 07:47 Rev Time 0.00
Received By jleahy Date 2017-07-06 Time 07:47 Sent To  
Notes
2017-07-06 07:48:46SEE FIRE DEPT. PROVISO! FOR MISSING EQUIPMENT, IN
 HALLWAYS ,ELECTRICAL ROOM ECT. ECT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-05 Cont ID  
Sent By GTelfair Date 2017-07-05 Time   Rev Time 0.00
Received By wjolin Date 2017-06-21 Time 14:28 Sent To E
Notes
2017-07-05 11:07:16PASSED WITH THE FOLLOWING PROVISO:
  
 1. ENSURE THAT ALL AREAS PRODUCE AN INTELLIGIBLE
 EVACUATION MESSAGE. BASED ON THE PLANS IT APPEARS THAT
 DUE TO THE LACK OF SPEAKERS SOME AREAS MAY NOT MEET THE
 BURDEN OF INTELLIGIBLENESS FOR THE EVACUATION MESSAGE.
  
 2. ENSURE THAT THE PUBLIC RESTROOMS WILL MEET THE
 BURDEN OF VISIBILITY AND INTELLIGIBLENESS IN EACH
 STALL.
  
 3. ALL ELECTRICAL ROOMS APPEAR TO HAVE SMOKE DETECTION
 FOR EARLY INITIATION WITH THE EXCEPTION OF HE EXCEPTION
 OF ELECTRICAL ROOM 174A. PLEASE STATE REASON FOR THE
 INCONSISTENCY.
  
 4. CORRIDOR 240, 340, 440, 540 ,640, 740, 840, 940, AND
 1040 APPEAR TO BE MISSING SMOKE DETECTION COVERAGE.
  
 5. PER FLORIDA ADMINISTRATIVE RULE 69A-48.007 BOTH
 INITIATION DEVICES AND NOTIFICATION APPLIANCES MUST BE
 ASSIGNED A DEVICE NUMBER AND LABELED AS SUCH.
  
 6. INITIATING FLOOR OF ALARM SHALL ACTIVE ALARM
 NOTIFICATION ON THE FLOOR OF INCIDENCE AS WELL AS THE
 IMMEDIATE FLOOR ABOVE AND BELOW THE FLOOR OF INCIDENCE.
  
 7. PLANS INDICATE THAT THE FIRE ALARM WILL REPORT TO A
 REMOTE MONITORING STATION. THE FIRE ALARM IS REQUIRED
 TO REPORT TO A CENTRAL STATION.
  
 8. PLANS INDICATE THAT A SMOKE DETECTOR AND HEAT
 DETECTOR ARE INSTALLED AT THE TOP OF EACH ELEVATOR
 HOISTWAY. ARE THESE DEVICES REQUIRED DUE TO SPRINKLER
 INSTALLATION? ARE THESE DEVICES REQUIRED DUE TO
 SEQUENCE OF OPERATION OF THE SMOKE PRESSURIZATION
 AND/OR SMOKE EXHAUST SYSTEM? IF SO WHAT CODE(S),
 STANDARD(S), OR SEQUENCE OF OPERATIONS ARE BEING USED
 TO DEEM THEM A REQUIREMENT?
  
 9. THE PLAN INDICATES THAT DELTA 0 IS THE INDICATIOR
 FOR ALL WORK TO BE REVIEWED UNDER THE SCOPE OF THIS
 REVISION. HOWEVER DELTA 0 DOES NOT EXIST ON PLANS.
 PLEASE REMOVE ALL DELTA INDICATORS AND CLOUDS THAT ARE
 OUTSIDE THE SCOPE OF THIS REVISION, AND RESUBMIT WITH
 THE APPRPRIATE DELTAS AND CLOUDS FOR THE SCOPE OF THIS
 REVISION ONLY.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-06 Cont ID  
Sent By jleahy Date 2017-07-06 Time 07:59 Rev Time 0.00
Received By jleahy Date 2017-07-06 Time 07:59 Sent To  
Notes
2017-06-16 14:18:43REVISION ROUTED TO FIRE INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved