Plan Review Details - Permit 17060684
Plan Review Stops For Permit 17060684
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-07 Cont ID  
Sent By shill Date 2018-07-07 Time 15:41 Rev Time 0.00
Received By shill Date 2018-07-07 Time 15:41 Sent To  
Notes
2018-07-07 15:41:55PROVISO
 REFRIGERATION UNDER SEPARATE PERMIT
 COOLERS & FREEZERS TO BE FULLY SPRINKLERED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-23 Cont ID  
Sent By jwitmer Date 2017-06-23 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2017-06-23 Time 14:11 Sent To  
Notes
2017-06-23 14:27:13 
 2014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060684
 W. P. B. PRIMARY: 13090329
 ADD: 5011 BROADWAY AVE.
 CONT: NELCON CONSTRUCTION, INC.
 TEL: 305-331-1400
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 23/2017
 ACTION: DENIED
  
 1) THE REFRIGERATION PANEL SHOP DRAWING PLAN WILL NEED
 TO QUALIFY IF THE BUILDING THE COOLERS & FREEZERS ARE
 LOCATED IS A FIRE SPRINKLERED BUILDING. NOTE BUILDINGS
 THAT ARE NOT FIRE SPRINKLERED ARE LIMITED TO AN
 AGGREGATE AREA OF NOT MORE THAN 400 SQ. FT. SEE SECTION
 2603.4.1.3 OF THE 2014 FBC-B. PLEASE INDICATE ON THE
 PLANS.
  
 2) PLEASE PROVIDE DOCUMENTATION OF CODE COMPLIANCE WITH
 SECTION 2603.4.1.2 OF THE 2014 FBC-B:
  
 2603.4.1.2 COOLER AND FREEZER WALLS. FOAM PLASTIC
 INSTALLED IN A MAXIMUM THICKNESS OF 10 INCHES (254 MM)
 IN COOLER AND FREEZER WALLS SHALL:
  
 2.1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4-INCH (102 MM) THICKNESS.
  
 2.2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES
 OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C),
 RESPECTIVELY.
  
 2.3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
  
 2.4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1. WHERE THE COOLER OR
 FREEZER IS WITHIN A BUILDING, BOTH THE COOLER OR
 FREEZER AND THAT PART OF THE BUILDING IN WHICH IT IS
 LOCATED SHALL BE SPRINKLERED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-07 Cont ID  
Sent By shill Date 2018-07-07 Time 15:41 Rev Time 0.00
Received By shill Date 2018-07-03 Time 16:13 Sent To  
Notes
2018-07-05 16:13:51RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-19 Time   Rev Time 0.00
Received By cpuell Date 2017-06-14 Time 11:11 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-06-21 Cont ID  
Sent By ccole Date 2017-06-19 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2017-06-23 Time 14:11 Sent To B
Notes
2017-06-19 12:13:02REFRIGERATION FOR THE PROJECT WILL BE SUBMITTED UNDER A
 SEPARATE PERMIT.
 THIS PERMIT IS FOR THE WALK-IN BOX PANEL INSTALLATION.
 I HAVE ROUTED IT TO BUILDING.
 6/19/17
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  