Plan Review Details - Permit 17060316
Plan Review Stops For Permit 17060316
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-24 Cont ID  
Sent By jwitmer Date 2017-07-24 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2017-07-24 Time 06:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-19 Cont ID  
Sent By jwitmer Date 2017-06-19 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2017-06-19 Time 07:08 Sent To  
Notes
2017-06-19 08:16:462014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060316
 ADD: 1401 FORUM WAY, SUITE: 300
 CONT: MILLER CONSTRUCTION
 TEL: 954-847-0619
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE19/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE THE COVERSHEET AND ALL ARCHITECTURAL
 SHEETS HAVE DIGITAL/ PIXILATED SIGNATURES, NOT AN
 ORIGINAL INK SIGNATURE. FL ADMIN CODE 61G16.003
 ARCHITECTS.
  
 2) THE COVERSHEET REFERENCED CODES, GENERAL NOTES LIST
 THE AUTHORITY HAVING JURISDICTION AS: WESTON, FL.
 PLEASE CORRECT, THE MUNICIPALITY HAVING JURISDICTION IS
 THE CITY OF WEST PALM BEACH, FL. PLEASE UPDATE PLANS.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 3) SHEET MD100 SHOWS A/C DUCTS PENETRATING A 2 HR. FIRE
 RATED VERTICAL EXIT STAIRWAY WITH NO FIRE RATING.
 PLEASE SHOW COMPLIANCE WITH 2014 FBC-B SECTION 1022.5
 PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH
 INTERIOR EXIT STAIRWAYS AND RAMPS ARE PROHIBITED EXCEPT
 FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK
 NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-25 Cont ID  
Sent By jpearson Date 2017-07-25 Time 13:44 Rev Time 0.00
Received By jpearson Date 2017-07-25 Time 13:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-06-12 Cont ID  
Sent By jpearson Date 2017-06-12 Time 10:18 Rev Time 0.00
Received By jpearson Date 2017-06-12 Time 10:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-07-25 Cont ID  
Sent By pleduc Date 2017-07-25 Time   Rev Time 0.00
Received By pleduc Date 2017-07-24 Time 16:37 Sent To  
Notes
2017-07-24 16:38:452 ND REVIEW
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY WORK ON THE FIRE SPRINKLER AND/OR FIRE ALARM
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-13 Cont ID  
Sent By pleduc Date 2017-06-13 Time   Rev Time 0.00
Received By pleduc Date 2017-06-12 Time 16:26 Sent To  
Notes
2017-06-13 09:24:35THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY WORK ON THE FIRE SPRINKLER AND/OR FIRE ALARM
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-25 Cont ID  
Sent By jpearson Date 2017-07-25 Time 13:44 Rev Time 0.00
Received By jpearson Date 2017-07-21 Time 09:02 Sent To  
Notes
2017-07-21 09:02:50B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-19 Cont ID  
Sent By jwitmer Date 2017-06-19 Time 08:17 Rev Time 0.00
Received By jwitmer Date 2017-06-08 Time 16:26 Sent To  
Notes
2017-06-09 16:26:29B20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-06-19 Cont ID  
Sent By jwitmer Date 2017-06-19 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2017-06-19 Time 07:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-07-21 Cont ID  
Sent By ccole Date 2017-07-21 Time 12:38 Rev Time 0.00
Received By ccole Date 2017-07-21 Time 12:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-16 Cont ID  
Sent By ccole Date 2017-06-16 Time 07:26 Rev Time 0.00
Received By ccole Date 2017-06-16 Time 07:25 Sent To  
Notes
2017-06-16 07:50:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060316
 6/16/17
  
 RESULTS: DENIED.
  
 1) SHEETS MD100 & M100: THERE APPEAR TO BE MISSING FIRE
 DAMPERS FOR THE DUCTS PENETRATING WHAT APPEAR TO BE
 FIRE-RATED WALLS EMCOMPASSING ROOM 348- PLEASE CLARIFY.
  
 2) THE MECHANICAL PLANS HAVE COPIED SEALS AND
 SIGNATURES. THE ENGINEER OF RECORD CHAD A. WISLER SHALL
 PROVIDE AN ORIGINAL SEAL WITH SIGNATURE AND DATE ON THE
 MECHANICAL PLANS- SECTION 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  