Plan Review Details - Permit 17060234
Plan Review Stops For Permit 17060234
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-09-26 Cont ID  
Sent By shill Date 2017-09-26 Time 08:43 Rev Time 0.00
Received By shill Date 2017-09-26 Time 08:28 Sent To  
Notes
2017-09-26 08:55:52****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PERMIT IS ISSUED AT APPLICANT'S RISK
  
 A. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL
 OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 B. REPLAT TO BE RECORDED PRIOR TO C.O.
  
 C. LIFE SAFETY AND OTHER ITEMS NOT REVIEWED; INTERIOR
 WILL BE REVIEWED UNDER THE BUILDING PERMIT. SOME PAGES
 IN THIS SUBMITTAL HAVE NOT BEEN REVIEWED BUT HAVE BEEN
 RETAINED IN THE SUBMITTAL FOR INFORMATIONAL PURPOSES.
  
 D. REVISE PLAN FOR BUILDING (VERTICAL) PERMIT; THE
 ASSEMBLY SPACES ARE FOR USE BY THE SCHOOL ONLY AND NO
 OTHER ENTITIES.
  
 E. MAINTAIN MEANS OF EGRESS/EXITING FOR EXISTING SCHOOL
 IN COMPLIANCE WITH FBC BUILDING CHAPTER 10.
  
 F. AFTER ISSUANCE, OBTAIN A COMPLETE COPY OF THE ISSUED
 PLANS, FOR THE SPECIAL INSPECTOR. COLOR COPY IS
 RECOMMENDED BUT NOT REQUIRED. NOTE THAT THE INSPECTION
 SET MUST BE THE SET ISSUED BY THE BUILDING DIVISION
 (COLOR STAMPS AND REVIEWER SIGNATURES), FBC 107.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 15:55 Rev Time 0.00
Received By shill Date 2017-08-29 Time 15:55 Sent To  
Notes
2017-08-29 15:55:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. THRESHOLD INSPECTION PLAN AND SOILS REPORT ARE
 PHOTOCOPIES; ORIGINALS REQUIRED FS471.
  
 2ND REVIEW; THE THRESHOLD INSPECTION PLAN AND SOILS
 REPORT ARE ALSO (STILL) PHOTOCOPIES (NO NEW DOCUMENTS
 SUBMITTED). RESPONSE LETTER STATES "COMPLIED. MULTIPLE
 ORIGINALS HAVE BEEN SUBMITTED WITH THIS PROJECT'S
 PREVIOUS PERMIT SUBMISSION. PLEASE REFERENCE THE TWO
 COPIES SUBMITTED WITH THIS RE-SUBMISSION AND/OR WITH
 THE MAIN BUILDING PERMIT SET."
  
 FBC 107, APPLICANT IS TO PROVIDE ALL DOCUMENTS REQUIRED
 TO DETERMINE CODE COMPLIANCE. DOCUMENTS IN ANOTHER
 PERMIT APPLICATION CANNOT BE USED FOR THIS PERMIT.
 DOCUMENTS WITH ANOTHER PERMIT APPLICATION ARE NOT
 OFFICIAL PERMIT RECORD UNTIL ISSUANCE. DOCUMENTS
 PREPARED BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED, DATED ORIGINALS. PLEASE
 PROVIDE THE ORIGINAL DOCUMENTS REQUESTED.
  
 2. SEE FIRE COMMENTS. ADVISE AS TO HOW EXITING FOR THE
 EXISTING SCHOOL WILL BE AFFECTED BY THE PROPOSED
 CONSTRUCTION. THIS INFORMATION IS REQUIRED PRIOR TO
 COMMENCEMENT OF ANY WORK AFFECTING THE EXIT AND EXIT
 DISCHARGE FOR EXISTING SCHOOL.
  
 2ND REVIEW, SEE FIRE REVIEW.
  
 NEW COMMENTS:
  
 3. AN ENTIRELY NEW SET OF PLANS WAS SUBMITTED. THE
 STRUCTURAL PAGES ARE NOT SIGNED, SEALED, DATED
 ORIGINALS (PHOTOCOPIES), SEE FS 471.
  
