Plan Review Details - Permit 17060686
Plan Review Stops For Permit 17060686
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-23 Cont ID  
Sent By ccole Date 2018-08-23 Time 14:58 Rev Time 0.00
Received By ccole Date 2018-08-23 Time 14:58 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-18 Cont ID  
Sent By ccole Date 2018-07-18 Time 15:30 Rev Time 0.00
Received By ccole Date 2018-07-18 Time 15:30 Sent To I
Notes
2018-07-18 15:33:402ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17060686
 7/12/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE 1ST REVIEW COMMENT PRINTED BELOW WAS NOT
 ADDRESSED. PLEASE PROVIDE SIGNED AND SEALED ENGINEERING
 FOR THE SITE-BUILT REFRIGERATION ROOFTOP RACK. SEE THE
 1ST REVIEW PRINTED BELOW.
  
 2) THE REFRIGERATION UNIT IDENTIFICATIONS (RTU'S 1-4)
 LISTED ON THE STRUCTURAL ENGINEERING SUBMITTAL FROM
 CARL FORBES P.E. DO NOT MATCH THE IDENTIFICATIONS
 LISTED ON THE PLANS WHICH ARE COMP # 1 & 2, AND COND #1
 & 2. PLEASE CORRECT THE ID'S ON THE SUBMITTAL TO MATCH.
  
 1ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060686
 7/12/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED "SHOP DRAWING" APPEARS TO HAVE BEEN
 PRODUCED BY THE ARCHITECT ESENAT-COHEN ARCHITECT, P.A.
 AND IS ACTUALLY A SITE BUILT ROOF STAND AND NOT A
 SHOP-BUILT PRODUCT. THE ARCHITECT MUST PROVIDE HIS
 OFFICIAL SEAL AND SIGNATURE ON THE DRAWING PER SECTION
 61G15-16.003 FAC, AND PROVIDE THE WIND LOAD DESIGN
 CRITERIA AS OUTLINED IN SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By ccole Date 2017-07-12 Time 08:15 Rev Time 0.00
Received By ccole Date 2017-07-12 Time 08:15 Sent To  
Notes
2017-07-12 08:32:401ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060686
 7/12/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED "SHOP DRAWING" APPEARS TO HAVE BEEN
 PRODUCED BY THE ARCHITECT ESENAT-COHEN ARCHITECT, P.A.
 AND IS ACTUALLY A SITE BUILT ROOF STAND AND NOT A
 SHOP-BUILT PRODUCT. THE ARCHITECT MUST PROVIDE HIS
 OFFICIAL SEAL AND SIGNATURE ON THE DRAWING PER SECTION
 61G15-16.003 FAC, AND PROVIDE THE WIND LOAD DESIGN
 CRITERIA AS OUTLINED IN SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-07-18 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-03 Time 16:14 Sent To  
Notes
2018-07-05 16:15:04RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-12 Time   Rev Time 0.00
Received By cpuell Date 2017-06-14 Time 11:04 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-16 Cont ID  
Sent By eschneid Date 2018-07-16 Time 11:45 Rev Time 0.25
Received By eschneid Date 2018-07-16 Time 11:38 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-06-28 Cont ID  
Sent By eschneid Date 2017-06-28 Time 09:13 Rev Time 0.50
Received By eschneid Date 2017-06-28 Time 09:13 Sent To B
Notes
2017-06-28 09:29:28FAILED
  
 PROVIDE WRITTEN RESPONSE.
  
 1) THE EQUIPMENT SUPPORT STAND INCLUDED ON THIS PERMIT
 DIFFER THAN THE LAYOUT OF THE ROOFTOP AC EQUIPMENT
 SHOWN ON MASTER PERMIT 13090329. PLEASE PROVIDE REVISED
 SIGHT LINE DRAWINGS VERIFYING THAT THE FINAL ROOFTOP
 EQUIPMENT LAYOUT, INCLUDING FINAL HEIGHT, ARE STILL
 SCREENED FROM VIEW IN ACCORDANCE WITH THE BROADWAY
 MIXED USE DISTRICT REQUIREMENTS. PLEASE NOTE THAT THE
 REVISED LAYOUT NEEDS TO BE REFLECTED ON THE MASTER
 PERMIT PLANS AS A REVISION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
2017-06-15 14:27:08ROUTED TO ERIC SCHNEIDER