Plan Review Details - Permit 17060677
Plan Review Stops For Permit 17060677
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-08-03 Cont ID  
Sent By shill Date 2017-08-03 Time 13:03 Rev Time 0.00
Received By shill Date 2017-08-03 Time 13:02 Sent To  
Notes
2017-08-03 13:05:05PROVISO
  
 NO REVISION REQUIRED TO BE SUBMTITED TO BUILDING
 DIVISION UNLESS REQUESTED BY THE INSPECTOR
  
 FBC BUILDING 1609, PROVIDE A DETAIL OR SPECIFICATION
 FOR ATTACHMENT OF THE MECHANICAL UNIT TO THE CURB.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-08-02 Cont ID  
Sent By shill Date 2017-08-02 Time 11:37 Rev Time 0.00
Received By shill Date 2017-08-02 Time 11:37 Sent To  
Notes
2017-08-02 11:47:292014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 COMMENT FROM PREVIOUS LISTS:
  
 2) SEMI-COMPLIED. FOR ALL ROOF TOP EQUIPMENT, PLEASE
 PROVIDE THE DETAIL FOR THE ATTACHMENT FROM THE ROOF
 STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 3RD REVIEW - PLAN WAS NOT REVISED. RESPONSE LETTER
 PROVIDES A DESCRIPTION OF A DETAIL (APPEARS TO BE
 7-A5.01, ALREADY ON PLAN), AND AT THE END OF THE
 DESCRIPTION STATES "THE UNIT WILL BE CONNECTED TO THE
 NEW SUPPORT STEEL USING 1/2' STAINLESS STEEL BOLTS."
 RESPONSE LETTER ALSO REFERS TO ATTACHED PRODUCT SHEET.
  
 COMMENT #2 REQUESTS "A DETAIL FOR ATTACHMENT FROM THE
 ROOF STAND TO THE EQUIPMENT ABOVE". THE PRODUCT SHEET
 CANNOT BE USED TO SPECIFY ATTACHMENT (NOT SIGNED AND
 SEALED, NO WIND DESIGN CRITERIA, LACKS FASTENING
 SPECIFICATION.
  
 THE RESPONSE LETTER DOES NOT ADDRESS THE COMMENT; 1/2"
 STAINLESS STEEL BOLTS IS TOO GENERAL AND THE RESPONSE
 LETTER IS NOT RETAINED AS A PART OF THE PERMIT
 DOCUMENTS.
  
 EITHER A SEPARATE DETAIL CAN BE PROVIDED, OR THE DETAIL
 ON THE PLAN CAN BE MODIFIED TO INCLUDE THE
 SPECIFICATION.
  
 PLEASE REVISE PLAN TO INCLUDE THE INFORMATION
 REQUESTED; ALSO INCLUDE INFORMATION SUCH AS NUMBER
 REQUIRED, OR FASTENING PATTERN AS APPLICABLE, DIAMETER,
 LENGTH.
  
 THIS MAY BE A PROVISO ITEM UPON REQUEST. PLANS HAVE
 BEEN STAMPED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 SAMANTHA HILL
 (FOR JAMES A. WITMER BN, PX, CBO)
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6724
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-14 Cont ID  
Sent By jwitmer Date 2017-07-14 Time 15:52 Rev Time 0.00
Received By jwitmer Date 2017-07-14 Time 14:05 Sent To  
Notes
2017-07-14 15:52:062014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060677
 ADD: 2218 S. DIXIE HWY.
 CONT: BEELINE BUILDING CORP.
 TEL: 561-254-6779
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JULY 14, 2017
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SEMI-COMPLIED. FOR ALL ROOF TOP EQUIPMENT, PLEASE
 PROVIDE THE DETAIL FOR THE ATTACHMENT FROM THE ROOF
 STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 3-6) COMPLIED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-23 Cont ID  
Sent By jwitmer Date 2017-06-23 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2017-06-23 Time 09:01 Sent To  
Notes
2017-06-23 11:37:042014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060677
 ADD: 2218 S. DIXIE HWY.
 CONT: BEELINE BUILDING CORP.
 TEL: 561-254-6779
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 23, 2017
 ACTION: DENIED
  
 1) THERE IS A DISCREPANCY IN THE PLANS. SHEET A3.01
 INDICATES A NEW ROOF TOP UNIT WHEREAS THE MECHANICAL
 SHEET M3.01 INDICATES THE REPLACEMENT OF (2) 6 TON ROOF
 TOP UNITS AND THE REPLACEMENT OF AN EXISTING 15 TON
 ROOF TOP UNIT. WHEN WE VIEW THIS PROPERTY WITH EITHER
 THE PALM BEACH COUNTY PROPERTY APPRAISERS AERIAL
 PICTURES, OR THE COUNTY WIDE GIS/ GOOGLE, BING OR
 PICTORIAL AERIAL PHOTOGRAPHS THERE ARE ONLY (2) ROOF
 TOP UNITS. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
 PLEASE CORRECT PLANS TO DEPICT AN ACCURATE ACCOUNTING
 OF EXISTING ROOF TOP UNITS.
  
 2) FOR THE NEW ROOF TOP UNIT, THE PLANS WILL NEED TO
 PROVIDE DETAILS FOR THE TYPE OF ROOF FRAMING, WOOD
 TRUSSES, METAL BAR JOIST AND OR CONCRETE T SYSTEM OR
 TWIN T SYSTEMS, TYPE OF ROOF DECK AND THE REQUIRED
 FRAMING AROUND THE NEW ROOF PENETRATION, AND ATTACHMENT
 OF ROOF TOP CURB TO THE ROOF FRAMING SYSTEM AS WELL AS
 THE NEW RTU TO THE CURB.
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 3) FOR THE 2 REPLACEMENT ROOF TOP UNITS, PLEASE PROVIDE
 IF THE EXISTING CURB IS TO BE USED, IF EITHER A NEW
 CURB OR CURB ADAPTOR WILL BE REQUIRED, AND PROVIDE THE
 ANCHORING SYSTEM FOR THE CURB ADAPTOR AND THE ANCHORS
 REQUIRED TO ANCHOR THE REPLACEMENT RTU, UNITS. 2014
 FBC-B 1604.4 ANALYSIS. 2014 FBC-M- 301.15 WIND
 RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 4) NEITHER THE ARCHITECTURAL SHEETS NOR MECHANICAL
 SHEETS PROVIDE THE WIND DESIGN CRITERIA FOR THE NEW
 ROOF TOP & REPLACEMENT RTU UNITS. 2014 FBC-B 1603.1.4
 WIND DESIGN DATA.
  
 5) PLEASE NOTE EXISTING ROOF TOP UNITS ARE BEING
 REPLACED AND NEW ROOF TOP UNITS, PLEASE SHOW COMPLIANCE
 WITH:
 2014 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL BE
 PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH
 OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN
 SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO
 AS TO PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533
 MM) IN DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN
 30 INCHES (762 MM) BEYOND EACH END OF SUCH APPLIANCE,
 EQUIPMENT, FAN OR COMPONENT.
  
 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-28 Cont ID  
Sent By jpearson Date 2017-07-28 Time 10:02 Rev Time 0.00
Received By jpearson Date 2017-07-28 Time 10:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-07-21 Cont ID  
Sent By jpearson Date 2017-07-21 Time 14:27 Rev Time 0.00
Received By jpearson Date 2017-07-21 Time 14:27 Sent To  
Notes
2017-07-21 15:01:39CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (2ND REVIEW):
  
 1. LIGHTING PLAN SHOWS 1 OFFICE AND 2 BATHROOMS WITH
 OCCUPANCY SENSORS, BUT NO OTHER AREAS SHOW THE REQUIRED
 CONTROL. THE MECHANICAL ROOM HAS A STANDARD SWITCH, AND
 THE SALES AREAS SAY THAT THEY ARE TO BE CONNECTED TO
 LCP, BUT NO DETAIL IS PROVIDED FOR LCP AND NO OCCUPANCY
 SENSORS ARE SHOWN ON PLAN. CLARIFY AND/OR CORRECT. FBC
 107.2.1, C405.2.2
 2. SHOW LOCATION OF PANEL MDP ON POWER PLAN. FBC
 107.2.1
 3. AHU-1 IS BEING FED FROM PANEL AC AND IS SHOWN ON A
 20 AMP BREAKER WITH #12 WIRE. SPECS FROM THE MECHANICAL
 PLAN STATE THAT THE MINIMUM CIRCUIT AMPACITY FOR THIS
 IS 79 AMPS AND THE MAXIMUM OVER CURRENT PROTECTION
 (OCP) IS SHOWN AS 80 AMP. PROVIDE CORRECTION. NEC
 110.3, 310.15(B)(16), 440.22(C), FBC 107.2.1
 4. LOAD CALCULATION FOR PANEL AC DOES NOT INCLUDE THE
 ACCURATE LOAD FOR AHU-1. IT ALSO SHOWS THE MOTOR LOAD
 AT 100% INSTEAD OF THE REQUIRED 125%. PROVIDE
 CORRECTION AND UPDATE PANEL AC AND PANEL C WITH THIS
 INFORMATION. IT APPEARS THAT PANEL AC OCP AND POSSIBLY
 PANEL C WILL BE OVERLOADED WHEN THIS IS INCLUDED. MAKE
 ANY ADJUSTMENTS TO EQUIPMENT OR OCP AS NEEDED. FBC
 107.2.1, NEC 220, 215.2, 215.3, 408.30
 5. RISER DIAGRAM NEEDS TO BE COMPLETE WITH ALL WIRE
 SIZES TO CONFIRM CODE COMPLIANCE. VERIFYING WIRE AT
 LATER DATE IS NOT ACCEPTABLE. PROVIDE CORRECTION. NEC
 215.5, FBC 107.2.1
 6. RISER DIAGRAM STATES THAT THE ESTIMATED FAULT
 CURRENT IS 21,000, WHICH MATCHES THE RATING OF PANEL
 MDP. THE CALCULATION PROVIDED STATES THAT THE FAULT
 CURRENT IS 23,192, WHICH IS IN EXCESS OF THE RATING OF
 PANEL MDP. PROVIDE LETTER FROM POWER COMPANY WITH
 ACCURATE FAULT CURRENT, ADJUST EQUIPMENT AS NECESSARY.
 NEC 110.9, 110.10
 7. PROVIDE ACCURATE LOAD CALCULATION FOR PANEL A,
 SEVERAL LOADS ARE MISSING/NOT INCLUDED. SIZE EQUIPMENT
 AND OCP AS NEEDED. NEC 220, 215.2, 215.3, 408.30
 8. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE TO
 CONFIRM THAT THE SERVICE IS NOT OVERLOADED. WHILE THE
 OTHER SPACE IS STATED AS BEING VACANT, IF IT IS USED IN
 THE FUTURE THIS COULD BE A PROBLEM. OUT OF THE
 AVAILABLE 400 AMP SERVICE, APPROXIMATELY 300 AMPS ARE
 REQUIRED FOR THIS TENANT. PROVIDE FULL LOAD
 CALCULATION, UPGRADE SERVICE IF NECESSARY. NEC 220,
 230.31, FBC 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-22 Cont ID  
Sent By jleahy Date 2017-06-22 Time 18:07 Rev Time 0.00
Received By jleahy Date 2017-06-22 Time 17:59 Sent To  
Notes
2017-06-22 18:06:52CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 C405.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND
 C405.2.4.
  
 C405.2.1 MANUAL LIGHTING CONTROLS.
 ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS
 THAT MEET THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND
 C405.2.1.2.
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR
 THE LIGHTING SERVING THAT AREA. THE REQUIRED CONTROLS
 SHALL BE LOCATED WITHIN THE AREA SERVED BY THE CONTROLS
 OR BE A REMOTE SWITCH THAT IDENTIFIES THE LIGHTS SERVED
 AND INDICATES THEIR STATUS.
  
 C405.2.2.2 OCCUPANCY SENSORS.
 OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND
 JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET
 (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING HEIGHT
 PARTITIONS. THESE AUTOMATIC CONTROL DEVICES SHALL BE
 INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30
 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL
 EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO
 AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50
 PERCENT POWER.
  
 EXCEPTION: FULL AUTOMATIC-ON CONTROLS SHALL BE
 PERMITTED TO CONTROL LIGHTING IN PUBLIC CORRIDORS,
 STAIRWAYS, RESTROOMS, PRIMARY BUILDING ENTRANCE AREAS
 AND LOBBIES, AND AREAS WHERE MANUAL-ON OPERATION WOULD
 ENDANGER THE SAFETY OR SECURITY OF THE ROOM OR BUILDING
 OCCUPANTS
  
 NO OUTLETS SHOWN ON DRAWINGS
  
 FAULT CURRENT CALCULATION REQUIRED PER 110.21
  
 A/C EQUIPMENT SHOWN BUT NO ELECTRIC.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-07-17 Cont ID  
Sent By pleduc Date 2017-07-17 Time   Rev Time 0.00
Received By pleduc Date 2017-07-17 Time 13:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-19 Cont ID  
Sent By pleduc Date 2017-06-19 Time   Rev Time 0.00
Received By pleduc Date 2017-06-19 Time 13:04 Sent To  
Notes
2017-06-19 14:06:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 3.01 - ON THE WAY TO THE FRONT EXIT DOOR,
 THERE IS A SPACE TO GO THROUGH BETWEEN DISPLAY 8 & 6 ON
 THE DIAGONAL. THE DIMENSION OF THIS DIAGONAL SPACE IS
 NOT INDICATED AND SHALL MEET THE MINIMUM REQUIREMENTS
 OF THE CODE.
  
 NFPA 101 CHAPTER 7 MEANS OF EGRESS
  
 7.3.4 MINIMUM WIDTH.
 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS
 OTHERWISE PROVIDED IN 7.3.4.1.1 THROUGH 7.3.4.1.3,
 SHALL BE AS FOLLOWS:
 (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS
 COMPONENT IN THIS CHAPTER OR CHAPTERS 11 THROUGH 43
 (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF
 THIS CHAPTER AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY
 A MINIMUM WIDTH
  
  
 NFPA 101 CHAPTER 36, NEW MERCANTILE
  
 36.2.5.5 REQUIRED AISLES SHALL BE NOT LESS THAN 36 IN.
 (915 MM) INCLEAR WIDTH.
  
  
 PLEASE PROVIDE THE APPLICABLE DIMENSION AND ENSURE THAT
 IT MEETS THE MINIMUM REQUIRMENTS AT ALL TIMES.
  
  
  
  
 2) SHEET A 3.01 - THERE IS A NEW DOOR INDICATED LEADING
 TO THE VESTIBULE. THERE IS NO DOOR SCHEDULE FOR THIS
 DOOR INCLUDING, BUT NOT LIMITED TO, EXIT HARDWARE. ALL
 OTHER DOORS ARE ALSO NOT ACCOUNTED FOR ON A DOOR
 SCHEDULE.
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND
 TO THE SPECIAL REQUIREMENTS OF 7.2.1.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18
 THROUGH 23.
  
  
 PLEASE REIVEW AND PROVIDE A DETAILED DOOR SCHEDULE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-02 Cont ID  
Sent By shill Date 2017-08-02 Time 11:47 Rev Time 0.00
Received By shill Date 2017-07-26 Time 16:36 Sent To  
Notes
2017-07-27 16:37:26B05

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-21 Cont ID  
Sent By jpearson Date 2017-07-21 Time 15:01 Rev Time 0.00
Received By jpearson Date 2017-07-10 Time 10:08 Sent To  
Notes
2017-07-12 10:08:45B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-23 Cont ID  
Sent By jwitmer Date 2017-06-23 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2017-06-14 Time 11:35 Sent To  
Notes
2017-06-16 11:35:47B05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-06-23 Cont ID  
Sent By jwitmer Date 2017-06-23 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2017-06-23 Time 09:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-08-01 Cont ID  
Sent By ccole Date 2017-08-01 Time 12:45 Rev Time 0.00
Received By ccole Date 2017-08-01 Time 12:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-07-19 Cont ID  
Sent By ccole Date 2017-07-19 Time 17:32 Rev Time 0.00
Received By ccole Date 2017-07-19 Time 13:37 Sent To  
Notes
2017-07-19 17:44:542ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17060677
 7/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY REQUESTED PLEASE PROVIDE AN AHRI
 CERTIICATE FOR THE NEW 15 TON SYSTEM- SECTION C101.4.7
 FBC-14 ENERGY CONSERVATION.
  
 2) SHEET M1.01: THE O/A INTAKE OPENING FOR THE
 MECHANCIAL ROOM IS NOT IN COMPLIANCE WITH SECTION 401.4
 (2) WHICH SPECIFIES A MINIMUM 10' CLEARANCE DISTANCE
 FROM THE PARKING LOT AREA.
  
 3) M1.01: THE 9" FLEX DUCT SUPPLYING THE TWO 250 CFM
 DIFFUSERS OVER THE DISPLAY BOX 2 AREA IS UNDERSIZED AT
 1.0 W.G PRESSURE. PLEASE UPSIZE THE DUCT TO MINIMUM 10"
 DIAMETER.
  
 4) M2.01: PLEASE ADD THE 0.6 CFM/SF CALCULATION TO THE
 TORAL REQUIRED CFMS OF O/A FOR THE SHOWROOM- TABLE
 403.3.
  