 4. PLEASE REMOVE SHEETS NOT REQUIRED FOR THIS
 FOUNDATION SUBMITTAL. FOR INSTANCE:
  
 CIVIL SHEET 5, PAVING AND DRAINAGE DETAILS
 A0.05, SECOND FLOOR LIFE SAFETY PLAN - SOUTH
 A0.16 WINDOW ELEVATIONS
  
 IT APPEARS THAT A FULL SET OF PLANS FOR THE BUILDING
 WAS SUBMITTED. PAGES NOT NEEDED FOR FOUNDATION SHOULD
 BE REMOVED. GENERALLY, DOCUMENTS REQUIRED FOR
 FOUNDATION PERMIT ARE:
  
 PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION
 PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB)
 GEOTECHNICAL REPORT
 SURVEY DRAWING
 STORM WATER POLLUTION PREVENTION PLAN
 SITE PLAN
 1ST FLOOR ARCHITECTURAL PLAN
 ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING
 FOUNDATION PLAN
 FOUNDATION DETAILS AND CROSS SECTIONS
 STRUCTURAL ENGINEER'S GENERAL NOTES
 UNDERGROUND PLUMBING PLAN (IF APPLICABLE)
 ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT (IF
 APPLICABLE)
 ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR
 EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT).
 IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT,
 AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR
 PLAN SHOWING UNDERGROUND FIRE LINE
 THRESHOLD INSPECTION PLAN OR RESIDENT INSPECTION PLAN
 (AS APPLICABLE)
 SI OR RESIDENT INSPECTOR AGREEMENT (AS APPLICABLE)
  
 5. THREE COMPLETE IDENTICAL SETS OF PLANS AND PERMIT
 DOCUMENTS REQUIRED, FBC 107.
  
 6. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 PERMIT IS ISSUED AT APPLICANT'S RISK
  
 A. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL
 OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 B. REPLAT TO BE RECORDED PRIOR TO C.O.
  
 C. LIFE SAFETY AND OTHER ITEMS NOT REVIEWED; INTERIOR
 WILL BE REVIEWED UNDER THE BUILDING PERMIT.
  
 D. REVISE PLAN; THE ASSEMBLY SPACES ARE FOR USE BY THE
 SCHOOL ONLY AND NO OTHER ENTITIES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-15 Cont ID  
Sent By shill Date 2017-06-15 Time 16:13 Rev Time 0.00
Received By shill Date 2017-06-15 Time 08:47 Sent To  
Notes
2017-06-15 16:13:23****CORRECTIONS****
 REVISED 8/11/17
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THRESHOLD INSPECTION PLAN AND SOILS REPORT ARE
 PHOTOCOPIES; ORIGINALS REQUIRED FS471.
  
 2. SEE FIRE COMMENTS. ADVISE AS TO HOW EXITING FOR THE
 EXISTING SCHOOL WILL BE AFFECTED BY THE PROPOSED
 CONSTRUCTION. THIS INFORMATION IS REQUIRED PRIOR TO
 COMMENCEMENT OF ANY WORK AFFECTING THE EXIT AND EXIT
 DISCHARGE FOR EXISTING SCHOOL.
  
 3. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 PERMIT IS ISSUED AT APPLICANT'S RISK
  
 A. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL
 OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 B. REPLAT TO BE RECORDED PRIOR TO C.O.
  
 C. LIFE SAFETY AND OTHER ITEMS NOT REVIEWED; INTERIOR
 WILL BE REVIEWED UNDER THE BUILDING PERMIT.
  
 D. REVISE PLAN; THE ASSEMBLYL SPACES ARE FOR USE BY THE
 SCHOOL ONLY AND NO OTHER ENTITIES.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-09-20 Cont ID  
Sent By jpearson Date 2017-09-20 Time 12:44 Rev Time 0.00
Received By jpearson Date 2017-09-20 Time 12:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-08-23 Cont ID  
Sent By jpearson Date 2017-08-23 Time 11:13 Rev Time 0.00
Received By jpearson Date 2017-08-23 Time 11:13 Sent To  
Notes
2017-08-23 11:13:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEW SUBMISSION SHOWS MODIFICATIONS TO THE EXISTING
 SERVICE. PROVIDE CLARIFICATION. IS THIS SERVICE AT A
 DIFFERENT ADDRESS, REQUIRING A SEPARATE PERMIT? WHY IS
 PANEL K BEING ADDED? PANEL K AND THE EXISTING SERVICE
 ARE NOT SHOWN ON POWER PLAN SUBMITTED, WHAT IS THE
 LOCATION OF THESE ITEMS? PROVIDE LOAD CALCULATION FOR
 EXISTING SERVICE AND JUSTIFICATION FOR INCREASE (?) IN
 SIZE. PROVIDE NOTE FOR ANY SEPARATE PERMITS REQUIRED.
 FBC 107.2.1
  
 BECAUSE THIS IS FOR A FOUNDATION PERMIT ONLY, THIS IS
 THE ONLY QUESTION AT THIS TIME. WHEN A FULL PLAN REVIEW
 IS COMPLETED FOR THE MASTER PERMIT, ADDITIONAL COMMENTS
 WILL BE FORTHCOMING.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-20 Cont ID  
Sent By jpearson Date 2017-06-14 Time 07:40 Rev Time 0.00
Received By jpearson Date 2017-06-14 Time 07:40 Sent To  
Notes
2017-06-14 07:41:32REVIEWED FOR FOUNDATION ONLY.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2017-09-20 Cont ID  
Sent By squinone Date 2017-09-20 Time   Rev Time 0.00
Received By squinone Date 2017-09-20 Time   Sent To FIRE
Notes
2017-09-20 17:12:00STATUS: PASSED WITH CONDITIONS
  
 1. DO NOT USE FLAMINGO DRIVE FOR CONSTRUCTION TRAFFIC.
 2. PHASE 1 OF PARTIAL FOOTING AND FOUNDATION
 CONSTRUCTION MUST BE 15-FEET MINIMUM FROM THE EXISTING
 WATERMAIN. REFER TO CIVIL SHEET 7 OF 8 TO REVIEW MARKUP
 OF ALLOWED PARTIAL FOOTING AND FOUNDATION CONSTRUCTION.
 UPON COMPLETION OF UTILITY REMOVAL, THE APPLICANT MUST
 APPLY FOR ANOTHER PARTIAL FOOTING AND FOUNDATION PERMIT
 FOR APPROVAL OF SECOND PHASE.
  
 LET ME KNOW IF THERE ARE ANY QUESTIONS OR CONCERNS.
  
 SINCERELY,
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 P: 561.494.1040 EXT: 1108
 F: 561.494.1116
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2017-08-30 Cont ID  
Sent By squinone Date 2017-08-30 Time   Rev Time 0.00
Received By squinone Date 2017-08-30 Time   Sent To I
Notes
2017-08-30 10:23:18PROJECT: THE GREENE SCHOOL - ADDITION
 PERMIT NO. 17060234
 STATUS: FAILED
  
 COMMENTS (PLEASE RESPOND TO COMMENTS IN WRITTING):
 1. REMOVAL OF EXISTING UTILITIES HAS TO BE COMPLETED
 PRIOR TO FOUNDATION PERMIT APPROVAL.
 2. A REPLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO
 THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY (C.O.) FOR
 THE EXPANSION.
  
 LET ME KNOW IF THERE ARE ANY QUESTIONS OR CONCERNS.
  
 SINCERELY,
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By SQ Date 2017-07-19 Time   Rev Time 8.00
Received By squinone Date 2017-07-19 Time   Sent To I
Notes
2017-07-19 14:10:40THE GREENE SCHOOL - ADDITION, 17060234
  
 COMMENTS:
 1. PLANS ARE CURRENTLY UNDER REVIEW IN ENGINEERING.
 2. RIGHT OF WAY PERMIT IS REQUIRED FOR THE CONSTRUCTION
 OF THE DRIVEWAYS ON FLAMINGO AND BISCAYNE.
 3. REMOVE PARKING STRIPING FROM FLAMINGO.
 4. DO NOT USE FLAMINGO DRIVE FOR CONSTRUCTION TRAFFIC.
  
 LET ME KNOW IF THERE ARE ANY QUESTIONS OR CONCERNS.
  
 SINCERELY,
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 P: 561.494.1040 EXT: 1108
 F: 561.494.1116
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-09-25 Cont ID  
Sent By pleduc Date 2017-09-25 Time   Rev Time 0.00
Received By pleduc Date 2017-09-25 Time 12:06 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-08-28 Cont ID  
Sent By pleduc Date 2017-08-28 Time   Rev Time 0.00
Received By pleduc Date 2017-08-28 Time 13:56 Sent To  
Notes
2017-08-28 14:24:402ND REVIEW COMMENTS
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THIS REVIEW AND THE COMMENTS ARE RELATED TO THE
 FOUNDATION PERMIT ONLY.
  
  
 1) SHEET 2 OF 8 - THERE ARE NO INDICATION HOW THE
 EXISTING REQUIRED EXITING, INCLUDING WALKWAY AND
 STAIRS, WILL BE MAINTAINED DURING DEMO AND ALL PHASES
 OF CONSTRUCTION.
  
 NOT COMPLIED. YOUR COMMENTS THAT A DETAILED LIFE SAFETY
 PLAN WAS SUBMITTED COULD NOT BE FOUND.
  
 THE LIFE SAFETY PLAN SHALL INCLUDED THE EXIT PATH FROM
 ALL SOUTH END EXITS, INCLUDING THE STAIRS FROM THE 2 ND
 FL, THE TRAVEL PATH LEADING TO A POINT OF PUBLIC WAY,
 THESE PLANS SHALL INCLUDE EXIT WIDTH, ELEVATION
 CHANGES, EXIT SIGNAGE, SEPARATION MEASURES FROM
 CONSTRUCTION.
  
 THESE ITEMS WERE DISCUSSED AT LENGTH DURING A MEETING
 WITH THE AHRENS TEAM.
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN INDICATING
 HOW AND WHERE THE EXITING FROM THE CURRENT BUILDING
 WILL BE MAINTAINED AND PROTECTED.
  
  
  
  
 2) SHEET 7 OF 8 - THE FIRE LINE APPEARS TO BE UNDER THE
 FOUNDATION. PER NFPA 24 THIS IS A VIOLATION OF THE
 REQUIRERMENT.
  
 NOT COMPLIED. THERE IS NO DRAWING OR NOTE THAT SAYS THE
 FIRE LINE BEING MOVED.
  
 ADDITIONALLY, IT SHALL BE NOTED ON THE RESUBMITTAL THAT
 ALL UNDERGROUND WORK SHALL COMPLY WITH NFPA 24,
 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE
 MAINS AND THEIR APPURTENANCES, 2010 EDITION.AND BE DONE
 UNDER SEPARATE PERMIT BY CERTIFIED FLORIDA UNDERGROUND
 CONTRACTORS. NO FIRE LINE PIPE SHALL BE COVERED OVER
 PRIOR TO A FIRE INSPECTION.
  
 10.6 PROTECTION AGAINST DAMAGE.
 10.6.1 PIPE SHALL NOT BE RUN UNDER BUILDINGS.
 10.6.2 WHERE PIPE MUST BE RUN UNDER BUILDINGS, SPECIAL
 PRECAUTIONS SHALL BE TAKEN, INCLUDING THE FOLLOWING:
 (1) ARCHING THE FOUNDATION WALLS OVER THE PIPE
 (2) RUNNING PIPE IN COVERED TRENCHES
 (3) PROVIDING VALVES TO ISOLATE SECTIONS OF PIPE UNDER
 BUILDINGS
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-19 Cont ID  
Sent By pleduc Date 2017-06-19 Time   Rev Time 0.00
Received By pleduc Date 2017-06-16 Time 16:38 Sent To  
Notes
2017-06-19 10:26:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THIS REVIEW AND THE COMMENTS ARE RELATED TO THE
 FOUNDATION PERMIT ONLY.
  
  
 1) SHEET 2 OF 8 - THERE ARE NO INDICATION HOW THE
 EXISTING REQUIRED EXITING, INCLUDING WALKWAY AND
 STAIRS, WILL BE MAINTAINED DURING DEMO AND ALL PHASES
 OF CONSTRUCTION.
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN INDICATING
 HOW AND WHERE THE EXITING FROM THE CURRENT BUILDING
 WILL BE MAINTAINED AND PROTECTED.
  
  
  
  
 2) SHEET 7 OF 8 - THE FIRE LINE APPEARS TO BE UNDER THE
 FOUNDATION. PER NFPA 24 THIS IS A VIOLATION OF THE
 REQUIRMENT.
  
 10.6 PROTECTION AGAINST DAMAGE.
 10.6.1 PIPE SHALL NOT BE RUN UNDER BUILDINGS.
 10.6.2 WHERE PIPE MUST BE RUN UNDER BUILDINGS, SPECIAL
 PRECAUTIONS SHALL BE TAKEN, INCLUDING THE FOLLOWING:
 (1) ARCHING THE FOUNDATION WALLS OVER THE PIPE
 (2) RUNNING PIPE IN COVERED TRENCHES
 (3) PROVIDING VALVES TO ISOLATE SECTIONS OF PIPE UNDER
 BUILDINGS
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-09-26 Cont ID  
Sent By shill Date 2017-09-26 Time 08:55 Rev Time 0.00
Received By shill Date 2017-09-20 Time 11:25 Sent To  
Notes
2017-09-25 15:24:519/25/17 TO GJ DESK
  
