Plan Review Details - Permit 17060345
Plan Review Stops For Permit 17060345
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-11 Cont ID  
Sent By jwitmer Date 2017-07-11 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2017-07-11 Time 06:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-20 Cont ID  
Sent By jwitmer Date 2017-06-20 Time 17:28 Rev Time 0.00
Received By jwitmer Date 2017-06-20 Time 16:58 Sent To  
Notes
2017-06-20 17:18:462014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060345
 ADD: 1701 S. FLAGLER DR. SUITE NUMBER 308
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-758-3020
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES., JUNE 20, 2017
 ACTION: DENIED
  
 1) THE CONTRACTOR OF RECORD WILL NEED TO PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER TO THE PLANS
 THEY ARE THE AUTHOR OF. 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE.
  
 2) THE FLOOR PLAN UNDER THE HEADING OF SCOPE OF WORK
 LIST NEW FLOOR INSULATION AND WOOD FLOORING.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-14 Cont ID  
Sent By jpearson Date 2017-07-14 Time 11:01 Rev Time 0.00
Received By jpearson Date 2017-07-14 Time 11:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-16 Cont ID  
Sent By jleahy Date 2017-06-16 Time 14:00 Rev Time 0.00
Received By jleahy Date 2017-06-16 Time 14:00 Sent To  
Notes
2017-06-16 14:01:30CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ONE SET IS IN PENCIL PLEASE RESUBMIT

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-07-07 Cont ID  
Sent By pleduc Date 2017-07-07 Time   Rev Time 0.00
Received By pleduc Date 2017-07-07 Time 13:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-12 Cont ID  
Sent By pleduc Date 2017-06-12 Time   Rev Time 0.00
Received By pleduc Date 2017-06-12 Time 12:38 Sent To  
Notes
2017-06-12 15:47:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE NO REFERENCES OF COMPLIANCE WITH ANY FIRE
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE
 ON THE SUBMITTAL.
  
  
  
 2) ALL SUBMITTED SHEETS - FLOORING AND SOUND BARRIERS
 ARE BEING PROPOSED FOR THIS PROJECT. THERE ARE NO
 PRODUCT SUBMITTALS.
  
 31.3.3.3 INTERIOR FLOOR FINISH. IN BUILDINGS UTILIZING
 OPTION 1 OR OPTION 2, NEWLY INSTALLED INTERIOR FLOOR
 FINISH IN EXITS AND EXIT ACCESS CORRIDORS SHALL BE NOT
 LESS THAN CLASS II IN ACCORDANCE WITH 10.2.7.
  
 YOUR BUILDING DOES NOT HAVE A SUPPRESSION SYSTEM BUT
 DOES HAVE A FIRE ALARM, USING (2) OPTION 2, BUILDINGS
 PROVIDED WITH A COMPLETE APPROVED AUTOMATIC FIRE
 DETECTION AND NOTIFICATION SYSTEM IN ACCORDANCE WITH
 31.3.4.4
  
 10.2.7 INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1 CARPET AND CARPETLIKE INTERIOR FLOOR FINISHES
 SHALL COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION CHARACTERISTICS OF FINISHED TEXTILE FLOOR
 COVERING MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE,
 SHALL HAVE A MINIMUM CRITICAL RADIANT FLUX OF 0.1
 W/CM2.
 10.2.7.3* INTERIOR FLOOR FINISHES SHALL BE CLASSIFIED
 IN ACCORDANCE WITH 10.2.7.4, BASED ON TEST RESULTS FROM
 NFPA 253, STANDARD METHOD OF TEST FOR CRITICAL RADIANT
 FLUX OF FLOOR COVERING SYSTEMS USING A RADIANT HEAT
 ENERGY SOURCE, OR ASTM E 648, STANDARD TEST METHOD FOR
 CRITICAL RADIANT FLUX OF FLOOR COVERING SYSTEMS USING A
 RADIANT HEAT ENERGY SOURCE.
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE CLASSIFIED AS
 FOLLOWS IN ACCORDANCE WITH THEIR CRITICAL RADIANT FLUX
 VALUES:
 (1) CLASS I INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
 (2) CLASS II INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.22 W/CM2 BUT LESS THAN 0.45 W/CM2, AS DETERMINED BY
 THE TEST DESCRIBED IN 10.2.7.3.
  
  
 PLEASE PROVIDE MANUFACTURES SPECIFICATION SHEETS THAT
 COMPLY WITH THE ABOVE CODES AND STANDARDS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-14 Cont ID  
Sent By gjohnson Date 2017-07-14 Time 17:56 Rev Time 0.00
Received By gjohnson Date 2017-07-03 Time 09:14 Sent To  
Notes
2017-07-06 09:14:46B10
 **TRAVELLING WITH 17060354**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-20 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-08 Time 10:07 Sent To  
Notes
2017-06-09 10:07:07B11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-06-20 Cont ID  
Sent By jwitmer Date 2017-06-20 Time 17:09 Rev Time 0.00
Received By jwitmer Date 2017-06-20 Time 16:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-14 Cont ID  
Sent By gjohnson Date 2017-07-14 Time 17:56 Rev Time 0.00
Received By gjohnson Date 2017-07-14 Time 16:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-16 Cont ID  
Sent By gjohnson Date 2017-06-16 Time 13:32 Rev Time 0.00
Received By gjohnson Date 2017-06-16 Time 13:12 Sent To  
Notes
2017-06-16 13:40:241ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE TWO SETS OF PLANS THAT ARE SIGNED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN AND ARE INK ONE
 OF THE PLAN SETS PROVIDED WAS IN PENCIL THIS IS NOT
 APPROVED. PER WPB AMEND TO FBC 107.2.1AND 107.2.1.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  