| 2017-06-28 10:29:51 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. PROVIDE 2 COPIES OF PLAN FOR REVIEW. FBC 107.1 |
| | 2. PROVIDE EXISTING FLOOR PLAN SHOWING LOCATION OF ALL |
| | SMOKE/CO ALARMS IN RESIDENCE. IF NONE ARE EXISTING, OR |
| | NOT TO CODE, SHOW AS NEW INSTALLATIONS WITH |
| | INTERCONNECTION AS REQUIRED PER CODE. FBC R314, R315. |
| | FBC 107.2.1 |
| | 3. PROVIDE PANEL SCHEDULE SHOWING ANY NEW OR ALTERED |
| | CIRCUITS, WITH AFCI OR GFCI PROTECTION PER CODE. NEC |
| | 408.4, 215.5; FBC 107.2.1 |
| | 4. PROVIDE SWITCHED LIGHT FOR EXTERIOR DOOR IF NOT |
| | THERE ALREADY (NOT SHOWN ON PLAN). FOR DWELLING UNITS, |
| | ATTACHED GARAGES, AND DETACHED GARAGES WITH ELECTRIC |
| | POWER, AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING |
| | OUTLET SHALL BE INSTALLED ON THE EXTERIOR SIDE OF |
| | OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. NEC |
| | 210.70(A)(2)(B), FBC RE3903.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |