| Plan Review Stops For Permit 17060251 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2017-12-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-12-14 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-12-14 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2017-12-14 09:34:38 | CHANGED VALURE TO $59,000 JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2017-12-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-12-05 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-12-05 |
Time |
08:18 |
Sent To |
I |
|
| Notes |
| 2017-12-05 08:32:38 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, | | | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE | | | WORK, ARCHITECTURAL | | | AND DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; | | | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY | | | INCLUDE | | | THE LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST | | | ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS | | | PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | VALUE OF $25,000 IS FOR GENERATOR, TRANSFER SWITCH, | | | TRANSFORMER, DISCONNECT, WIRE, AND LABOR? | | | | | | SUBMIT A SIGNED CONTRACT SHOWING ALL MATERIAL, | | | EQUIPMENT, AND LABOR REQUIRED, OTHERWISE CITY WILL | | | ASSESS A VALUE OF $75,000 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-11-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-11-03 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-11-03 |
Time |
17:14 |
Sent To |
FIRE |
|
| Notes |
| 2017-11-03 17:19:33 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | VALUE FOR WORK SHOWN IS NOT REPRESENTATIVE OF VALUE ON | | | PERMIT. | | | | | | PLEASE SUPPLY A SIGNED CONTRACT FOR PROPOSED WORK. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE | | | CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET | | | BY THE BUILDING OFFICIAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-06-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-06-21 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-06-21 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2017-06-21 13:02:23 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | COMPLY WITH ZONING AND FIRE COMMENT FOR AN ELECTRICAL | | | PLAN REVIEW. | | 2017-06-21 09:26:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE IS NOT SITE PLAN SUBMITTED SHOWING THE | | | LOCATION OF THE GENERATOR WITH DIMESIONS TO ALL | | | INPORTANT BUILDINGS AND STRUCTURES AND TO CONFIRM ITS | | | LOCATION. | | | | | | PLEASE PROVIDE A DETAILED SITE PLAN. | | | | | | | | | | | | 2) THERE IS NO INDICATION IF THIS GENERATOR SUPPLIES | | | EMERGENCY POWER TO THE LIFE SAFETY SYSTEMS OF THE | | | STRUCTURES IT SERVES. IF SO, THE INSTALLATION SHALL | | | COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY AND | | | STANDBY POWER SYSTEMS. | | | | | | THIS STANDARD COVERS PERFORMANCE REQUIREMENTS FOR | | | EMERGENCY AND STANDBY POWER SYSTEMS PROVIDING AN | | | ALTERNATE SOURCE OF ELECTRICAL POWER IN BUILDINGS AND | | | FACILITIES IN THE EVENT THAT THE NORMAL ELECTRICAL | | | POWER SOURCE FAILS. SYSTEMS INCLUDE POWER SOURCES, | | | TRANSFER EQUIPMENT, CONTROLS, SUPERVISORY EQUIPMENT, | | | AND ACCESSORY EQUIPMENT NEEDED TO SUPPLY ELECTRICAL | | | POWER TO THE SELECTED CIRCUITS. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | COMPLIANCE. | | | | | | | | | 3) SHOULD # 2 APPLY, PLEASE PROVIDE HOW THE LIFE SAFETY | | | SYSTEMS WILL BE MAINTAINED AND MONITORED DURING THE | | | SWITCH OVER TO THE NEW ONE. | | | | | | HOW LONG WILL THE SWITCH OVER TAKE? WILL A FIRE WATCH | | | BE IMPLEMENTED? BY WHOM? WILL A TEMPORARY GENERATOR BE | | | INSTALLED? ETC.... | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-11-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-11-03 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-03 |
Time |
13:03 |
Sent To |
E |
|
| Notes |
| 2017-11-03 13:11:38 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) IF THIS INSTALL OPERATES ANY LIFE SAFETY EQUIPMENT | | | IT SHALL BE INSTALLED, INSPECTED AND TESTED PER NFPA | | | 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS, | | | 2010 EDITION. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-06-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-06-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-06-21 |
Time |
09:03 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-12-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-12-05 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-11-30 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2017-12-01 13:12:45 | RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-11-03 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-10-12 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2017-10-13 12:57:49 | RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-06-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-06-21 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-06-07 |
Time |
13:27 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2017-12-04 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2017-12-04 |
Time |
11:15 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2017-12-04 |
Time |
11:07 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2017-11-01 |
|
|
Cont ID |
|
| Sent By |
ES |
Date |
2017-11-01 |
Time |
09:55 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2017-10-17 |
Time |
19:03 |
Sent To |
E |
|
| Notes |
| 2017-11-01 10:01:49 | FAILED | | | | | | 1) REVISED COMMENT: STAFF IS UNABLE TO DETERMINE WHERE | | | ON THE BUILDING THE GENERATOR WILL BE LOCATED WITH THE | | | PARTIAL SITE PLAN THAT WAS PROVIDED. PROVIDE A SITE | | | PLAN OF THE FULL BUILDING SHOWING THE LOCATION OF THE | | | EXISTING GENERATOR, INCLUDING SETBACK INFORMATION AND | | | SCREENING. | | | | | | 2) THE PROPOSED GENERATOR AND FUEL TANK WILL BE ALMOST | | | SIX FEET TALL. PLEASE PROVIDE HOW THE GENERATOR WILL BE | | | SCREENED. | | | | | | CONTACT ERIC SCHNEIDER AT (561) 822-1446. | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2017-06-15 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-06-21 |
Time |
13:01 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2017-06-15 |
Time |
12:20 |
Sent To |
E |
|
| Notes |
| 2017-06-15 12:27:42 | FAILED | | | | | | 1) PROVIDE TWO COPIES OF A SURVEY OR SITE PLAN SHOWING | | | THE LOCATION OF THE EXISTING GENERATOR, INCLUDING | | | SETBACK INFORMATION, SIZE OF EXISTING GENERATOR AND | | | SCREENING. | | | | | | 2) A FULL REVIEW WILL BE COMPLETED WHEN THE INFORMATION | | | REQUIRED IN ITEM NO. 1 IS PROVIDED. | | | | | | CONTACT ERIC SCHNEIDER AT (561) 822-1446. | | | [email protected] | | 2017-06-09 14:44:47 | ROUTED TO ERIC SCHNEIDER |
|
|