| Plan Review Stops For Permit 17060234 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-09-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-26 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-26 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2017-09-26 08:55:52 | ****PROVISOS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PERMIT IS ISSUED AT APPLICANT'S RISK | | | | | | A. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL | | | OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING | | | OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE | | | CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A | | | BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS | | | FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN | | | SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION | | | OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED | | | AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION | | | AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE | | | STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED | | | TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS | | | PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL | | | OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST | | | BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. | | | | | | B. REPLAT TO BE RECORDED PRIOR TO C.O. | | | | | | C. LIFE SAFETY AND OTHER ITEMS NOT REVIEWED; INTERIOR | | | WILL BE REVIEWED UNDER THE BUILDING PERMIT. SOME PAGES | | | IN THIS SUBMITTAL HAVE NOT BEEN REVIEWED BUT HAVE BEEN | | | RETAINED IN THE SUBMITTAL FOR INFORMATIONAL PURPOSES. | | | | | | D. REVISE PLAN FOR BUILDING (VERTICAL) PERMIT; THE | | | ASSEMBLY SPACES ARE FOR USE BY THE SCHOOL ONLY AND NO | | | OTHER ENTITIES. | | | | | | E. MAINTAIN MEANS OF EGRESS/EXITING FOR EXISTING SCHOOL | | | IN COMPLIANCE WITH FBC BUILDING CHAPTER 10. | | | | | | F. AFTER ISSUANCE, OBTAIN A COMPLETE COPY OF THE ISSUED | | | PLANS, FOR THE SPECIAL INSPECTOR. COLOR COPY IS | | | RECOMMENDED BUT NOT REQUIRED. NOTE THAT THE INSPECTION | | | SET MUST BE THE SET ISSUED BY THE BUILDING DIVISION | | | (COLOR STAMPS AND REVIEWER SIGNATURES), FBC 107. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-08-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-29 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-29 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2017-08-29 15:55:17 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | COMMENTS FROM PREVIOUS LIST: | | | | | | 1. THRESHOLD INSPECTION PLAN AND SOILS REPORT ARE | | | PHOTOCOPIES; ORIGINALS REQUIRED FS471. | | | | | | 2ND REVIEW; THE THRESHOLD INSPECTION PLAN AND SOILS | | | REPORT ARE ALSO (STILL) PHOTOCOPIES (NO NEW DOCUMENTS | | | SUBMITTED). RESPONSE LETTER STATES "COMPLIED. MULTIPLE | | | ORIGINALS HAVE BEEN SUBMITTED WITH THIS PROJECT'S | | | PREVIOUS PERMIT SUBMISSION. PLEASE REFERENCE THE TWO | | | COPIES SUBMITTED WITH THIS RE-SUBMISSION AND/OR WITH | | | THE MAIN BUILDING PERMIT SET." | | | | | | FBC 107, APPLICANT IS TO PROVIDE ALL DOCUMENTS REQUIRED | | | TO DETERMINE CODE COMPLIANCE. DOCUMENTS IN ANOTHER | | | PERMIT APPLICATION CANNOT BE USED FOR THIS PERMIT. | | | DOCUMENTS WITH ANOTHER PERMIT APPLICATION ARE NOT | | | OFFICIAL PERMIT RECORD UNTIL ISSUANCE. DOCUMENTS | | | PREPARED BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD | | | ARE TO BE SIGNED, SEALED, DATED ORIGINALS. PLEASE | | | PROVIDE THE ORIGINAL DOCUMENTS REQUESTED. | | | | | | 2. SEE FIRE COMMENTS. ADVISE AS TO HOW EXITING FOR THE | | | EXISTING SCHOOL WILL BE AFFECTED BY THE PROPOSED | | | CONSTRUCTION. THIS INFORMATION IS REQUIRED PRIOR TO | | | COMMENCEMENT OF ANY WORK AFFECTING THE EXIT AND EXIT | | | DISCHARGE FOR EXISTING SCHOOL. | | | | | | 2ND REVIEW, SEE FIRE REVIEW. | | | | | | NEW COMMENTS: | | | | | | 3. AN ENTIRELY NEW SET OF PLANS WAS SUBMITTED. THE | | | STRUCTURAL PAGES ARE NOT SIGNED, SEALED, DATED | | | ORIGINALS (PHOTOCOPIES), SEE FS 471. | | | | | | 4. PLEASE REMOVE SHEETS NOT REQUIRED FOR THIS | | | FOUNDATION SUBMITTAL. FOR INSTANCE: | | | | | | CIVIL SHEET 5, PAVING AND DRAINAGE DETAILS | | | A0.05, SECOND FLOOR LIFE SAFETY PLAN - SOUTH | | | A0.16 WINDOW ELEVATIONS | | | | | | IT APPEARS THAT A FULL SET OF PLANS FOR THE BUILDING | | | WAS SUBMITTED. PAGES NOT NEEDED FOR FOUNDATION SHOULD | | | BE REMOVED. GENERALLY, DOCUMENTS REQUIRED FOR | | | FOUNDATION PERMIT ARE: | | | | | | PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION | | | PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB) | | | GEOTECHNICAL REPORT | | | SURVEY DRAWING | | | STORM WATER POLLUTION PREVENTION PLAN | | | SITE PLAN | | | 1ST FLOOR ARCHITECTURAL PLAN | | | ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING | | | FOUNDATION PLAN | | | FOUNDATION DETAILS AND CROSS SECTIONS | | | STRUCTURAL ENGINEER'S GENERAL NOTES | | | UNDERGROUND PLUMBING PLAN (IF APPLICABLE) | | | ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT (IF | | | APPLICABLE) | | | ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR | | | EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT). | | | IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT, | | | AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR | | | PLAN SHOWING UNDERGROUND FIRE LINE | | | THRESHOLD INSPECTION PLAN OR RESIDENT INSPECTION PLAN | | | (AS APPLICABLE) | | | SI OR RESIDENT INSPECTOR AGREEMENT (AS APPLICABLE) | | | | | | 5. THREE COMPLETE IDENTICAL SETS OF PLANS AND PERMIT | | | DOCUMENTS REQUIRED, FBC 107. | | | | | | 6. THIS PERMIT WILL BE ISSUED WITH PROVISO: | | | | | | PERMIT IS ISSUED AT APPLICANT'S RISK | | | | | | A. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL | | | OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING | | | OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE | | | CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A | | | BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS | | | FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN | | | SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION | | | OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED | | | AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION | | | AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE | | | STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED | | | TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS | | | PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL | | | OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST | | | BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. | | | | | | B. REPLAT TO BE RECORDED PRIOR TO C.O. | | | | | | C. LIFE SAFETY AND OTHER ITEMS NOT REVIEWED; INTERIOR | | | WILL BE REVIEWED UNDER THE BUILDING PERMIT. | | | | | | D. REVISE PLAN; THE ASSEMBLY SPACES ARE FOR USE BY THE | | | SCHOOL ONLY AND NO OTHER ENTITIES. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-06-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-15 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-15 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2017-06-15 16:13:23 | ****CORRECTIONS**** | | | REVISED 8/11/17 | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THRESHOLD INSPECTION PLAN AND SOILS REPORT ARE | | | PHOTOCOPIES; ORIGINALS REQUIRED FS471. | | | | | | 2. SEE FIRE COMMENTS. ADVISE AS TO HOW EXITING FOR THE | | | EXISTING SCHOOL WILL BE AFFECTED BY THE PROPOSED | | | CONSTRUCTION. THIS INFORMATION IS REQUIRED PRIOR TO | | | COMMENCEMENT OF ANY WORK AFFECTING THE EXIT AND EXIT | | | DISCHARGE FOR EXISTING SCHOOL. | | | | | | 3. THIS PERMIT WILL BE ISSUED WITH PROVISO: | | | | | | PERMIT IS ISSUED AT APPLICANT'S RISK | | | | | | A. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL | | | OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING | | | OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE | | | CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A | | | BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS | | | FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN | | | SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION | | | OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED | | | AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION | | | AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE | | | STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED | | | TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS | | | PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL | | | OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST | | | BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. | | | | | | B. REPLAT TO BE RECORDED PRIOR TO C.O. | | | | | | C. LIFE SAFETY AND OTHER ITEMS NOT REVIEWED; INTERIOR | | | WILL BE REVIEWED UNDER THE BUILDING PERMIT. | | | | | | D. REVISE PLAN; THE ASSEMBLYL SPACES ARE FOR USE BY THE | | | SCHOOL ONLY AND NO OTHER ENTITIES. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-09-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-09-20 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-09-20 |
Time |
12:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-08-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-08-23 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-08-23 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2017-08-23 11:13:10 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NEW SUBMISSION SHOWS MODIFICATIONS TO THE EXISTING | | | SERVICE. PROVIDE CLARIFICATION. IS THIS SERVICE AT A | | | DIFFERENT ADDRESS, REQUIRING A SEPARATE PERMIT? WHY IS | | | PANEL K BEING ADDED? PANEL K AND THE EXISTING SERVICE | | | ARE NOT SHOWN ON POWER PLAN SUBMITTED, WHAT IS THE | | | LOCATION OF THESE ITEMS? PROVIDE LOAD CALCULATION FOR | | | EXISTING SERVICE AND JUSTIFICATION FOR INCREASE (?) IN | | | SIZE. PROVIDE NOTE FOR ANY SEPARATE PERMITS REQUIRED. | | | FBC 107.2.1 | | | | | | BECAUSE THIS IS FOR A FOUNDATION PERMIT ONLY, THIS IS | | | THE ONLY QUESTION AT THIS TIME. WHEN A FULL PLAN REVIEW | | | IS COMPLETED FOR THE MASTER PERMIT, ADDITIONAL COMMENTS | | | WILL BE FORTHCOMING. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-09-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-06-14 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-14 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2017-06-14 07:41:32 | REVIEWED FOR FOUNDATION ONLY. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2017-09-20 |
|
|
Cont ID |
|
| Sent By |
squinone |
Date |
2017-09-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
squinone |
Date |
2017-09-20 |
Time |
|
Sent To |
FIRE |
|
| Notes |
| 2017-09-20 17:12:00 | STATUS: PASSED WITH CONDITIONS | | | | | | 1. DO NOT USE FLAMINGO DRIVE FOR CONSTRUCTION TRAFFIC. | | | 2. PHASE 1 OF PARTIAL FOOTING AND FOUNDATION | | | CONSTRUCTION MUST BE 15-FEET MINIMUM FROM THE EXISTING | | | WATERMAIN. REFER TO CIVIL SHEET 7 OF 8 TO REVIEW MARKUP | | | OF ALLOWED PARTIAL FOOTING AND FOUNDATION CONSTRUCTION. | | | UPON COMPLETION OF UTILITY REMOVAL, THE APPLICANT MUST | | | APPLY FOR ANOTHER PARTIAL FOOTING AND FOUNDATION PERMIT | | | FOR APPROVAL OF SECOND PHASE. | | | | | | LET ME KNOW IF THERE ARE ANY QUESTIONS OR CONCERNS. | | | | | | SINCERELY, | | | SOFIA QUINONES-BENEJAM, EI | | | PROJECT ENGINEER | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | P: 561.494.1040 EXT: 1108 | | | F: 561.494.1116 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2017-08-30 |
|
|
Cont ID |
|
| Sent By |
squinone |
Date |
2017-08-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
squinone |
Date |
2017-08-30 |
Time |
|
Sent To |
I |
|
| Notes |
| 2017-08-30 10:23:18 | PROJECT: THE GREENE SCHOOL - ADDITION | | | PERMIT NO. 17060234 | | | STATUS: FAILED | | | | | | COMMENTS (PLEASE RESPOND TO COMMENTS IN WRITTING): | | | 1. REMOVAL OF EXISTING UTILITIES HAS TO BE COMPLETED | | | PRIOR TO FOUNDATION PERMIT APPROVAL. | | | 2. A REPLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO | | | THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY (C.O.) FOR | | | THE EXPANSION. | | | | | | LET ME KNOW IF THERE ARE ANY QUESTIONS OR CONCERNS. | | | | | | SINCERELY, | | | SOFIA QUINONES-BENEJAM, EI | | | PROJECT ENGINEER | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33402 | | | (MAILING ADDRESS: PO BOX 3366) | | | P: 561.494.1108 | | | C: 561.459.6518 | | | F: 561.494.1116 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2017-07-19 |
|
|
Cont ID |
|
| Sent By |
SQ |
Date |
2017-07-19 |
Time |
|
Rev Time |
8.00 |
| Received By |
squinone |
Date |
2017-07-19 |
Time |
|
Sent To |
I |
|
| Notes |
| 2017-07-19 14:10:40 | THE GREENE SCHOOL - ADDITION, 17060234 | | | | | | COMMENTS: | | | 1. PLANS ARE CURRENTLY UNDER REVIEW IN ENGINEERING. | | | 2. RIGHT OF WAY PERMIT IS REQUIRED FOR THE CONSTRUCTION | | | OF THE DRIVEWAYS ON FLAMINGO AND BISCAYNE. | | | 3. REMOVE PARKING STRIPING FROM FLAMINGO. | | | 4. DO NOT USE FLAMINGO DRIVE FOR CONSTRUCTION TRAFFIC. | | | | | | LET ME KNOW IF THERE ARE ANY QUESTIONS OR CONCERNS. | | | | | | SINCERELY, | | | SOFIA QUINONES-BENEJAM, EI | | | PROJECT ENGINEER | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | P: 561.494.1040 EXT: 1108 | | | F: 561.494.1116 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-09-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-09-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-09-25 |
Time |
12:06 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2017-08-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-08-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-08-28 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2017-08-28 14:24:40 | 2ND REVIEW COMMENTS | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THIS REVIEW AND THE COMMENTS ARE RELATED TO THE | | | FOUNDATION PERMIT ONLY. | | | | | | | | | 1) SHEET 2 OF 8 - THERE ARE NO INDICATION HOW THE | | | EXISTING REQUIRED EXITING, INCLUDING WALKWAY AND | | | STAIRS, WILL BE MAINTAINED DURING DEMO AND ALL PHASES | | | OF CONSTRUCTION. | | | | | | NOT COMPLIED. YOUR COMMENTS THAT A DETAILED LIFE SAFETY | | | PLAN WAS SUBMITTED COULD NOT BE FOUND. | | | | | | THE LIFE SAFETY PLAN SHALL INCLUDED THE EXIT PATH FROM | | | ALL SOUTH END EXITS, INCLUDING THE STAIRS FROM THE 2 ND | | | FL, THE TRAVEL PATH LEADING TO A POINT OF PUBLIC WAY, | | | THESE PLANS SHALL INCLUDE EXIT WIDTH, ELEVATION | | | CHANGES, EXIT SIGNAGE, SEPARATION MEASURES FROM | | | CONSTRUCTION. | | | | | | THESE ITEMS WERE DISCUSSED AT LENGTH DURING A MEETING | | | WITH THE AHRENS TEAM. | | | | | | PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN INDICATING | | | HOW AND WHERE THE EXITING FROM THE CURRENT BUILDING | | | WILL BE MAINTAINED AND PROTECTED. | | | | | | | | | | | | | | | 2) SHEET 7 OF 8 - THE FIRE LINE APPEARS TO BE UNDER THE | | | FOUNDATION. PER NFPA 24 THIS IS A VIOLATION OF THE | | | REQUIRERMENT. | | | | | | NOT COMPLIED. THERE IS NO DRAWING OR NOTE THAT SAYS THE | | | FIRE LINE BEING MOVED. | | | | | | ADDITIONALLY, IT SHALL BE NOTED ON THE RESUBMITTAL THAT | | | ALL UNDERGROUND WORK SHALL COMPLY WITH NFPA 24, | | | STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE | | | MAINS AND THEIR APPURTENANCES, 2010 EDITION.AND BE DONE | | | UNDER SEPARATE PERMIT BY CERTIFIED FLORIDA UNDERGROUND | | | CONTRACTORS. NO FIRE LINE PIPE SHALL BE COVERED OVER | | | PRIOR TO A FIRE INSPECTION. | | | | | | 10.6 PROTECTION AGAINST DAMAGE. | | | 10.6.1 PIPE SHALL NOT BE RUN UNDER BUILDINGS. | | | 10.6.2 WHERE PIPE MUST BE RUN UNDER BUILDINGS, SPECIAL | | | PRECAUTIONS SHALL BE TAKEN, INCLUDING THE FOLLOWING: | | | (1) ARCHING THE FOUNDATION WALLS OVER THE PIPE | | | (2) RUNNING PIPE IN COVERED TRENCHES | | | (3) PROVIDING VALVES TO ISOLATE SECTIONS OF PIPE UNDER | | | BUILDINGS | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-06-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-06-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-06-16 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2017-06-19 10:26:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THIS REVIEW AND THE COMMENTS ARE RELATED TO THE | | | FOUNDATION PERMIT ONLY. | | | | | | | | | 1) SHEET 2 OF 8 - THERE ARE NO INDICATION HOW THE | | | EXISTING REQUIRED EXITING, INCLUDING WALKWAY AND | | | STAIRS, WILL BE MAINTAINED DURING DEMO AND ALL PHASES | | | OF CONSTRUCTION. | | | | | | PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN INDICATING | | | HOW AND WHERE THE EXITING FROM THE CURRENT BUILDING | | | WILL BE MAINTAINED AND PROTECTED. | | | | | | | | | | | | | | | 2) SHEET 7 OF 8 - THE FIRE LINE APPEARS TO BE UNDER THE | | | FOUNDATION. PER NFPA 24 THIS IS A VIOLATION OF THE | | | REQUIRMENT. | | | | | | 10.6 PROTECTION AGAINST DAMAGE. | | | 10.6.1 PIPE SHALL NOT BE RUN UNDER BUILDINGS. | | | 10.6.2 WHERE PIPE MUST BE RUN UNDER BUILDINGS, SPECIAL | | | PRECAUTIONS SHALL BE TAKEN, INCLUDING THE FOLLOWING: | | | (1) ARCHING THE FOUNDATION WALLS OVER THE PIPE | | | (2) RUNNING PIPE IN COVERED