Plan Review Details - Permit 17060676
Plan Review Stops For Permit 17060676
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-17 Cont ID  
Sent By tmoore Date 2017-07-17 Time 08:08 Rev Time 0.00
Received By tmoore Date 2017-07-17 Time 08:07 Sent To  
Notes
2017-07-17 08:08:34OK TO ISSUE WITH FEES PAID. NOW HAVE ALL NEEDED
 RELEASES. TM

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-06 Cont ID  
Sent By tmoore Date 2017-07-06 Time 08:54 Rev Time 0.00
Received By tmoore Date 2017-07-06 Time 08:52 Sent To  
Notes
2017-07-06 08:54:17MR. MAUNEY,
 I RECEIVED YOUR E-MAILS, PRINTED OUT THE ATTACHMENTS,
 AND ADDED THEM TO YOUR APPLICATION. AS THEY RELATE TO
 YOUR COMMENTS BELOW, LET ME ADDRESS THE QUESTIONS.
  
 1) ASSUMING YOU DID NOT FILL OUT AND FAX THE WATER
 DEPARTMENT REQUEST FORM TO PULL THE WATER METER AND
 MARK THE SEWER LATERAL, I DID THAT FOR YOU THIS
 MORNING. YOU ARE REQUIRED TO KEEP THE DEMO WET. UNLESS
 YOU BRING WATER OR ARE GIVEN WATER FROM A NEIGHBOR, YOU
 WILL NEED A HYDRANT METER/BACKFLOW OR A PERMANENT
 BACKFLOW AND METER INSTALLED. EITHER WAY THE DEMO MUST
 BE KEPT WET, AND THE BACKFLOW INSTALLATION REQUIRES A
 PERMIT.
  
 2) I SEE NO PERMIT PULLED FOR CAPPING THE SEWER
 LATERAL. YOUR PLUMBING CONTRACTOR MUST COME IN AND
 APPLY FOR IT ON OUR PERMIT APPLICATION FORM. THIS CAN
 BE FILLED OUT HERE OR FOUND ON LINE.
  
 3) RECEIVED COPY, OK.
  
 4) FPL CONFIRMATION RECEIVED. OK
  
 5) FPU CONFIRMATION RECEIVED. OK
  
 6) DEBRIS DISPOSAL COPY RECEIVED. OK
  
 7) NOC COPY RECEIVED. OK
  
 8) IF THE HOUSE IS YOUR PRIMARY RESIDENCE YOU CAN APPLY
 FOR PERMIT AS AN OWNER BUILDER FILLING OUT THE OWNER
 BUILDER DISCLOSURE STATEMENT, SECTION 489.103 OF THE
 FLORIDA STATUTES. YOU WILL WIL BE ASKED TO SHOW YOUR
 DRIVER LICENSE TO PROVE YOUR PRIMARY RESIDENCE. THIS
 WAS IMPLIED IN OUR PHONE CONVERSATION.
 IF NOT A LICENSED DEMO CONTRACTOR WILL BE NEEDED. THEY
 WILL FILL OUT THE APPLICATION.
  
 AS SOON AS YOU COMPLETE THESE ITEMS, I CAN ISSUE THE
 PERMIT.
  
 THANKS, TOM M. 561-805-6669
  
  
  
  
 TOM,
  
 PLEASE COMMENT ON THE FOLLOWING ITEMS SO I CAN GET THE
 HOUSE DEMOLISHED ASAP.
  
 THANKS,
 TERRY MAUNEY
  
 1) SUBMIT TO UTILITIES, ON THEIR FORM, A REQUEST TO
 PULL THE METER AND MARK THE SEWER LATERAL LOCATION. IF
 IT IS DESIRED THAT THE METER BE KEPT FOR OTHER UNITS ON
 THE PROPERTY THAN THE PROPOSED DEMOLITION CAN BE
 ISOLATED AND A BACK FLOW INSTALLED. THIS REQUIRES AN
 APPLICATION AS THE TYPE OF BACKFLOW USED IS REGULATED.
  
 THE METER IS NOT NEEDED FOR NOW. I WANT TO KEEP THINGS
 SIMPLE AND DEMO THE BUILDING ASAP.
  
 2) A TURN-A-ROUND PERMIT WILL BE NEEDED TO CAP THE
 SEWER LATERAL OF THE FRONT HOUSE. AFTER THE LATERAL IS
 CAPPED A FINAL INSPECTION WILL BE NEEDED TO BE
 REQUESTED AND PASSED. THIS PERMIT WILL NEED TO BE
 PULLED BY A PLUMBING CONTRACTOR.
  
 PLEASE EMAIL A FORM FOR THE TURN-A-ROUND PERMIT.
  
 3) A RODENT LETTER FROM A RECOGNIZED PEST CONTROL
 COMPANY. THEY WILL INSPECT AND IF RODENTS ARE FOUND
 TREAT FOR THEM. THEY WILL THEN PROVIDE A LETTER
 CONFIRMING NO RODENTS ARE LEFT ON PROPERTY AND A COPY
 OF THIS WILL BE INCLUDED IN THE APPLICATION.
  
 PLEASE CONFIRM THAT RODENT LETTER I EMAILED IS
 SUFFICIENT FOR THE DEMO PERMIT.
  
 4) CONFIRMATION FROM F.P.L. THAT POWER HAS BEEN CUT.
 THEIR SERVICE DROP WILL ALSO NEED TO BE REMOVED.
  
 PLEASE CONFIRM THAT THE FPL LETTER I EMAILED IS
 SUFFICIENT THE DEMO PERMIT.
  
 5) CONFIRMATION FROM F.P.U. THAT GAS HAS BEEN CUT TO
 THE PROPOSED DEMO.
  
 PLEASE CONFIRM THAT THE FPU LETTER I EMAILED IS
 SUFFICIENT THE DEMO PERMIT.
  
 6) A DEBRIS DISPOSAL FORM WILL NEED TO BE FILLED OUT AT
 PICK UP. A SMALL FEE WILL BE ASSOCIATED WITH THAT FORM.
  
 PLEASE EMAIL THE DISPOSAL FORM.
  
 7) A N.O.C. COPY WILL NEED TO BE ON FILE.
  
 PLEASE EMAIL THE N.O.C FORM.
  
 8) THIS PROPERTY IS COMMERCIAL RENTAL PROPERTY AND NOT
 USED FOR PERSONAL USE. IT MUST BE DEMOLISHED BY A
 LICENSED CONTRACTOR
  
 A LICENSED CONTRACTOR WILL BE RETAINED TO DEMOLISH THE
 HOUSE.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By tmoore Date 2017-06-21 Time 07:24 Rev Time 0.00
Received By tmoore Date 2017-06-21 Time 07:05 Sent To  
Notes
2017-06-21 07:24:16APPLICATION SUBMITTED WITH NO UTILITY RELEASES. FOR
 DEMO PERMIT TO BE ISSUED THE FOLLOWING MUST BE
 COMPLETED.
  
 1) SUBMIT TO UTILITIES, ON THEIR FORM, A REQUEST TO
 PULL THE METER AND MARK THE SEWER LATERAL LOCATION. IF
 IT IS DESIRED THAT THE METER BE KEPT FOR OTHER UNITS ON
 THE PROPERTY THAN THE PROPOSED DEMOLITION CAN BE
 ISOLATED AND A BACK FLOW INSTALLED. THIS REQUIRES AN
 APPLICATION AS THE TYPE OF BACKFLOW USED IS REGULATED.
  
 2) A TURN-A-ROUND PERMIT WILL BE NEEDED TO CAP THE
 SEWER LATERAL OF THE FRONT HOUSE. AFTER THE LATERAL IS
 CAPPED A FINAL INSPECTION WILL BE NEEDED TO BE
 REQUESTED AND PASSED. THIS PERMIT WILL NEED TO BE
 PULLED BY A PLUMBING CONTRACTOR.
  
 3) A RODENT LETTER FROM A RECOGNIZED PEST CONTROL
 COMPANY. THEY WILL INSPECT AND IF RODENTS ARE FOUND
 TREAT FOR THEM. THEY WILL THEN PROVIDE A LETTER
 CONFIRMING NO RODENTS ARE LEFT ON PROPERTY AND A COPY
 OF THIS WILL BE INCLUDED IN THE APPLICATION.
  
 4) CONFIRMATION FROM F.P.L. THAT POWER HAS BEEN CUT.
 THEIR SERVICE DROP WILL ALSO NEED TO BE REMOVED.
  
 5) CONFIRMATION FROM F.P.U. THAT GAS HAS BEEN CUT TO
 THE PROPOSED DEMO.
  
 6) A DEBRIS DISPOSAL FORM WILL NEED TO BE FILLED OUT AT
 PICK UP. A SMALL FEE WILL BE ASSOCIATED WITH THAT FORM.
  
 7) A N.O.C. COPY WILL NEED TO BE ON FILE.
  
 8) THIS PROPERTY IS COMMERCIAL RENTAL PROPERTY AND NOT
 USED FOR PERSONAL USE. IT MUST BE DEMOLISHED BY A
 LICENSED CONTRACTOR
  
 WHEN THESE ITEMS HAVE BEEN COMPLETED, PLEASE PROVIDE TO
 THE BUILDING DEPARTMENT TO BE ADDED TO APPLICATION.
 THE APPLICATION WILL BE FILED IN THE SMALL PLAN CABINET
 UNDER "M" FOR MAUNEY. FOR ANY QUESTIONS, FEEL FREE TO
 CALL TOM AT 805-6669.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-06-20 Cont ID  
Sent By hhall Date 2017-06-20 Time 10:12 Rev Time 0.00
Received By hhall Date 2017-06-20 Time 10:11 Sent To B
Notes
2017-06-20 10:12:39PASSED - NO UTILITY CONFLICTS
 ADDRESS HISTORICAL COMMENTS

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-06-16 Cont ID  
Sent By cpuell Date 2017-07-13 Time 12:54 Rev Time 0.00
Received By destabro Date 2017-06-16 Time 14:48 Sent To ENG
Notes
2017-06-16 14:49:376/16/2017 - ALTHOUGH OF HISTORIC AGE, THIS PROPERTY IS
 NOT LOCATED IN A HISTORIC DISTRICT OR PROTECTED BY
 INDIVIDUAL DESIGNATION. PERMIT IS MISSING NECESSARY
 UTILITIES AND PEST CONTROL CHECK SHEETS, AND DEBRIS
 REMOVAL FORMS.DLE
2017-06-15 14:27:44ROUTED TO DESIREE ESTABROOK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cpuell Date 2017-07-12 Time 12:55 Sent To  
Notes
2017-07-13 12:55:54TMOORE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-13 Cont ID  
Sent By cpuell Date 2017-07-13 Time 12:54 Rev Time 0.00
Received By cpuell Date 2017-06-14 Time 11:01 Sent To HIST
Notes
***NONE***