Plan Review Details - Permit 17060447
Plan Review Stops For Permit 17060447
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-14 Cont ID  
Sent By cthroop Date 2017-08-14 Time 14:31 Rev Time 0.00
Received By cthroop Date 2017-08-14 Time 10:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-27 Cont ID  
Sent By cthroop Date 2017-06-27 Time 13:49 Rev Time 0.00
Received By cthroop Date 2017-06-26 Time 08:16 Sent To  
Notes
2017-06-27 14:11:43BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SOILS REPORT.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 2. PROVIDE ENERGY SUBMITTAL PER FBC E103.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 3. DESIGN PROFESSIONALS SEAL MISSING ON PLAN PAGES.
 FBC-107.1 GENERAL - FAC 61G1-16.004 - A TITLE BLOCK
 MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT
 ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED.
 (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO
 BE A CORPORATION, LIMITED LIABILITY COMPANY,
 PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME,
 OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN
 HIS OR HER OWN NAME.
  
 4. PROVIDE ICC-ES REPORT AND MANUFACTURER'S
 INSTALLATION INSTRUCTIONS FOR SPRAY FOAM INSULATION
 W/SPRAY ON IGNITION BARRIER INTUMESCENT COATING.
 R402.1.1 INSULATION AND FENESTRATION CRITERIA.
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF TABLE R402.1.1 BASED ON THE CLIMATE
 ZONE SPECIFIED IN CHAPTER 3.
  
 5. FBC 107.3.5.3 ? INDICATE THE MEANS OF TERMITE
 PROTECTION PROPOSED PURSUANT TO FBC-R318.
 R318.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.?
  
 6. PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTION FOR
 BBQ GRILL.
  
 7. ONLY ONE COPY OF PRODUCT APPROVALS SUBMITTED.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 DEFINED FIELDS - INTERNAL USE ONLY
  
 USC-404 - NEW: SFR DETACHED
 LOT AREA - .38 ACRES
 CONSTRUCTION TYPE - V-B
 UNITS - 1
 FLOORS - 2
 BEDROOMS - 4
 BATHROOMS - 5
 ROOMS - 23
 BUILDING CODE - 2014
 OCC CLASS - 5TH ED R3
 SQUARE FOOTAGE - LIVABLE - 4,120
 SQUARE FOOTIAGE - FOOTPRINT - 5,940
 SQUARE FOOTAGE - ROOF - 5,940
 SETBACKS - FRONT - 25' REAR - 57.5' L - 6.5' R - 12.5'
 OCC LOAD - R3
 PROPOSED USE - SFR LOW DENSITY
 SPRINKLER SYSTEM - NO
 SPRINKLER REQUIRED - NO
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-04 Cont ID  
Sent By jpearson Date 2017-08-04 Time 07:46 Rev Time 0.00
Received By jpearson Date 2017-08-04 Time 07:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-14 Cont ID  
Sent By jpearson Date 2017-06-14 Time 09:38 Rev Time 0.00
Received By jpearson Date 2017-06-14 Time 09:38 Sent To  
Notes
2017-06-14 10:10:32CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PANEL A, CIRCUIT 16 SHOWS A 15 AMP CIRCUIT WITH #14
 WIRE TO THE BATHROOM OUTLETS. PROVIDE CORRECTION. "A
 MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS." NEC 210.11(C)(3)
 , FBC RE3703.4
 2. BASED ON THE INFORMATION PROVIDED ON THE MECHANICAL
 PLAN, THE AHU'S HAVE A 15 KW HEAT STRIP, AND THIS
 CIRCUIT IS FED FROM A 60 AMP BREAKER WITH #6 WIRE. IT
 APPEARS THAT THE WIRE SIZE AND BREAKER SIZE ARE LESS
 THAN THE MINIMUM CIRCUIT AMPACITY REQUIRED. PROVIDE
 CORRECTION. FBC RE3702.7, 3702.11, NEC 440.35
 3. PROVIDE NOTE ON PLAN THAT THE GENERATOR WILL BE
 UNDER SEPARATE PERMIT. FBC 107.2.1
 4. PROVIDE SPEC SHEET FOR 300 AMP TRANSFER SWITCH
 INDICATED AT SERVICE. PROVIDE DETAILS FOR LOAD
 MANAGEMENT PER NEC. NEC 110.3, 702.4(B)(2)
 5. ALTHOUGH GENERATOR WILL BE UNDER SEPARATE PERMIT, IT
 APPEARS THAT THE 3 FOOT CLEARANCE REQUIREMENTS WILL NOT
 BE MET WITH THE CURRENT DESIGN OF THE EQUIPMENT GARAGE.
 PROVIDE CLARIFICATION AND/OR CORRECTION. NEC 110.26
 6. SEVERAL LOCATION ON PLANS SHOW A DECORATIVE SCONCE
 IN CLOSETS. PROVIDE CORRECTION. "LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS." NEC
 410.16(B), FBC RE4003.12
 7. LIGHTING IN "HER MASTER CLOSET" IS SHOWN WITH
 STANDARD RECESS LIGHTS. "LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS". PROVIDE
 CORRECTION. NEC 410.16(B), FBC RE4003.12
 8. SMOKE ALARM REQUIRED AT BOTTOM OF STAIRS. PROVIDE
 CORRECTION. FBC R314.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-09-14 Cont ID  
Sent By cpuell Date 2017-09-14 Time 09:41 Rev Time 0.00
Received By cpuell Date 2017-08-31 Time 10:47 Sent To  
Notes
2017-09-01 10:47:37RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-01 Cont ID  
Sent By lmarchan Date 2017-09-01 Time 10:45 Rev Time 0.00
Received By lmarchan Date 2017-08-01 Time 15:10 Sent To  
Notes
2017-08-02 15:10:44R21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-11 Cont ID  
Sent By hmoser Date 2017-07-11 Time 10:15 Rev Time 0.00
Received By hmoser Date 2017-06-09 Time 15:21 Sent To  
Notes
2017-06-12 15:22:02R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-09-25 Cont ID  
Sent By cthroop Date 2017-09-25 Time 13:03 Rev Time 0.00
Received By cthroop Date 2017-09-25 Time 12:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-06-27 Cont ID  
Sent By cthroop Date 2017-06-27 Time 11:50 Rev Time 0.00
Received By cthroop Date 2017-06-26 Time 08:16 Sent To  
Notes
2017-06-27 11:51:40BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-09-05 Cont ID  
Sent By hmoser Date 2017-09-05 Time 10:10 Rev Time 0.00
Received By hmoser Date 2017-09-05 Time 08:21 Sent To P
Notes
2017-09-05 10:17:31PASS PROVISO
 1) REFER TO SECTION R403.2.4 AIR-HANDLING UNITS
 2014 RESIDENTIAL CODE
 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR.
 2014 RESIDENTIAL CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-28 Cont ID  
Sent By hmoser Date 2017-08-28 Time 10:45 Rev Time 0.00
Received By hmoser Date 2017-08-28 Time 08:50 Sent To  
Notes
2017-08-28 10:50:58PLAN DENIED
 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 2014 RESIDENTIAL CODE.
 2) ENERGY CALCULATIONS AND PLAN DO NOT MATCH
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-11 Cont ID  
Sent By hmoser Date 2017-07-11 Time 10:14 Rev Time 0.00
Received By hmoser Date 2017-07-10 Time 15:07 Sent To  
Notes
2017-07-11 10:14:45PLAN DENIED
 1) PROVIDE ENERGY CALCULATIONS WITH PLAN. PER SECTION
 C403.2 FLORIDA ENERGY CODE 2014
 2) REFER TO SECTION M1602.4 # 1 BALANCED
 RETURN AIR 2014 RESIDENTIAL CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-09-14 Cont ID  
Sent By thunt Date 2017-09-14 Time 07:19 Rev Time 0.00
Received By thunt Date 2017-09-13 Time 14:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-08-17 Cont ID  
Sent By gjohnson Date 2017-08-17 Time 12:14 Rev Time 0.00
Received By gjohnson Date 2017-08-17 Time 11:43 Sent To  
Notes
2017-08-17 12:24:442ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. HORIZONTAL DRY VENTS ARE NOT ALLOWED PLEASE REMOVE
 THEM FROM THE WC IN POWDER ROOM BATH, THE SHOWER IN
 BATH#4 THE WC IN MASTER BATH, THE SHOWER IN BATH #2 AND
 THE WC IN BATH #3. PER FBC RES P3104.3, P3104.4
  
 2.IN BATH #3 THE LAV SHALL CONNECT TO THE BRANCH DRAIN
 BETWEEN THE TUB AND WC TO CREATE A CODE COMPLAINT WET
 VENT SYSTEM PER FBC RES P3108.1
  
 3.IN THE MASTER BATH THE LAV SHALL CONNECT TO THE
 BRANCH DRAIN BETWEEN THE SHOWER AND WC TO CREATE A CODE
 COMPLAINT WET VENT SYSTEM PER FBC RES P3108.1
  
 4. FBC RES P3005.2.6 BASE OF STACKS.
 A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH WASTE
 OR SOIL STACK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-14 Cont ID  
Sent By gjohnson Date 2017-06-14 Time 18:19 Rev Time 0.00
Received By gjohnson Date 2017-06-14 Time 17:15 Sent To M
Notes
2017-06-14 18:21:411ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PLUMBING RISER DIAGRAM. PER WPB AMEND
 TO FBC 107.3.5.3(11)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-06-27 Cont ID  
Sent By cthroop Date 2017-06-27 Time 13:49 Rev Time 0.00
Received By cthroop Date 2017-06-26 Time 08:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-08-22 Time   Rev Time 0.00
Received By pgreilic Date 2017-08-18 Time 16:39 Sent To M
Notes
2017-08-22 08:59:33PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-06-29 Time   Rev Time 0.00
Received By pgreilic Date 2017-06-28 Time 15:14 Sent To  
Notes
2017-06-29 16:08:06 
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  
  