Plan Review Details - Permit 17060335
Plan Review Stops For Permit 17060335
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-28 Cont ID  
Sent By cthroop Date 2017-12-28 Time 09:43 Rev Time 0.00
Received By cthroop Date 2017-12-28 Time 09:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By rmcdouga Date 2017-07-25 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2017-07-25 Time 07:22 Sent To  
Notes
2017-07-25 07:56:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT STRUCTURAL DRAWINGS FOR THE GENERATOR PAD AND
 GENERATOR WINDLOAD ANCHORING REQUIREMENTS THAT HAVE
 BEEN SIGNED AND SEALED BY A FLORIDA LICENSED ENGINEER.
 FS 471 & FAC 61G15
  
 2) ALTHOUGH A PORTION OF THE PROPERTY IS LOCATED IN A
 SPECIAL FLOOD HAZARD ZONE, THE GENERATOR IS LOCATED IN
 A B ZONE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-28 Cont ID  
Sent By jleahy Date 2017-12-28 Time 09:24 Rev Time 0.00
Received By jleahy Date 2017-12-28 Time 09:24 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By jleahy Date 2017-07-05 Time 08:17 Rev Time 0.00
Received By jleahy Date 2017-06-29 Time 08:17 Sent To FIRE
Notes
2017-06-29 08:28:25FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUATION OF WORK TO LOW. PROVIDE SIGNED CONTRACT FOR
 WORK INVOLVED.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PLANS TO BE SIGNED AND SEALED BY AN ENGINEER.
  
 FBC-107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS - THE CONSTRUCTION
 DOCUMENTS SHALL BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL WHERE REQUIRED BY CHAPTER 471,
 FLORIDA STATUTES& 61G15 FLORIDA ADMINISTRATIVE CODE OR
 CHAPTER 481, FLORIDA STATUTES& 61G1 FLORIDA
 ADMINISTRATIVE CODE, THEN HE OR SHE SHALL AFFIX HIS OR
 HER OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 NEED SUBMITALS FOR GENERATOR AND TRANSFER SWITCH, AND
 GEAR THAT IS BEING REPLACED.
 PLEASE INDICATE WHICH SWITCH GEAR IS BEING REPLACED
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-21 Cont ID  
Sent By pleduc Date 2017-12-21 Time   Rev Time 0.00
Received By pleduc Date 2017-12-20 Time 15:54 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-14 Cont ID  
Sent By wjolin Date 2017-07-14 Time 12:00 Rev Time 0.00
Received By jleahy Date 2017-07-14 Time 11:57 Sent To B
Notes
2017-07-14 12:00:21PLANS WILL BE STAMPED AND DATED BY THE FD AFTER ALL
 REVIEWER COMMENTS HAVE BEEN SATISFIED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-28 Cont ID  
Sent By cthroop Date 2017-12-28 Time 09:44 Rev Time 0.00
Received By cthroop Date 2017-12-13 Time 11:47 Sent To I
Notes
2017-12-14 11:48:09RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-25 Cont ID  
Sent By rmcdouga Date 2017-07-25 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2017-06-08 Time 15:57 Sent To  
Notes
2017-06-09 15:57:52ROUTED TO ZONING

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2017-07-25 Cont ID  
Sent By rmcdouga Date 2017-07-25 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2017-07-25 Time 08:06 Sent To  
Notes
2017-07-25 08:34:31ALTHOUGH A PORTION OF THE PROPERTY INCLUDING PART OF
 THE MAIN STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (A8) THE GENERATOR IS NOT. THE GENERATOR IS
 LOCATED IN A "B" ZONE.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By PG Date 2017-12-20 Time   Rev Time 0.00
Received By ajones Date 2017-12-14 Time 15:14 Sent To  
Notes
2017-12-20 12:05:26PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2017-06-13 Cont ID  
Sent By njwira Date 2017-06-13 Time 15:29 Rev Time 0.00
Received By njwira Date 2017-06-09 Time 17:08 Sent To  
Notes
2017-06-13 15:29:50REQUIRES A MINOR PD AMMENDMENT