| 2017-07-13 12:09:20 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | SAMANTHA HILL |
| | [email protected] |
| | 561-805-6724 |
| | |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT, OR |
| | PLEASE CALL ME TO DISCUSS OPTIONS |
| | |
| | FROM PREVIOUS LIST: |
| | PROVIDE THE FOLLOWING INFORMATION FOR FLOORING |
| | SUBMITTALS: |
| | |
| | 1. OK. |
| | 2. OK |
| | 3. STATED VALUE OF WORK. - VALUE TOO LOW; VALUE SHOULD |
| | INCLUDE THE VALUE OF LABOR, MATERIALS, OVERHEAD, |
| | PROFIT, EVEN IF PROVIDED BY OTHERS |
| | 4. DESCRIPTION OF EXISTING SITE: |
| | 5. A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN |
| | CONCRETE/SUSPENDED GYPSUM) - NOT ADDRESSED; OUR RECORDS |
| | SHOW 7" SLAB |
| | 6. PROPOSED UNDERLAYMENT. - QUIETWALK UNDERLAYMENT TEST |
| | REPORTS SUBMITTED |
| | 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT PER ASTM |
| | E-84, E-90 & E-492. - TEST REPORTS FOR STC/IIC ARE FOR |
| | AN 8" SLAB, THIS FLOOR HAS A 7" SLAB, PLEASE ADDRESS |
| | 8. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| | |
| | FBC 603.1 FLAME SPREAD - ASTM E-84 - NOT ADDRESSED |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |