Plan Review Details - Permit 17060666
Plan Review Stops For Permit 17060666
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-24 Cont ID  
Sent By cthroop Date 2018-03-24 Time 14:13 Rev Time 0.00
Received By cthroop Date 2018-03-24 Time 10:42 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-05 Cont ID  
Sent By cthroop Date 2018-01-05 Time 11:30 Rev Time 0.00
Received By cthroop Date 2018-01-04 Time 10:28 Sent To  
Notes
2018-01-05 11:52:52BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SEPERATE PERMIT REQUIRED FOR CABANA. NO REVIEW
 PERFORMED ON CABANA AT THIS TIME. THIS REVIEW (2ND) IS
 FOR THE MAIN RESIDENCE ONLY. THE VALUE MAY BE
 PROPORTIONED BETWEEN STRUCTURES.
 2. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 3. PROVIDE SITE DRAINAGE PLAN.
 4. PLANS FOR CONCRETE FLOOR SYSTEM TO BE SIGNED AND
 SEALED BY DESIGN PROFESSIONAL.
 5. PROVISO - SHORING ENGINEER TO INSPECT AND APPROVE IN
 WRITING THE SHORING OF ELEVATED DECK.
 6. ENERGY SUBMITTAL INCLUDES INFORMATION FOR BOTH
 STRUCTURES. A SEPERATE ENERGY SUBMITTAL IS REQUIRED FOR
 EACH STRUCTURE.
 7. NOA 15-0122.04 FOR HARDIE PLANK HAS EXPIRED. PROVIDE
 CURRENT NOA.
 8. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 BBQ GRILL.
 9. STATE FINISHED FLOOR ELEVATION ON PLANS.
 10. SITE PLAN SHOWS PROPERTY IS LOCATED ON CORTEZ ROAD.
 PROPERTY IS LOCATED ON POTTER ROAD.
 11. SELECT ICYNENE PRODUCT TO ACHIEVE THE R-30 RATING.
 MANUFACTURERS INSTALLATION INSTRUCTIONS TO BE ON-SITE
 AT TIME OF INSTALLATION/INSPECTION.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NON-PRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By cthroop Date 2017-07-19 Time 16:39 Rev Time 0.00
Received By cthroop Date 2017-07-19 Time 11:29 Sent To M
Notes
2017-07-19 17:01:45BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SEPERATE PERMIT REQUIRED FOR DETACHED GARAGE.
 SEPERATE PLANS NOT REQUIRED. THE FOLLOWING COMMENTS ARE
 FOR THE MAIN RESIDENCE ONLY.
 2. IMPACT FEES REQUIRED.
 3. PROVIDE SITE DRAINAGE PLAN.
 4. DESIGN CRITERIA ON PLAN PAGE 2 OF 7 REFERENCES THE
 2010 FBC. CURRENT CODE IS 2014 FBC 5TH ED.
 5. PROVIDE SHOP DRAWINGS, SIGNED AND SEALED BY DESIGN
 PROFESSIONAL FOR PRE-ENGINEERED CONCRETE FLOOR SYSTEM.
 6. PROVIDE ICC-ES REPORT (ESR-1826) FOR PROPOSED
 ICYNENE INSULATION. DESIGNER TO SELECT SYSTEM TO BE
 USED. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTION
 ON-SITE AT TIME OF INSPECTION.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 FBC-110.7 IMPACT OF CONSTRUCTION. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 SUPPLY A DRAINAGE DESIGN
  
 GOVERNING CODES
 2014 FLORIDA BUILDING CODE 5TH ED W/2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1 ADMINISTRATION
  
 R402.1.1 INSULATION AND FENESTRATION CRITERIA.
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF TABLE R402.1.1 BASED ON THE CLIMATE
 ZONE SPECIFIED IN CHAPTER 3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-03-15 Cont ID  
Sent By jpearson Date 2018-03-15 Time 13:23 Rev Time 0.00
Received By jpearson Date 2018-03-15 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-01-03 Cont ID  
Sent By jpearson Date 2018-01-03 Time 15:54 Rev Time 0.00
Received By jpearson Date 2018-01-03 Time 15:53 Sent To  
Notes
2018-01-03 15:53:55CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS: PREVIOUS COMMENT NOT
 ADDRESSED SATISFACTORILY HAVE FURTHER COMMENTS IN
 PARENTHESES. COMMENTS CORRECTED ARE NOTED.
  
 1. CORRECTED.
 2. CORRECTED.
 3. #6 GROUNDING ELECTRODE CONDUCTOR SHOWN FROM PANEL B
 TO CWP IS INCORRECT IN SIZE AND LOCATION. GEC MUST BE
 SIZED PER NEC 250.66. ADDITIONALLY, ALL GROUNDING
 ELECTRODES PRESENT MUST BE BONDED TOGETHER, NOT JUST
 THE CWP. NEC 250.50; FBC RE3608.1 (GROUNDING ELECTRODE
 SYSTEM IS ESTABLISHED AT THE MAIN SERVICE, WHICH IS
 LOCATED ON THE SIDE OF THE GARAGE. THE ONLY OTHER
 LOCATION FOR A GROUNDING ELECTRODE WOULD BE AT A
 SEPARATE STRUCTURE. PROVIDE CORRECTION.)
 4. PROVIDE FEEDER INFORMATION, WIRE AND BREAKER SIZE
 FOR PANEL C. NEC 215.5 (NOT PROVIDED. ADDITIONALLY, NO
 LOAD FOR PANEL C IS SHOWN IN THE PANEL SCHEDULE FOR
 PANEL B. PROVIDE CORRECTION.)
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3 (NOT SHOWN ON PLAN.)
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. GARAGE BUILDING, 2ND FLOOR BEDROOM DOES NOT SHOW A
 SMOKE ALARM. ADDITIONALLY, THE COMBO SMOKE/CO ALARM IS
 REQUIRED TO BE WITHIN 10 FEET OF BEDROOM. ADDITIONALLY,
 A SMOKE ALARM IS REQUIRED ON EACH LEVEL OF THE BUILDING
 AND THERE IS NOT ONE SHOWN ON 1ST FLOOR PLAN. PROVIDE
 CORRECTION. FBC R314, R315 (NOT PROVIDED, A NOTE IS NOT
 SUFFICIENT.)
 11. GARAGE BUILDING, BEDROOM CLOSET SHOWS A RECESS
 LIGHT. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS
 AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOSETS. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12 (STATING THAT LED LIGHTS WILL
 BE USED IS NOT SUFFICIENT AS MANY LED LIGHTS HAVE OPEN
 BULBS. PROVIDE CORRECTION AS PREVIOUSLY REQUESTED.)
 12. MASTER CLOSETS SHOW RECESS LIGHTS. LIGHTING WITH
 OPEN OR PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES
 OR LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS.
 PROVIDE CORRECTION. NEC 410.16(B), FBC RE4003.12
 (STATING THAT LED LIGHTS WILL BE USED IS NOT SUFFICIENT
 AS MANY LED LIGHTS HAVE OPEN BULBS. PROVIDE CORRECTION
 AS PREVIOUSLY REQUESTED.)
 13. MASTER BATH SHOWS A RECESS LIGHT ABOVE TUB.
 LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE
 FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(A),
 FBC RE4003.11 (CORRECTION NOT PROVIDED. LIGHTING ABOVE
 TUB MUST BE VAPOR ROOF. PROVIDE AS REQUESTED.)
 14. OUTDOOR RECESS LIGHTS IN PORCH AND COVERED WALKWAY
 AREAS ARE REQUIRED TO BE SUITABLE FOR DAMP LOCATIONS.
 PROVIDE NOTE TO COMPLY. NEC 410.10(A), FBC RE4003.11
 (NOT PROVIDED.)
  
 NEW COMMENTS:
 15. NOTE UNDER RECESS LIGHTS STATES THAT 50% OF
 LIGHTING SHALL BE HIGH EFFICIENCY. PROVIDE COMPLIANCE:
 "A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1
 16. PLEASE BE ADVISED THAT SOME OF THE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: ?WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-30 Cont ID  
Sent By jpearson Date 2017-06-30 Time 08:27 Rev Time 0.00
Received By jpearson Date 2017-06-30 Time 08:05 Sent To  
Notes
2017-06-30 09:15:44CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE GROUNDING ELECTRODE SYSTEM FOR MAIN HOUSE AS
 REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED BY A
 FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3
 2. #6 GROUNDING ELECTRODE CONDUCTOR SHOWN FROM PANEL A
 TO CWP IS INCORRECT IN SIZE AND LOCATION. ALL GROUNDING
 ELECTRODE CONDUCTORS MUST ATTACH TO THE GROUNDED
 SERVICE CONDUCTOR ON THE SUPPLY SIDE OF THE SERVICE AND
 SHALL BE SIZED PER NEC 250.66. NEC 250.64(D)(3); FBC
 RE3607.1
 3. #6 GROUNDING ELECTRODE CONDUCTOR SHOWN FROM PANEL B
 TO CWP IS INCORRECT IN SIZE. GEC MUST BE SIZED PER NEC
 250.66. ADDITIONALLY, ALL GROUNDING ELECTRODES PRESENT
 MUST BE BONDED TOGETHER, NOT JUST THE CWP. SEE COMMENT
 #1 ALSO. NEC 250.50; FBC RE3608.1
 4. PROVIDE FEEDER INFORMATION, WIRE AND BREAKER SIZE
 FOR PANEL C. NEC 215.5
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 6. PANEL B, CIRCUITS 2,4 AND 6,8 AND 10,12 SHOW A #6
 ROMEX WIRE ON A 60 AMP BREAKER. #6 WIRE IS NOT RATED
 FOR 60 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC
 RE3705.4.4
 7. PANEL C, CIRCUIT 2,4 SHOW A #6 ROMEX WIRE ON A 60
 AMP BREAKER. #6 WIRE IS NOT RATED FOR 60 AMPS. PROVIDE
 CORRECTION. NEC 334.80; FBC RE3705.4.4
 8. NOTE ON RISER DIAGRAM STATES "PER 2008 NEC". CORRECT
 TO CURRENT CODE, 2011 NEC. FBC PREFACE
 9. PROVIDE 20 AMP CIRCUIT FOR BATH GFCI OUTLETS. A
 MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. NEC 210.11(C)(3)
 , FBC RE3703.4
 10. GARAGE BUILDING, 2ND FLOOR BEDROOM DOES NOT SHOW A
 SMOKE ALARM. ADDITIONALLY, THE COMBO SMOKE/CO ALARM IS
 REQUIRED TO BE WITHIN 10 FEET OF BEDROOM. ADDITIONALLY,
 A SMOKE ALARM IS REQUIRED ON EACH LEVEL OF THE BUILDING
 AND THERE IS NOT ONE SHOWN ON 1ST FLOOR PLAN. PROVIDE
 CORRECTION. FBC R314, R315
 11. GARAGE BUILDING, BEDROOM CLOSET SHOWS A RECESS
 LIGHT. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS
 AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOSETS. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12
 12. MASTER CLOSETS SHOW RECESS LIGHTS. LIGHTING WITH
 OPEN OR PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES
 OR LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS.
 PROVIDE CORRECTION. NEC 410.16(B), FBC RE4003.12
 13. MASTER BATH SHOWS A RECESS LIGHT ABOVE TUB.
 LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE
 FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(A),
 FBC RE4003.11
 14. OUTDOOR RECESS LIGHTS IN PORCH AND COVERED WALKWAY
 AREAS ARE REQUIRED TO BE SUITABLE FOR DAMP LOCATIONS.
 PROVIDE NOTE TO COMPLY. NEC 410.10(A), FBC RE4003.11
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-07-05 Cont ID  
Sent By gjohnson Date 2017-07-05 Time 13:39 Rev Time 0.00
Received By gjohnson Date 2017-07-05 Time 13:39 Sent To  
Notes
2017-07-05 13:40:36GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-26 Cont ID  
Sent By hmoser Date 2018-03-26 Time 10:40 Rev Time 0.00
Received By hmoser Date 2018-02-20 Time 14:29 Sent To  
Notes
2018-02-21 14:29:43R41

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-23 Cont ID  
Sent By hmoser Date 2018-01-23 Time 14:39 Rev Time 0.00
Received By hmoser Date 2017-12-15 Time 17:49 Sent To  
Notes
2017-12-18 17:50:30R41

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-20 Cont ID  
Sent By hmoser Date 2017-07-20 Time 15:04 Rev Time 0.00
Received By hmoser Date 2017-06-14 Time 12:31 Sent To  
Notes
2017-06-15 12:32:02R41

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-03-24 Cont ID  
Sent By cthroop Date 2018-03-24 Time 11:41 Rev Time 0.00
Received By cthroop Date 2018-03-24 Time 10:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-01-05 Cont ID  
Sent By cthroop Date 2018-01-05 Time 11:22 Rev Time 0.00
Received By cthroop Date 2018-01-04 Time 10:28 Sent To  
Notes
2018-01-05 11:23:06BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By cthroop Date 2017-07-19 Time 16:36 Rev Time 0.00
Received By cthroop Date 2017-07-19 Time 11:29 Sent To  
Notes
2017-07-19 16:37:51BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-03-26 Cont ID  
Sent By hmoser Date 2018-03-26 Time 10:40 Rev Time 0.00
Received By hmoser Date 2018-03-26 Time 09:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-01-23 Cont ID  
Sent By hmoser Date 2018-01-23 Time 14:38 Rev Time 0.00
Received By hmoser Date 2018-01-23 Time 14:34 Sent To I
Notes
2018-01-23 14:38:21PLAN DENIED
 ENERGY CALCULATIONS AND PLAN DO NOT MATCH
 CFM AND SEER. REFER TO SECTION
 107 FBC 2014.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-07-20 Cont ID  
Sent By hmoser Date 2017-07-20 Time 15:04 Rev Time 0.00
Received By hmoser Date 2017-07-20 Time 13:11 Sent To  
Notes
2017-07-20 15:04:08PASS PROVISO
 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 2014RESIDENTIAL CODE
 2) REFER TO SECTION 403.2.4 AIR HANDLER UNITS
 2014 FLORIDA ENERGY CODE
  
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-03-16 Cont ID  
Sent By lcrespo Date 2018-03-16 Time 17:10 Rev Time 0.00
Received By lcrespo Date 2018-03-16 Time 17:10 Sent To  
Notes
2018-03-16 17:12:1203/16/18 APPROVED BY PLUMBING AND PUT BACK IN R41, LAC

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-11 Cont ID  
Sent By thunt Date 2018-01-11 Time 15:21 Rev Time 0.00
Received By thunt Date 2018-01-11 Time 15:21 Sent To  
Notes
2018-01-11 15:22:11PROVISO APPROVAL: PROVIDE A CODE COMPLIANT SANITARY
 RISER DRAWING

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-05 Cont ID  
Sent By gjohnson Date 2017-07-05 Time 11:50 Rev Time 0.00
Received By gjohnson Date 2017-07-05 Time 09:45 Sent To  
Notes
2017-07-05 12:02:501ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1.THE ENERGY CALCULATIONS SHOW A PROPANE TANKLESS
 HEATER OR IS IT A NATURAL GAS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2. THE SOIL STACK FOR SECOND FLOOR IN MAIN HOUSE SHALL
 CONNECT TO BUILDING DRAIN DOWN STREAM OF THE BATHROOM
 GROUP. PER FBC RES P3108.1
  
 3. A CLEAN OUT IS REQUIRED AT THE BASE OF EVERY SOIL
 STACK. PER FBC RES P3005.2.6
  
 4. THE LAUNDRY SINK AND WASHING MACHINE IN MAIN HOUSE
 SHALL BE SHOWN ON THE RISER CONNECTED TO SECOND FLOOR
 PIPING. PER FBC RES P3108.1
  
 5. THE KITCHEN SINK IN THE OUTDOOR KITCHEN SHALL
 CONNECT DOWN STREAM OF THE BATHROOM. PER FBC RES
 P3108.1
  
 6. THE LAV IN THE DOWN STAIRS BATHROOM IN DETACHED
 GARAGE IS NIT VENTED. PER FBC RES P3101.2.1
  
 7. THE WASHING MACHINE UPSTAIRS IN THE DETACHED GARAGE
 IS NOT SHOWN ON THE RISER DIAGRAM PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 8. ISLAND SINK UPSTAIRS IN DETACHED GARAGE SHALL
 CONNECT DOWN STREAM OF THE BATHROOM GROUP. PER FBC RES
 P3108.1
  
 9. PROVIDE ACCESS TO THE SHUT OFF VALVES FOR STACKABLE
 WASHING MACHINES . PER FBC RES P2903.9.3
  
 10. PLEASE SHOW LOCATION OF WATER HEATERS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-07-19 Cont ID  
Sent By cthroop Date 2017-07-19 Time 16:38 Rev Time 0.00
Received By cthroop Date 2017-07-19 Time 11:29 Sent To  
Notes
2017-07-19 16:38:50ROOF PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 3 Status P Date 2018-03-02 Cont ID  
Sent By awooten Date 2018-03-02 Time   Rev Time 0.00
Received By awooten Date 2018-03-02 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-01-18 Cont ID  
Sent By AW Date 2018-01-18 Time 16:04 Rev Time 0.00
Received By awooten Date 2018-01-18 Time   Sent To  
Notes
2018-01-18 16:04:37***********************************ZONING REVIEW
 FAILED**********************************
  
 1. ADDITIONAL/SEPARATE PERMITS ARE REQUIRED FOR FENCES,
 POOLS, POOL EQUIPMENT, LANDSCAPE,
 IRRIGATION AND DRIVEWAY
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. AS PER SECTION
 94-305(B)(4) OF THE ZONING CODE ("ZLDR"): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 3. FOR LANDSCAPING YOU HAVE TWO OPTIONS, YOU CAN SUBMIT
 A SEPARATE LANDSCAPE PERMIT AND IRRIGATION PLAN WITH
 TWO (2) COPIES OF A LANDSCAPE PLAN SHOWING COMPLIANCE
 WITH SECTIONS 94-442 AND 94-445 OF THE ZLDR, OR YOU CAN
 SUBMIT FOR A CONDITIONAL LANDSCAPE APPROVAL
 APPLICATION, IN WHICH YOU WOULD HAVE TO SUBMIT FOR
 LANDSCAPE PERMIT AND PASS THE FINAL LANDSCAPE
 INSPECTION PRIOR TO ISSUSANCE OF CO. FOR THE
 CONDITIONAL LANDSCAPE APPROVAL APPLICATION, PLEASE
 CONTACT ME.
  
 GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS SHALL BE AS FOLLOWS:
  
 A. SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
  
 PLEASE LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 ALANA WOOTEN
 PLANNING AND ZONING
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-17 Cont ID  
Sent By nwira Date 2017-07-17 Time 16:11 Rev Time  
Received By awooten Date 2017-07-17 Time   Sent To  
Notes
2017-07-17 16:11:37***********************************ZONING REVIEW
 FAILED**********************************
  
 1. ADDITIONAL/SEPARATE PERMITS ARE REQUIRED FOR FENCES,
 POOLS, POOL EQUIPMENT, LANDSCAPE,
 IRRIGATION AND DRIVEWAY
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. AS PER SECTION
 94-305(B)(4) OF THE ZONING CODE ("ZLDR"): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 3. PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PLAN WITH TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS SHALL BE AS FOLLOWS:
  
 A. SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
  
 PLEASE LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 ALANA WOOTEN
 PLANNING AND ZONING
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]
  
  
  