Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2017-09-05 Cont ID  
Sent By spalmer Date 2017-09-05 Time 14:31 Rev Time 0.00
Received By spalmer Date 2017-09-05 Time 14:31 Sent To  
Notes
2017-09-05 14:31:29CUSTOMER DOING A STRAIGHT A/C CHANGEOUT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-08-08 Cont ID  
Sent By ccole Date 2017-08-08 Time 11:08 Rev Time 0.00
Received By ccole Date 2017-08-08 Time 11:08 Sent To  
Notes
2017-08-08 11:27:213RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17060431
 8/8/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #1 FROM THE PREVIOUS REVIEW STILL EXISTS. I AM
 REPRINTING IT BELOW WITH ADDITONAL COMMENTS BASED ON
 THE RESUBMITTED DOCUMENTS.
  
 1) IT APPEARS THAT ONE SET OF NEW AC PLANS FOR THE
 GARAGE APARTMENTS WAS NOT SUBMITTED. THE PERMIT
 APPLICATION INDICATES A 2.5 TON AND A 2-TON SYSTEM TO
 BE INSTALLED, HOWEVER ONLY ONE OF PLANS FOR THE 2.5 TON
 SYSTEM WAS SUBMITTED. ADDITIONALLY THE 2.5 TON SYSTEM
 SPECIFIED APPEARS TO BE OVERSIZED FOR THE APARTMENT, OR
 POSSIBLY, THE WRONG EQUIPMENT SCHEDULE WAS WRITTEN ON
 THE PLAN. PLEASE CORRECT AND REMOVE OR MARK VOID ON ALL
 SHEETS IN THE PERMIT FILE THAT ARE NO LONGER APPLICABLE
 TO THE PROJECT.
  
 2) REFER TO TABLE R301.1 FBC-14 ENERGY CONSERVATION AND
 PROVIDE THE CORRECT CLIMATE ZONE NUMBER FOR PALM BEACH
 COUNTY ON THE ENERGY FORM R405-2014: 1A.
  
 3) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION
 COMPONENT CRITERIA CHECKLIST SUBMITTED WITH FORM
 R405-2014.
  
 4) THE DIRECTIONAL ORIENTATION OF THE GARAGE APARTMENT
 SHOWN ON THE WRIGHTSOFT AC CALCULATION INDICATES THE
 FRONT DOOR FACES EAST, HOWEVER THE FRONT DOOR AS SHOWN
 ON THE GIS APPEARS TO BE FACING WEST. PLEASE CORRECT
 THE AC CALCULATIONS AND THE ENERGY FORM R405-2014 WHICH
 SHOWS INCORRECT WINDOW ORIENTATIONS AND INCORRECT
 NUMBERS OF WINDOWS WHEN COMPARED WITH THE
  
 AC PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-07-13 Cont ID  
Sent By ccole Date 2017-07-13 Time 14:44 Rev Time 0.00
Received By ccole Date 2017-07-13 Time 14:44 Sent To  
Notes
2017-07-13 15:03:192ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17060431
 7/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT ONE SET OF NEW AC PLANS FOR THE
 GARAGE APARTMENTS WAS NOT SUBMITTED. THE PERMIT
 APPLICATION INDICATES A 2.5 TON AND A 2-TON SYSTEM TO
 BE INSTALLED, HOWEVER ONLY ONE OF PLANS FOR THE 2.5 TON
 SYSTEM WAS SUBMITTED. ADDITIONALLY THE 2.5 TON SYSTEM
 SPECIFIED APPEARS TO BE OVERSIZED FOR THE APARTMENT, OR
 POSSIBLY, THE WRONG EQUIPMENT SCHEDULE WAS WRITTEN ON
 THE PLAN. PLEASE CORRECT AND REMOVE OR MARK VOID ON ALL
 SHEETS IN THE PERMIT FILE THAT ARE NO LONGER APPLICABLE
 TO THE PROJECT.
  
 2) INDICATE ON THE SUBMITTED PLAN THE MINIMUM WORKING
 CLEARANCE SPACE FOR THE NEW AIR HANDLER IN THE CLOSET-
 3 INCHES ALONG THE SIDES, BACK, AND TOP WITH A TOTAL
 WIDTH OF THE CLOSET AT LEAST 12 INCHES WIDER THAN THE
 AIR HANDLER.
  
 3) PROVIDE THE DIFFUSER SIZES ON THE PLAN.
  
 4) PROVIDE TWO COMPLETE AND CLEAR, LEGIBLE COPIES OF
 THE FL. PRODUCT APPROVAL #14239-R3. THE DOCUMENT
 SUBMITTED IS MISSING PAGES 2 & 4 AND HAS FAINT
 ILLEGIBLE PRINT. PLEASE NOTE THAT THE REQUIRED
 STRUCTURAL DETAILS FOR THE CONDENSER MOUNTING PAD ARE
 CONTAINED IN NOTE #7 ON PAGE 1.
  
 5) COMMENT #2 FROM THE PREVIOUS REVIEW STILL EXISTS. I
 HAVE REPRINTED THE COMMENT BELOW- PLEASE COMPLY.
  
 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY
 CONSERVATION: THE PREVIOUSLY UNCONDITIONED GARAGE
 APARTMENT MUST BE BROUGHT INTO FULL COMPLIANCE WITH THE
 CODE, THEREFORE THE SUBMITTED ENERGY FORM R402-2014 IS
 INCOMPLETE, AND ALSO INVALID. PLEASE READ THE "SCOPE"
 AT THE TOP OF THE FORM: "TO COMPLY, A BUILDING MUST
 MEET OR EXCEED ALL OF THE ENERGY EFFICIENCY
 REQUIREMENTS ON
  
 TABLE R402A AND ALL APPLICABLE MANDATORY REQUIREMENTS
 SUMMARIZED INTABLE R402B OF THIS FORM...."
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-19 Cont ID  
Sent By ccole Date 2017-06-19 Time 09:45 Rev Time 0.00
Received By ccole Date 2017-06-19 Time 09:45 Sent To  
Notes
2017-06-19 10:11:321ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060431
 6/19/17
  
 RESULTS: DENIED.
  
 1) THE COMPANY THAT PREPARED THE AC AND ENERGY
 CALCULATIONS- ENERGY HOUSE TECHNOLOGY- CANNOT DRAW THE
 AC PLAN FOR THE MAIN HOUSE AND THE GARAGE APARTMENT
 UNLESS THE COMPANY IS FL. STATE LICENSED AS AN AC OR
 MECHANICAL CONTRACTOR, AND IS THE INSTALLING CONTRACTOR
 ON THE PROJECT- SECTIION 105.3.1 WEST PALM BEACH
 AMENDMENTS TO THE FBC.
  
 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY
 CONSERVATION: THE PREVIOUSLY UNCONDITIONED GARAGE
 APARTMENT MUST BE BROUGHT INTO FULL COMPLIANCE WITH THE
 CODE, THEREFORE THE SUBMITTED ENERGY FORM R402-2014 IS
 INCOMPLETE, AND ALSO INVALID. PLEASE READ THE "SCOPE"
 AT THE TOP OF THE FORM: "TO COMPLY, A BUILDING MUST
 MEET OR EXCEED ALL OF THE ENERGY EFFICIENCY
 REQUIREMENTS ON
  
 TABLE R402A AND ALL APPLICABLE MANDATORY REQUIREMENTS
 SUMMARIZED INTABLE R402B OF THIS FORM...."
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  