Plan Review Details - Permit 17060402
Plan Review Stops For Permit 17060402
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-29 Cont ID  
Sent By rmcdouga Date 2017-08-29 Time 07:12 Rev Time 0.00
Received By rmcdouga Date 2017-08-29 Time 06:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-06 Cont ID  
Sent By rmcdouga Date 2017-07-06 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2017-07-06 Time 10:24 Sent To  
Notes
2017-07-06 10:35:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER'S ORIGINAL SEAL AND HANDWRITTEN
 SIGNATURE IS REQUIRED ON SHEET G-1. DIGITAL SIGNATURES
 ARE ONLY FOR ELECTRONICALLY SUBMITTED DRAWINGS. FAC
 61G15-23.003, FS 471.025

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-28 Cont ID  
Sent By jleahy Date 2017-08-28 Time 18:18 Rev Time 0.00
Received By jleahy Date 2017-08-28 Time 18:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-06 Cont ID  
Sent By jleahy Date 2017-07-06 Time 10:01 Rev Time 0.00
Received By jleahy Date 2017-07-06 Time 10:01 Sent To  
Notes
2017-07-06 10:08:18FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR THE WORK TOO LOW.
  
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS
 PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL
 BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING
  
  
 NEED CUT SHEETS FOR THE TRANSFER SWITCHES AND
 PARALLELING MODULE.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-07-06 Cont ID  
Sent By jleahy Date 2017-07-06 Time 10:20 Rev Time 0.00
Received By jleahy Date 2017-07-06 Time 10:20 Sent To  
Notes
2017-07-06 10:21:17SEE PERMIT 17050731 FOR GAS FOR GENERATOR.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-29 Cont ID  
Sent By rmcdouga Date 2017-08-29 Time 07:12 Rev Time 0.00
Received By rmcdouga Date 2017-08-23 Time 11:39 Sent To  
Notes
2017-08-24 11:40:19RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-06 Cont ID  
Sent By jleahy Date 2017-07-06 Time 10:33 Rev Time 0.00
Received By jleahy Date 2017-06-09 Time 13:01 Sent To  
Notes
2017-06-12 13:01:33ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-28 Cont ID  
Sent By njwira Date 2017-08-28 Time 14:22 Rev Time 0.00
Received By njwira Date 2017-08-24 Time 14:28 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-06-13 Cont ID  
Sent By njwira Date 2017-06-13 Time 16:56 Rev Time 0.00
Received By njwira Date 2017-06-12 Time 16:50 Sent To  
Notes
2017-06-13 16:57:17PLEASE PROVIDE TWO(2)COPIES OF A SURVEY SHOWING WHERE
 THE GENERATOR IS GOING
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved