Plan Review Details - Permit 17060251
Plan Review Stops For Permit 17060251
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-12-14 Cont ID  
Sent By jleahy Date 2017-12-14 Time 09:34 Rev Time 0.00
Received By jleahy Date 2017-12-14 Time 09:34 Sent To  
Notes
2017-12-14 09:34:38CHANGED VALURE TO $59,000 JLEAHY

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-12-05 Cont ID  
Sent By jleahy Date 2017-12-05 Time 08:18 Rev Time 0.00
Received By jleahy Date 2017-12-05 Time 08:18 Sent To I
Notes
2017-12-05 08:32:38FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS
 PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 VALUE OF $25,000 IS FOR GENERATOR, TRANSFER SWITCH,
 TRANSFORMER, DISCONNECT, WIRE, AND LABOR?
  
 SUBMIT A SIGNED CONTRACT SHOWING ALL MATERIAL,
 EQUIPMENT, AND LABOR REQUIRED, OTHERWISE CITY WILL
 ASSESS A VALUE OF $75,000

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-11-03 Cont ID  
Sent By jleahy Date 2017-11-03 Time 16:38 Rev Time 0.00
Received By jleahy Date 2017-11-03 Time 17:14 Sent To FIRE
Notes
2017-11-03 17:19:33FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR WORK SHOWN IS NOT REPRESENTATIVE OF VALUE ON
 PERMIT.
  
 PLEASE SUPPLY A SIGNED CONTRACT FOR PROPOSED WORK.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By jleahy Date 2017-06-21 Time 13:01 Rev Time 0.00
Received By jleahy Date 2017-06-21 Time 13:01 Sent To  
Notes
2017-06-21 13:02:23CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 COMPLY WITH ZONING AND FIRE COMMENT FOR AN ELECTRICAL
 PLAN REVIEW.
2017-06-21 09:26:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS NOT SITE PLAN SUBMITTED SHOWING THE
 LOCATION OF THE GENERATOR WITH DIMESIONS TO ALL
 INPORTANT BUILDINGS AND STRUCTURES AND TO CONFIRM ITS
 LOCATION.
  
 PLEASE PROVIDE A DETAILED SITE PLAN.
  
  
  
 2) THERE IS NO INDICATION IF THIS GENERATOR SUPPLIES
 EMERGENCY POWER TO THE LIFE SAFETY SYSTEMS OF THE
 STRUCTURES IT SERVES. IF SO, THE INSTALLATION SHALL
 COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY AND
 STANDBY POWER SYSTEMS.
  
 THIS STANDARD COVERS PERFORMANCE REQUIREMENTS FOR
 EMERGENCY AND STANDBY POWER SYSTEMS PROVIDING AN
 ALTERNATE SOURCE OF ELECTRICAL POWER IN BUILDINGS AND
 FACILITIES IN THE EVENT THAT THE NORMAL ELECTRICAL
 POWER SOURCE FAILS. SYSTEMS INCLUDE POWER SOURCES,
 TRANSFER EQUIPMENT, CONTROLS, SUPERVISORY EQUIPMENT,
 AND ACCESSORY EQUIPMENT NEEDED TO SUPPLY ELECTRICAL
 POWER TO THE SELECTED CIRCUITS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 COMPLIANCE.
  
  
 3) SHOULD # 2 APPLY, PLEASE PROVIDE HOW THE LIFE SAFETY
 SYSTEMS WILL BE MAINTAINED AND MONITORED DURING THE
 SWITCH OVER TO THE NEW ONE.
  
 HOW LONG WILL THE SWITCH OVER TAKE? WILL A FIRE WATCH
 BE IMPLEMENTED? BY WHOM? WILL A TEMPORARY GENERATOR BE
 INSTALLED? ETC....
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-03 Cont ID  
Sent By jleahy Date 2017-11-03 Time 17:20 Rev Time 0.00
Received By pleduc Date 2017-11-03 Time 13:03 Sent To E
Notes
2017-11-03 13:11:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) IF THIS INSTALL OPERATES ANY LIFE SAFETY EQUIPMENT
 IT SHALL BE INSTALLED, INSPECTED AND TESTED PER NFPA
 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS,
 2010 EDITION.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By pleduc Date 2017-06-21 Time   Rev Time 0.00
Received By pleduc Date 2017-06-21 Time 09:03 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-05 Cont ID  
Sent By jleahy Date 2017-12-05 Time 08:18 Rev Time 0.00
Received By jleahy Date 2017-11-30 Time 13:11 Sent To  
Notes
2017-12-01 13:12:45RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-03 Cont ID  
Sent By jleahy Date 2017-11-03 Time 17:20 Rev Time 0.00
Received By jleahy Date 2017-10-12 Time 12:57 Sent To  
Notes
2017-10-13 12:57:49RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-21 Cont ID  
Sent By jleahy Date 2017-06-21 Time 13:01 Rev Time 0.00
Received By jleahy Date 2017-06-07 Time 13:27 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2017-12-04 Cont ID  
Sent By eschneid Date 2017-12-04 Time 11:15 Rev Time 0.25
Received By eschneid Date 2017-12-04 Time 11:07 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2017-11-01 Cont ID  
Sent By ES Date 2017-11-01 Time 09:55 Rev Time 0.25
Received By eschneid Date 2017-10-17 Time 19:03 Sent To E
Notes
2017-11-01 10:01:49FAILED
  
 1) REVISED COMMENT: STAFF IS UNABLE TO DETERMINE WHERE
 ON THE BUILDING THE GENERATOR WILL BE LOCATED WITH THE
 PARTIAL SITE PLAN THAT WAS PROVIDED. PROVIDE A SITE
 PLAN OF THE FULL BUILDING SHOWING THE LOCATION OF THE
 EXISTING GENERATOR, INCLUDING SETBACK INFORMATION AND
 SCREENING.
  
 2) THE PROPOSED GENERATOR AND FUEL TANK WILL BE ALMOST
 SIX FEET TALL. PLEASE PROVIDE HOW THE GENERATOR WILL BE
 SCREENED.
  
 CONTACT ERIC SCHNEIDER AT (561) 822-1446.
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-06-15 Cont ID  
Sent By jleahy Date 2017-06-21 Time 13:01 Rev Time 0.25
Received By eschneid Date 2017-06-15 Time 12:20 Sent To E
Notes
2017-06-15 12:27:42FAILED
  
 1) PROVIDE TWO COPIES OF A SURVEY OR SITE PLAN SHOWING
 THE LOCATION OF THE EXISTING GENERATOR, INCLUDING
 SETBACK INFORMATION, SIZE OF EXISTING GENERATOR AND
 SCREENING.
  
 2) A FULL REVIEW WILL BE COMPLETED WHEN THE INFORMATION
 REQUIRED IN ITEM NO. 1 IS PROVIDED.
  
 CONTACT ERIC SCHNEIDER AT (561) 822-1446.
 [email protected]
2017-06-09 14:44:47ROUTED TO ERIC SCHNEIDER