TRENCHES | | | (3) PROVIDING VALVES TO ISOLATE SECTIONS OF PIPE UNDER | | | BUILDINGS | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-09-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-26 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-20 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2017-09-25 15:24:51 | 9/25/17 TO GJ DESK | | | | | | | | 2017-09-20 11:25:47 | TO SOFIA (ENGINEERING) | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-08-30 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-08-30 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-08-21 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-07-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-07-20 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-06-09 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-11-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-06 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-11-06 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2017-11-06 09:57:04 | MU 2017-30025, $3,148.12 | | | CONTRACTOR USED JOB SET FOR IMPACT FEE REVIEW AS THE | | | REVISION PLAN (STEEL STRUCTURE) DID NOT HAVE THE | | | INFORMATION REQUIRED. I PHOTOCOPIED THE IMPACT FEE | | | STAMP AND RETURNED THE ORIGINAL PLAN TO CONTRACTOR. | | | | | | STEEL STRUCTURE AND IMPACT REVIEWED UNDER REVISION | | | 17100798 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2017-06-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-15 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-15 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2017-06-15 16:30:29 | IMPACT FEES DUE AT TIME OF BUILDING OR STRUCTURE PERMIT | | | (VERTICAL) |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2017-08-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-08-25 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-09-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-09-26 |
Time |
07:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-26 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2017-09-26 07:01:00 | PROVISO: | | | THESE CORRECTIONS SHALL BE MADE ON REVISED SHEETS PRIOR | | | TO 1ST ROUGH INSPECTION. | | | 1.THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN | | | THE TWO MOST UPSTREAM WATER CLOSET DRAINS. THE VENT | | | SHALL CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE | | | INSTALLED IN ACCORDANCE WITH SECTION 905. THE CIRCUIT | | | VENT PIPE SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL | | | OR WASTE. PER FBC PL 914.2 | | | 2. PLEASE PROVIDE SQFT DRAINED BY ROOF DRAINS. PER WPB | | | AMEND TO FBC 107.2.1 | | | 3. PLEASE EXPAND SANITARY RISER IT IS DIFFICULT TO READ | | | AND WHEN IT IS SCANNED IN FOR OUR RECORDS IT WILL BE | | | EVEN HARDER TO READ. WPB AMEND TO FBC 107.2.1.4 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-08-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-08-24 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-08-24 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2017-08-24 15:15:44 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1.THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN | | | THE TWO MOST UPSTREAM WATER CLOSET DRAINS. THE VENT | | | SHALL CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE | | | INSTALLED IN ACCORDANCE WITH SECTION 905. THE CIRCUIT | | | VENT PIPE SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL | | | OR WASTE. PER FBC PL 914.2 | | | | | | 2. PLEASE PROVIDE SQFT DRAINED BY ROOF DRAINS. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 3. PLEASE EXPAND SANITARY RISER IT IS DIFFICULT TO READ | | | AND WHEN IT IS SCANNED IN FOR OUR RECORDS IT WILL BE | | | EVEN HARDER TO READ. WPB AMEND TO FBC 107.2.1.4 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-06-14 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-06-14 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-06-14 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2017-06-14 14:40:53 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. A3.01 SHOWS THE RAIN WATER LEADER EXITING | | | BUILDING ABOVE THE SLAB, SHT S403 DETAIL J+K SHOWS DOWN | | | SPOUT EXITING THROUGH THE FOOTER PLEASE CLARIFY. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 2. PLEASE PROVIDE PLUMBING FLOOR PLAN AND SANITARY , | | | STORM RISER DIAGRAMS. PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
