| | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17060684 |
| | W. P. B. PRIMARY: 13090329 |
| | ADD: 5011 BROADWAY AVE. |
| | CONT: NELCON CONSTRUCTION, INC. |
| | TEL: 305-331-1400 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 23/2017 |
| | ACTION: DENIED |
| | |
| | 1) THE REFRIGERATION PANEL SHOP DRAWING PLAN WILL NEED |
| | TO QUALIFY IF THE BUILDING THE COOLERS & FREEZERS ARE |
| | LOCATED IS A FIRE SPRINKLERED BUILDING. NOTE BUILDINGS |
| | THAT ARE NOT FIRE SPRINKLERED ARE LIMITED TO AN |
| | AGGREGATE AREA OF NOT MORE THAN 400 SQ. FT. SEE SECTION |
| | 2603.4.1.3 OF THE 2014 FBC-B. PLEASE INDICATE ON THE |
| | PLANS. |
| | |
| | 2) PLEASE PROVIDE DOCUMENTATION OF CODE COMPLIANCE WITH |
| | SECTION 2603.4.1.2 OF THE 2014 FBC-B: |
| | |
| | 2603.4.1.2 COOLER AND FREEZER WALLS. FOAM PLASTIC |
| | INSTALLED IN A MAXIMUM THICKNESS OF 10 INCHES (254 MM) |
| | IN COOLER AND FREEZER WALLS SHALL: |
| | |
| | 2.1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE |
| | TESTED IN A MINIMUM 4-INCH (102 MM) THICKNESS. |
| | |
| | 2.2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES |
| | OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C), |
| | RESPECTIVELY. |
| | |
| | 2.3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 |
| | MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE |
| | METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT |
| | ANY POINT. |
| | |
| | 2.4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 903.3.1.1. WHERE THE COOLER OR |
| | FREEZER IS WITHIN A BUILDING, BOTH THE COOLER OR |
| | FREEZER AND THAT PART OF THE BUILDING IN WHICH IT IS |
| | LOCATED SHALL BE SPRINKLERED. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |