Plan Review Details - Permit 17060565
Plan Review Stops For Permit 17060565
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-08-11 Cont ID  
Sent By skennedy Date 2017-08-11 Time 11:58 Rev Time 0.00
Received By skennedy Date 2017-08-11 Time 11:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-29 Cont ID  
Sent By jwitmer Date 2017-06-29 Time 11:17 Rev Time 0.00
Received By jwitmer Date 2017-06-29 Time 11:17 Sent To  
Notes
2017-06-29 11:17:452014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060556 (MASTER)
 TRAVELING TOGETHER 17060559, 17060562, 17060565,
 17060568, 17060571,
 17060574, 17060578, 17060581, 17060584, 17060587,
 17060590, 17060593, 17060596, 17060599, 17060602,
 17060605, 17060608, 17060611, 17060614
  
 ADD: 410 EVERNIA ST. SUITE NUMBER 802
 CONT: URBAN TEAM CONSTRUCTION
 TEL: 305-710-3886
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JUNE 29/2017
 ACTION: DENIED
  
 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
  
  
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
  
 1) 2ND REQUEST THE VALUES STATED ARE EXTREMELY LOW FOR
 THE VALUE STATED AND THE SCOPE OF WORK. 108.3 IS FOR
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT.
 I?VE SPOKEN WITH THE CHIEF PLUMBING INSPECTOR AND FOR
 THE REPLACEMENT OF T FIXTURES, REMOVAL, DISPOSAL, LABOR
 TO BRING THE NEW FIXTURES TO THE TENANT UNIT, UNPACK
 SET AND INSTALL NEW VALVES, SPOUT, HANDLES, SHOWER
 HEADS, PLUS LABOR AND OVERHEAD A MINIMUM OF $2,500.00
 PER UNIT WOULD BE A MINIMUM VALUE WE WOULD ACCEPT WE
 BELIEVE THE ACTUAL VALUE IS $3,500.00 PER UNIT.
 IN REGARDS TO THE VALUE STATED FOR THE REMOVAL &
 INSTALLATION OF LIGHT FIXTURES, THE $25.00 DOLLARS
 STATED IS THE AVERAGE WAGE FOR AN ELECTRICIAN, NOT THE
 VALUE THE CONTRACTOR CHARGES, THE RATE CHARGED CAN BE
 AS HIGH AS $90.00 DEPENDING ON THE COMPLEXITY AND TYPE
 OF JOB. WE WILL USE $75.00 FOR THE AVERAGE RATE FOR AN
 ELECTRICIAN, PLEASE PROVIDE THE CUT SHEETS FOR
 FIXTURES, COST OF THE FIXTURE AND BULB. . FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, PLUMBING,
 MECHANICAL, INTERIOR FINISHES, NORMAL SITE WORK
 (EXCAVATION AND BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT.
  
 1ST ROUND OF COMMENTS. FOR THE SCOPE OF WORK THE VALUE
 OF THE PROJECT IS LOW.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) COMPLIED. PLEASE PROVIDE A FLOOR PLAN OF THE FLOOR
 FINISHES TO BE REPLACE AND WHAT FINISH MATERIALS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) 2ND REQUEST. SAME COMMENT AS THE 1ST REVIEW. THE
 QUALIFIER OF THE COMPANY HAS TO TAKE OWNERSHIP OF THE
 PLANS SUBMITTED UNLESS THE PLANS ARE DESIGNED BY EITHER
 AN ARCHITECT UNDER F. S 481 OR AN ENGINEER UNDER F. S.
 471.
 1ST ROUND OF COMMENTS. THE AUTHOR (QUALIFIER OF
 COMPANY) OF THE FLOOR PLAN IS TO PRINT THEIR NAME, SIGN
 THEIR NAME AND PRINT THEIR LICENSE NUMBER OF THE PLANS
 THEY DREW. 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE
 CHARGE.
 4) 2ND REQUEST. THE SUBMITTED SHAW SUNDRIES GROUND
 WORKS ACOUSTICAL UNDERLAYMENT STYLE 074VS IS A SALES
 BROCHURE LISTING TESTING, NOT THE ACTUAL TEST REPORTS.
 SEE 1ST ROUND OF COMMENTS.
  
 1ST ROUND OF COMMENTS. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 4A) 2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-22 Cont ID  
Sent By jwitmer Date 2017-06-22 Time 15:39 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2017-06-22 15:39:522014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060556 (MASTER)
 TRAVELING TOGETHER 17060559, 17060562, 17060565,
 17060568, 17060571,
 17060574, 17060578, 17060581, 17060584, 17060587,
 17060590, 17060593, 17060596, 17060599, 17060602,
 17060605, 17060608, 17060611, 17060614
  
 ADD: 410 EVERNIA ST. SUITE NUMBER 802
 CONT: URBAN TEAM CONSTRUCTION
 TEL: 305-710-3886
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 22/2017
 ACTION: DENIED
  
 1) FOR THE SCOPE OF WORK THE VALUE OF THE PROJECT IS
 LOW.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 2) PLEASE PROVIDE A FLOOR PLAN OF THE FLOOR FINISHES TO
 BE REPLACE AND WHAT FINISH MATERIALS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
 3) THE AUTHOR (QUALIFIER OF COMPANY) OF THE FLOOR PLAN
 IS TO PRINT THEIR NAME, SIGN THEIR NAME AND PRINT THEIR
 LICENSE NUMBER OF THE PLANS THEY DREW. 107.3.4 DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE.
 4) BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-08-11 Cont ID  
Sent By skennedy Date 2017-08-11 Time 11:58 Rev Time 0.00
Received By skennedy Date 2017-08-11 Time 11:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-08-09 Cont ID  
Sent By jpearson Date 2017-08-09 Time 13:17 Rev Time 0.00
Received By jpearson Date 2017-08-09 Time 13:17 Sent To  
Notes
2017-08-09 13:17:05CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE COPY OF PLAN WAS SUBMITTED. 2 COPIES ARE
 REQUIRED. FBC 107.1
 2. PER CONVERSATION WITH CONTRACTOR, THE PLAN SHOULD
 STATE THAT ALL ELECTRICAL WORK IS EXISTING AND THEY
 SCOPE OF WORK IS TO INSTALL LIGHT FIXTURES ONLY. FBC
 107.2.1
 3. PLAN SHOWS 3 DIFFERENT MODELS, WHICH IS THE LAYOUT
 FOR THIS UNIT? PROVIDE CORRECT LAYOUT AND REMOVE ANY
 SHEETS THAT ARE IRRELEVANT. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-07-05 Cont ID  
Sent By jpearson Date 2017-07-05 Time 14:46 Rev Time 0.00
Received By jpearson Date 2017-07-05 Time 14:46 Sent To  
Notes
2017-07-05 14:46:47CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL 2ND REVIEW COMMENTS:
  
 1. PREVIOUS COMMENT NOT ADDRESSED: "NO ELECTRICAL PLAN
 PROVIDED FOR REVIEW. PROVIDE PLAN SHOWING ALL
 ELECTRICAL WORK". WITH EACH APPLICATION, THERE ARE
 SEVERAL DIFFERENT FLOOR LAYOUTS. REMOVE ANY ITEMS NOT
 RELATED TO THE UNIT IN QUESTION AND PROVIDE ELECTRICAL
 PLAN SHOWING WHICH FIXTURES WILL BE
 REMOVED/REPLACED/INSTALLED. ELECTRICAL PLAN IS REQUIRED
 TO BE SIGNED BY A DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; FBC
 107.3.5
 2. PREVIOUS COMMENT NOT ADDRESSED: "PROVIDE COPY OF
 CONTRACT SHOWING TOTAL COST OF JOB, TO INCLUDE LABOR
 AND MATERIALS". PROVIDING AN UNSIGNED CONTRACT WITH A
 PER FIXTURE PRICE IS NOT ACCEPTABLE. PROVIDE TOTAL
 VALUE OF JOB FOR EACH UNIT, INCLUDING LABOR AND COST OF
 FIXTURES. PROVIDE SPEC SHEET OF LIGHT FIXTURES. NEC
 110.3; FBC 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By jpearson Date 2017-06-21 Time 08:34 Rev Time 0.00
Received By jpearson Date 2017-06-21 Time 08:34 Sent To  
Notes
2017-06-21 08:34:42CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. NO ELECTRICAL PLAN PROVIDED FOR REVIEW. PROVIDE PLAN
 SHOWING ALL ELECTRICAL WORK. FBC 107.3.5
 2. PROVIDE COPY OF CONTRACT SHOWING TOTAL COST OF JOB,
 TO INCLUDE LABOR AND MATERIALS. FBC 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-11 Cont ID  
Sent By skennedy Date 2017-08-11 Time 11:58 Rev Time 0.00
Received By skennedy Date 2017-08-03 Time 15:48 Sent To  
Notes
2017-08-04 15:48:13B27
 **TRAVELLING TOGETHER - 17060556, 17060559, 17060562,
 17060565, 17060568, 17060571, 17060574, 17060578,
 17060581, 17060584, 17060587, 17060590, 17060593,
 17060596, 17060599, 17060602, 17060605, 17060608,
 17060611, 17060614**

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-07 Cont ID  
Sent By gjohnson Date 2017-07-07 Time 15:34 Rev Time 0.00
Received By gjohnson Date 2017-06-23 Time 15:21 Sent To  
Notes
2017-06-26 15:22:03B18
 **TRAVELLING TOGETHER - 17060556, 17060559, 17060562,
 17060565, 17060568, 17060571, 17060574, 17060578,
 17060581, 17060584, 17060587, 17060590, 17060593,
 17060596, 17060599, 17060602, 17060605, 17060608,
 17060611, 17060614**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-22 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-13 Time 11:47 Sent To  
Notes
2017-06-19 11:47:12B14
 **TRAVELLING TOGETHER - 17060556, 17060559, 17060562,
 17060565, 17060568, 17060571, 17060574, 17060578,
 17060581, 17060584, 17060587, 17060590, 17060593,
 17060596, 17060599, 17060602, 17060605, 17060608,
 17060611, 17060614**

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-08-11 Cont ID  
Sent By skennedy Date 2017-08-11 Time 11:58 Rev Time 0.00
Received By skennedy Date 2017-08-11 Time 11:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-07-07 Cont ID  
Sent By gjohnson Date 2017-07-07 Time 15:33 Rev Time 0.00
Received By gjohnson Date 2017-07-07 Time 15:33 Sent To  
Notes
2017-07-07 15:33:452014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060556 (MASTER)
 TRAVELING TOGETHER 17060559, 17060562, 17060565,
 17060568, 17060571,
 17060574, 17060578, 17060581, 17060584, 17060587,
 17060590, 17060593, 17060596, 17060599, 17060602,
 17060605, 17060608, 17060611, 17060614
  
  
 2NDREVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT HAS NOT COMPLIED
  
 2ND REQUEST1. PLEASE PROVIDE FLOOR PLAN AND INDICATE
 PLUMBING WORK ON PLAN. PER WPB AMEND TO FBC 107.2.1
 PROVIDE SCOPE OF PLUMBING WORK WHICH SPECIFIC FIXTURES
 ARE BEING REPLACED , SPECIFY UNIT
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By gjohnson Date 2017-06-21 Time 14:13 Rev Time 0.00
Received By gjohnson Date 2017-06-21 Time 14:13 Sent To  
Notes
2017-06-21 14:14:071ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE FLOOR PLAN AND INDICATE PLUMBING WORK
 ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  