P |
Date |
2017-09-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-20 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-19 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2017-09-19 15:13:47 | SPECIAL INSPECTOR AGREEMENT, PORTIONS APPROVED: | | | TIERRA SOUTH FLORIDA | | | FRANCOIS THOMAS, PE 56381, SI 7021399 | | | PEDRO ROSA, BN3764 | | | ANDREW MORGAN, PE 57171 (SEOR) | | | | | | ***PROVISO*** | | | A RESUME WAS SUBMITTED FOR ENRIQUE BURBANO BUT HE HAS | | | NOT SIGNED THE AGREEMENT AS OF 9/19/17. PROVIDE SI | | | AGREEMENT PAGE 3 OF 4, SIGNED BY FRANCOIS THOMAS, PE,SI | | | AND ENRIQUE BURBANO, BN4650 | | | | | | ORIGINALS SENT TO RECORDS ON 9/20/17 UNDER PERMIT | | | NUMBERS 17040807, 17060234 |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2017-06-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-15 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-15 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2017-06-15 16:29:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | THE DOCUMENT SUBMITTED IS A PHOTOCOPY, ORIGINAL SIGNED | | | SEALED ENGINEERING REQUIRED FS471. | | | | | | B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | C) THRESHOLD BLDG., REQUIRED STATEMENT - OK | | | | | | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | PROVIDE A RESUME FOR EACH INSPECTOR. | | | | | | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. | | | | | | F) THE SPECIAL INSPECTOR AGREEMENT SIGNED BY ALL | | | PARTIES IS REQUIRED. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2017-09-19 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-09-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2017-09-19 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2017-08-25 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-08-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2017-08-25 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-08-25 15:35:04 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE SITE PLAN IS MISSING FROM THE PERMIT SUBMITTAL. | | | PLEASE PROVIDE. [7/6/17 REPEAT COMMENT] | | | | | | 2.) ARCHITECTURAL FLOOR PLANS AND ELEVATIONS DO NOT | | | MATCH THE APPROVED PLANS. PLEASE ADDRESS. NOTE: ANY | | | MODIFICATION TO THE APPROVED PLANS WILL REQUIRE A MINOR | | | AMENDMENT TO THE APPROVED PLANS PRIOR TO BUILDING | | | PERMIT. [7/6/17 REPEAT COMMENT] | | | | | | | | | NOTES: | | | | | | * REFERENCE: ISPR 16-01B (CONDITIONAL APPROVAL LETTER | | | ISSUED ON 6/29/17) | | | | | | * A RE-PLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO | | | THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.) | | | | | | * SEPARATE PERMIT SUBMITTAL AND REVIEW REQUIRED FOR | | | LANDSCAPE IMPROVEMENTS. | | | | | | * APPLICATION FOR A MINOR SITE PLAN AMENDMENT (IF | | | NECESSARY) CAN BE FOUND IN THE 2017 DEVELOPMENT | | | APPLICATION, AVAILABLE FOR DOWNLOAD ON THE CITY'S | | | WEBSITE. | | | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2017-07-03 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-07-03 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2017-06-30 |
Time |
|
Sent To |
ENG |
|
| Notes |
| 2017-07-03 09:21:24 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE SITE PLAN IS MISSING FROM THE PERMIT SUBMITTAL. | | | PLEASE PROVIDE. | | | | | | 2.) ARCHITECTURAL FLOOR PLANS AND ELEVATIONS DO NOT | | | MATCH THE APPROVED PLANS. PLEASE ADDRESS. NOTE: ANY | | | MODIFICATION TO THE APPROVED PLANS WILL REQUIRE A MINOR | | | AMENDMENT TO THE APPROVED PLANS PRIOR TO BUILDING | | | PERMIT. | | | | | | | | | NOTES: | | | | | | * REFERENCE: ISPR 16-01B (CONDITIONAL APPROVAL LETTER | | | ISSUED ON 6/29/17) | | | | | | * A RE-PLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO | | | THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.) | | | | | | * SEPARATE PERMIT SUBMITTAL AND REVIEW REQUIRED FOR | | | LANDSCAPE IMPROVEMENTS. | | | | | | * APPLICATION FOR A MINOR SITE PLAN AMENDMENT (IF | | | NECESSARY) CAN BE FOUND IN THE 2017 DEVELOPMENT | | | APPLICATION, AVAILABLE FOR DOWNLOAD ON THE CITY'S | | | WEBSITE. | | | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|