  
2017-09-20 11:25:47TO SOFIA (ENGINEERING)
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-30 Cont ID  
Sent By cpuell Date 2017-08-30 Time 16:41 Rev Time 0.00
Received By cpuell Date 2017-08-21 Time 13:49 Sent To  
Notes
2017-08-22 13:50:10C02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-20 Cont ID  
Sent By cpuell Date 2017-07-20 Time 13:07 Rev Time 0.00
Received By cpuell Date 2017-06-09 Time 10:10 Sent To  
Notes
2017-06-13 10:11:22C02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-11-06 Cont ID  
Sent By shill Date 2017-11-06 Time 09:56 Rev Time 0.00
Received By shill Date 2017-11-06 Time 09:56 Sent To  
Notes
2017-11-06 09:57:04MU 2017-30025, $3,148.12
 CONTRACTOR USED JOB SET FOR IMPACT FEE REVIEW AS THE
 REVISION PLAN (STEEL STRUCTURE) DID NOT HAVE THE
 INFORMATION REQUIRED. I PHOTOCOPIED THE IMPACT FEE
 STAMP AND RETURNED THE ORIGINAL PLAN TO CONTRACTOR.
  
 STEEL STRUCTURE AND IMPACT REVIEWED UNDER REVISION
 17100798

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-06-15 Cont ID  
Sent By shill Date 2017-06-15 Time 16:30 Rev Time 0.00
Received By shill Date 2017-06-15 Time 16:30 Sent To  
Notes
2017-06-15 16:30:29IMPACT FEES DUE AT TIME OF BUILDING OR STRUCTURE PERMIT
 (VERTICAL)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-08-25 Cont ID  
Sent By ccole Date 2017-08-25 Time 14:17 Rev Time 0.00
Received By ccole Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-09-26 Cont ID  
Sent By gjohnson Date 2017-09-26 Time 07:01 Rev Time 0.00
Received By gjohnson Date 2017-09-26 Time 07:00 Sent To  
Notes
2017-09-26 07:01:00PROVISO:
 THESE CORRECTIONS SHALL BE MADE ON REVISED SHEETS PRIOR
 TO 1ST ROUGH INSPECTION.
 1.THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM WATER CLOSET DRAINS. THE VENT
 SHALL CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 905. THE CIRCUIT
 VENT PIPE SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL
 OR WASTE. PER FBC PL 914.2
 2. PLEASE PROVIDE SQFT DRAINED BY ROOF DRAINS. PER WPB
 AMEND TO FBC 107.2.1
 3. PLEASE EXPAND SANITARY RISER IT IS DIFFICULT TO READ
 AND WHEN IT IS SCANNED IN FOR OUR RECORDS IT WILL BE
 EVEN HARDER TO READ. WPB AMEND TO FBC 107.2.1.4
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-08-24 Cont ID  
Sent By gjohnson Date 2017-08-24 Time 15:01 Rev Time 0.00
Received By gjohnson Date 2017-08-24 Time 15:15 Sent To  
Notes
2017-08-24 15:15:441ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1.THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM WATER CLOSET DRAINS. THE VENT
 SHALL CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 905. THE CIRCUIT
 VENT PIPE SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL
 OR WASTE. PER FBC PL 914.2
  
 2. PLEASE PROVIDE SQFT DRAINED BY ROOF DRAINS. PER WPB
 AMEND TO FBC 107.2.1
  
 3. PLEASE EXPAND SANITARY RISER IT IS DIFFICULT TO READ
 AND WHEN IT IS SCANNED IN FOR OUR RECORDS IT WILL BE
 EVEN HARDER TO READ. WPB AMEND TO FBC 107.2.1.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-14 Cont ID  
Sent By gjohnson Date 2017-06-14 Time 14:28 Rev Time 0.00
Received By gjohnson Date 2017-06-14 Time 14:28 Sent To  
Notes
2017-06-14 14:40:531ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A3.01 SHOWS THE RAIN WATER LEADER EXITING
 BUILDING ABOVE THE SLAB, SHT S403 DETAIL J+K SHOWS DOWN
 SPOUT EXITING THROUGH THE FOOTER PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 2. PLEASE PROVIDE PLUMBING FLOOR PLAN AND SANITARY ,
 STORM RISER DIAGRAMS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2017-09-20 Cont ID  
Sent By shill Date 2017-09-20 Time 09:57 Rev Time 0.00
Received By shill Date 2017-09-19 Time 15:13 Sent To  
Notes
2017-09-19 15:13:47SPECIAL INSPECTOR AGREEMENT, PORTIONS APPROVED:
 TIERRA SOUTH FLORIDA
 FRANCOIS THOMAS, PE 56381, SI 7021399
 PEDRO ROSA, BN3764
 ANDREW MORGAN, PE 57171 (SEOR)
  
 ***PROVISO***
 A RESUME WAS SUBMITTED FOR ENRIQUE BURBANO BUT HE HAS
 NOT SIGNED THE AGREEMENT AS OF 9/19/17. PROVIDE SI
 AGREEMENT PAGE 3 OF 4, SIGNED BY FRANCOIS THOMAS, PE,SI
 AND ENRIQUE BURBANO, BN4650
  
 ORIGINALS SENT TO RECORDS ON 9/20/17 UNDER PERMIT
 NUMBERS 17040807, 17060234

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-06-15 Cont ID  
Sent By shill Date 2017-06-15 Time 16:13 Rev Time 0.00
Received By shill Date 2017-06-15 Time 08:47 Sent To  
Notes
2017-06-15 16:29:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 THE DOCUMENT SUBMITTED IS A PHOTOCOPY, ORIGINAL SIGNED
 SEALED ENGINEERING REQUIRED FS471.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 C) THRESHOLD BLDG., REQUIRED STATEMENT - OK
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 PROVIDE A RESUME FOR EACH INSPECTOR.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) THE SPECIAL INSPECTOR AGREEMENT SIGNED BY ALL
 PARTIES IS REQUIRED.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-09-19 Cont ID  
Sent By llouie Date 2017-09-19 Time   Rev Time 0.00
Received By llouie Date 2017-09-19 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2017-08-25 Cont ID  
Sent By llouie Date 2017-08-25 Time   Rev Time 0.00
Received By llouie Date 2017-08-25 Time   Sent To  
Notes
2017-08-25 15:35:04** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE SITE PLAN IS MISSING FROM THE PERMIT SUBMITTAL.
 PLEASE PROVIDE. [7/6/17 REPEAT COMMENT]
  
 2.) ARCHITECTURAL FLOOR PLANS AND ELEVATIONS DO NOT
 MATCH THE APPROVED PLANS. PLEASE ADDRESS. NOTE: ANY
 MODIFICATION TO THE APPROVED PLANS WILL REQUIRE A MINOR
 AMENDMENT TO THE APPROVED PLANS PRIOR TO BUILDING
 PERMIT. [7/6/17 REPEAT COMMENT]
  
  
 NOTES:
  
 * REFERENCE: ISPR 16-01B (CONDITIONAL APPROVAL LETTER
 ISSUED ON 6/29/17)
  
 * A RE-PLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.)
  
 * SEPARATE PERMIT SUBMITTAL AND REVIEW REQUIRED FOR
 LANDSCAPE IMPROVEMENTS.
  
 * APPLICATION FOR A MINOR SITE PLAN AMENDMENT (IF
 NECESSARY) CAN BE FOUND IN THE 2017 DEVELOPMENT
 APPLICATION, AVAILABLE FOR DOWNLOAD ON THE CITY'S
 WEBSITE.
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-03 Cont ID  
Sent By llouie Date 2017-07-03 Time   Rev Time  
Received By llouie Date 2017-06-30 Time   Sent To ENG
Notes
2017-07-03 09:21:24** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE SITE PLAN IS MISSING FROM THE PERMIT SUBMITTAL.
 PLEASE PROVIDE.
  
 2.) ARCHITECTURAL FLOOR PLANS AND ELEVATIONS DO NOT
 MATCH THE APPROVED PLANS. PLEASE ADDRESS. NOTE: ANY
 MODIFICATION TO THE APPROVED PLANS WILL REQUIRE A MINOR
 AMENDMENT TO THE APPROVED PLANS PRIOR TO BUILDING
 PERMIT.
  
  
 NOTES:
  
 * REFERENCE: ISPR 16-01B (CONDITIONAL APPROVAL LETTER
 ISSUED ON 6/29/17)
  
 * A RE-PLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.)
  
 * SEPARATE PERMIT SUBMITTAL AND REVIEW REQUIRED FOR
 LANDSCAPE IMPROVEMENTS.
  
 * APPLICATION FOR A MINOR SITE PLAN AMENDMENT (IF
 NECESSARY) CAN BE FOUND IN THE 2017 DEVELOPMENT
 APPLICATION, AVAILABLE FOR DOWNLOAD ON THE CITY'S
 WEBSITE.
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  