Plan Review Details - Permit 17060222
Plan Review Stops For Permit 17060222
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-04 Cont ID  
Sent By fstal Date 2017-10-04 Time 10:05 Rev Time 0.00
Received By fstal Date   Time   Sent To M
Notes
2017-10-03 16:20:3310/04/2017
  
 PASS WITH PROVISO COMMENTS:
  
 FFPC 1.14.4 REVIEW AND APPROVAL SHALL NOT RELIEVE THE
 APPLICANT OF THE RESPONSIBILITY OF COMPLIANCE WITH THE
 CODE.
  
 TRASH CHUTE SPECIFICATION /CUT SHEET REQUIRED. CHUTE
 TERMINATION FLOOR, WILL THERE BE A FUSIBLE LINK TO
 CLOSE THE CHUTE AND FIRE SPRINKLER HEAD TO PROTECT THE
 TRASH DUMPSTER. SUBMIT DETAIL DRAWINGS AND PROVIDE
 PLANS ON JOB SITE.
  
 TRASH CHUTE INSTALLATION SHALL COME INTO COMPLIANCE
 WITH NFPA 82.
  
 STANDPIPE # 2, DETAIL INDICATES NO PSI GAUGE. PROVIDE
 PSI GAUGE.
  
 NOTE: PRV WILL BE SET AND TAGGED FROM THE FACTORY.
  
 THESE CODES ARE MINIMUM REQUIREMENTS ALL INSTALLATION
 SHALL COMPLY WITH NFPA 13, 14 STATE AND LOCAL CODES.
 ONSITE INSPECTIONS AND VERIFICATIONS BY A FIRE
 PREVENTION BUREAU INSPECTOR MAY NECESSITATE
 ADJUSTMENTS, ADDITIONS, RELOCATIONS, PERFORMANCE
 TESTING AND/OR OTHER APPLICATION DIMENSION TO MEET THE
 LIFE SAFETY COMPLIANCE CRITERIA.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-22 Cont ID  
Sent By fstal Date 2017-06-22 Time 17:19 Rev Time  
Received By fstal Date   Time   Sent To M
Notes
2017-06-22 17:21:08NFPA 1-14.2, 2012 THE APPLICANT SHALL BE RESPONSIBLE TO
 ENSURE THAT THE FOLLOWING CONDITIONS ARE MET:
 (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE
 PROTECTION REQUIREMENTS.
 (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE
 WITH THE APPLICABLE CODES AND STANDARDS.
  
 PROVIDE FIRE SPRINKLER ISOMETRIC PLAN, FOR TRASH
 CHUTES. INSTALLATIONS SHALL COME IN COMPLIANCE WITH
 NFPA 13 AND 82-5.2.6.1. ALSO INDICATE WHAT FLOOR CHUTE
 TERMINATES. 82-5.2.6.1, 2009 EDITION GRAVITY CHUTE.
 5.2.6.1.1 GRAVITY CHUTES SHALL BE PROTECTED INTERNALLY
 BY AUTOMATIC SPRINKLERS.
 5.2.6.1.2 THIS PROTECTION REQUIRES THAT A SPRINKLER BE
 INSTALLED AT OR ABOVE THE TOP SERVICE OPENING OF THE
 CHUTE.
 5.2.6.1.3 THIS PROTECTION REQUIRES AUTOMATIC SPRINKLERS
 INSTALLED IN GRAVITY CHUTE SERVICE OPENINGS SHALL BE
 RECESSED OUT OF THE CHUTE AREA THROUGH WHICH THE
 MATERIAL TRAVELS.
 5.2.6.1.4 IN ADDITION, A SPRINKLER SHALL BE INSTALLED
 WITHIN THE CHUTE AT ALTERNATE FLOOR LEVELS IN BUILDINGS
 OVER TWO STORIES IN HEIGHT, WITH A MANDATORY SPRINKLER
 LOCATED AT THE LOWEST SERVICE LEVEL.
 NFPA 13-6.2.8, 2010: SPRINKLERS SUBJECT TO MECHANICAL
 INJURY SHALL BE PROTECTED WITH LISTED GUARDS. PROVIDE
 CUT SHEET FOR GUARDS, PROVIDE GUARDS IN MECHANICAL
 ROOMS, ELECTRICAL ROOMS AND OTHER AREA PER CODE.
 FP -03 LEVEL 1: FIRE SPRINKLER HEADS IN GENERATOR ROOM
 INDICATE VIKING 155 DEGREE FIRE SPRINKLER TYPE HEAD;
 HEADS MAY REQUIRE HIGHER TEMPERATURE FOR ENVIRONMENT.
 LEVEL P-2: CLARIFICATION FIRE SPRINKLER PROTECTION IN
 ELEVATOR PITS?
 P-1 ADDITIONAL FIRE SPRINKLER PROTECTION SHALL BE
 REQUIRED, IF PRIVATE GARAGE INSTALL VEHICLE LIFTS.
 INSTALLATION SHALL COME IN COMPLIANCE WITH NFPA 13 AND
 13-NFPA 13-8.10.6.3, OBSTRUCTIONS THAT PREVENT
 SPRINKLER DISCHARGE FROM REACHING THE HAZARD.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-06 Cont ID  
Sent By hmoser Date 2017-10-06 Time 15:20 Rev Time 0.00
Received By hmoser Date 2017-09-27 Time 14:49 Sent To  
Notes
2017-09-28 14:49:31RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-29 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-06 Time 12:50 Sent To  
Notes
2017-06-07 12:50:18ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-06 Cont ID  
Sent By fstal Date 2017-10-04 Time 10:06 Rev Time 0.00
Received By hmoser Date 2017-10-06 Time 15:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By ccole Date 2017-06-29 Time 12:10 Rev Time 0.00
Received By ccole Date 2017-06-29 Time 12:10 Sent To  
Notes
2017-06-29 12:27:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060222
 6/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS INDICATED IN THE MAY 23RD LETTER TO ROBERT BROWN
 BUILDING OFFICIAL OF THE CITY OF WEST PALM BEACH,
 EDWARDS AND ZUCK CONSULTING ENGINEERS HAS BEEN ACQUIRED
 BY STANTEC CONSULTING SERVICES INC. AND ARE NO LONGER
 THE DESIGNERS OF RECORD. PLEASE REMOVE THE EDWARDS AND
 ZUCK TITLE BLOCK FROM THE FIRE SPRINKLER PLANS AND
 PROVIDE IN IT'S PLACE THE TITLE BLOCK OF THE NEW
 DESIGNERS OF RECORD- STANTEC CONSULTING. IN ADDITION,
 STANTEC CONSULTING SHALL PROVIDE SHOP DRAWING APPROVAL
 STAMPS ON ALL OF THE SPRINKLERMATIC PLAN SHEETS AND
 PRODUCT SUBMITTALS- SEE SECTION 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  