 4) A5.01: INDICATE HOW THE CONDENSER WILL BE ANCHORED
 TO THE NEW SUPPORT STEEL- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By ccole Date 2017-06-21 Time 12:47 Rev Time 0.00
Received By ccole Date 2017-06-21 Time 12:47 Sent To  
Notes
2017-06-21 13:25:201ST REVIEW FBC-2014 MECHANICAL, EXISTING, ENERGY
 CONSERVATION CODES.
 PERMIT #17060677
 6/21/17
  
 1) SUBMIT TWO COPIES OF THE DEVELOPMENT SERVICES
 DEPARTMENT AC CHANGEOUT FORM FOR THE REPLACED 15-TON
 AIR HANDLER AND THE TWO 6-TON CONDENSER UNITS.
  
 2) REFER TO SECTION C101.4.7 EXCEPTIONS FBC-14 ENERGY
 CONSERVATION: MATCHING SYSTEMS ARE REQUIRED FOR
 REPLACEMENT OF THE 15-TON SYSTEM AND THE MATCH MUST BE
 VERIFIED BY ANYONE OF THE FOLLOWING MEANS: A) AHRI
 CERTIFICATE B) ACCREDITTED LABORATORY C) MANUFACTURER'S
 LETTER D) LETTER FROM A FL. REGISTERED PROFESSIONAL
 ENGINEER.
  
 3) MECHANICAL PLAN M3.01: PROVIDE AN AC EQUIPMENT
 SCHEDULE ON THE PLAN.
  
 4) M3.01: INDICATE THE TYPE OF RETURN AIR DOOR TO BE
 INSTALLED AT THE MECHANICAL/ELECTRICAL ROOM. PLEASE
 NOTE THAT THE DOOR SHALL BE NON-COMBUSTIBLE PER SECTION
 C403.2.7.2 FBC-14 ENERGY CONSERVATION, AND SECTION 602
 FBC-14 MECHANICAL. PLEASE REVIEW ALL SUB-SECTIONS OF
 SECTION 602 FOR ALL MATERIALS ALLOWED TO BE IN THE
 PLENUM INCLUDING ELECTRICAL EQUIPMENT AND WIRING, FOAM
 PLASTIC ETC. PLEASE NOTE THAT NO FUEL-FIRED APPLIANCES
 OR EQUIPMENT ARE PERMITTED TO BE LOCATED IN THE ROOM-
 SECTION 602.1.
  
 5) M3.01: REFER TO SECTION 606.2.1 FBC-14 MECHANICAL
 AND SHOW THE LOCATION(S) OF THE REQUIRED SMOKE
 DETECTOR(S) IN THE MECHANICAL ROOM.
  
 6) M3.01: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 7) A3.01 & M3.01: THE TWO NEW OFFICES 102, AND
 EXECUTIVE OFFICE102 ROOMS BEING CREATED WILL REQUIRE
 RETURN AIR TO ACHIEVE BALANCED AIR FOR THE SYSTEM-
 SECTION 601.5. PLEASE PROVIDE DETAILS AND INDICATE THE
 AMOUNT OF SUPPLY CFMS AT EACH DIFFUSER LOCATION IN THE
 NEW ROOMS. IT MAY BE HELPFUL FOR THE DESIGN
 PROFESSIONAL TO ASSIGN DIFFERENT ROOM NUMBERS TO EACH
 OF THE THREE OFFICES.
  
 8) M3.01: PROVIDE EXHAUST VENTILATION FOR THE NEW
 TOILET ROOMS- TAVBLE 403.3.
  
 9) SHOW THE LOCATIONS OF THE NEW 6-TON CONDENSERS AND
 PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION- SECTION
 301.15 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-20 Cont ID  
Sent By gjohnson Date 2017-07-20 Time 16:55 Rev Time 0.00
Received By gjohnson Date 2017-07-20 Time 13:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-23 Cont ID  
Sent By gjohnson Date 2017-06-23 Time 07:17 Rev Time 0.00
Received By gjohnson Date 2017-06-21 Time 15:44 Sent To  
Notes
2017-06-23 07:25:421ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DETAILED SCOPE OF PLUMBING WORK THE
 RISERS ON THE PLUMBING PAGE ARE UNCLEAR TWO OF THE
 RISERS ARE LABELED NEW ADA BATH BUT NO NEW BATHROOM IS
 SHOWN ON THE FLOOR PLAN. ANOTHER RISER SHOWS TWO NEW
 LAVS BUT NONE SHOWN ON FLOOR PLAN PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 2. ANY NEW SINKS INCLUDING BREAKROOM SINKS SHALL COMPLY
 WITH. FBC ACC 606.2 AND 606.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  