Plan Review Details - Permit 17060221
Plan Review Stops For Permit 17060221
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-04-23 Cont ID  
Sent By hmoser Date 2018-04-26 Time 09:11 Rev Time 0.00
Received By scaldero Date 2018-04-23 Time 11:08 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-11-15 Cont ID  
Sent By pleduc Date 2017-11-15 Time   Rev Time 0.00
Received By pleduc Date 2017-11-14 Time 13:54 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-08-10 Cont ID  
Sent By pleduc Date 2017-08-10 Time   Rev Time 0.00
Received By pleduc Date 2017-08-10 Time 13:23 Sent To M
Notes
2017-08-10 13:40:472ND REVIEW
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE ONLY CHANGES THAT I WAS ABLE TO NOTE ON THE
 RE-SUBMITTAL IS THAT THE SAPHIRE SYSTEM WORDING WAS
 REMOVED.
  
 FIRE SPRINKLER PROTECTION IS REQUIRED IN ALL THE AREAS
 INDICATED WITH ANSUL SAPPHIRE IF WATER IS AN ISSUE, A
 PREACTION SYSTEM WOULD NEED TO BE INSTALLED IN THESE
 AREAS.
  
 1) NOT COMPLIED WITH
  
 SHEET FP 201 A - THERE IS A NOTE IN THE UPS ROOM, 193
 AND IM, 109, INDICATING "ANSUL SAPPHIRE SYSTEM TO BE
 PROVIDED BY OTHERS".
  
 PER NFPA 13,
  
 8.15.10 ELECTRICAL EQUIPMENT.
 8.15.10.1 UNLESS THE REQUIREMENTS OF 8.15.10.3 ARE MET,
 SPRINKLER PROTECTION SHALL BE REQUIRED IN ELECTRICAL
 EQUIPMENT ROOMS.
 8.15.10.2 HOODS OR SHIELDS INSTALLED TO PROTECT
 IMPORTANT ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE
 SHALL BE NONCOMBUSTIBLE.
 8.15.10.3 SPRINKLERS SHALL NOT BE REQUIRED IN
 ELECTRICAL EQUIPMENT ROOMS WHERE ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY.
 (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED.
 (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED
 ENCLOSURE INCLUDING PROTECTION FOR PENETRATIONS.
 (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN
 THE ROOM.
  
  
 PLEASE PROVIDED DOCUMENTATION THAT THIS ROMM MEETS ALL
 OF REQUIRED CONDITIONS.
  
 IF NOT, PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION.
 SHOULD A WET SYSTEM NOT BE THE PREFERRED SYSTEM, A DRY
 SYSTEM WITH PREACTION THAT BACKS UP THE ANSUL SYSTEM
 MAY BE CONSIDERED.
  
  
 2) NOT COMPLIED WITH
  
 SHEET FP 202, 202 A & 202 B - THERE IS A NOTE IN THE IM
 ROOM, 233, INDICATING "ANSUL SAPPHIRE SYSTEM TO BE
 PROVIDED BY OTHERS".
  
 PER NFPA 13,
  
 8.15.10 ELECTRICAL EQUIPMENT.
 8.15.10.1 UNLESS THE REQUIREMENTS OF 8.15.10.3 ARE MET,
 SPRINKLER PROTECTION SHALL BE REQUIRED IN ELECTRICAL
 EQUIPMENT ROOMS.
 8.15.10.2 HOODS OR SHIELDS INSTALLED TO PROTECT
 IMPORTANT ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE
 SHALL BE NONCOMBUSTIBLE.
 8.15.10.3 SPRINKLERS SHALL NOT BE REQUIRED IN
 ELECTRICAL EQUIPMENT ROOMS WHERE ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY.
 (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED.
 (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED
 ENCLOSURE INCLUDING PROTECTION FOR PENETRATIONS.
 (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN
 THE ROOM.
  
  
 PLEASE PROVIDED DOCUMENTATION THAT THIS ROMM MEETS ALL
 OF REQUIRED CONDITIONS.
  
 IF NOT, PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION.
 SHOULD A WET SYSTEM NOT BE THE PREFERRED SYSTEM, A DRY
 SYSTEM WITH PREACTION THAT BACKS UP THE ANSUL SYSTEM
 MAY BE CONSIDERED.
  
  
  
 3) NOT COMPLIED WITH
  
 SHEET FP 200 - THERE IS AN INDICATION WITHIN THE CALC
 AREA B BOX OF 1589 SQ. FT.. THIS INDICATION DOES NOT
 MATCH THE SQ. FT. INDICATION ON SHEET FP 202 B OR THE
 HYDRALIC CALCULATION SUBMITTAL.
  
 PLEASE REVIEW AND CLARIFY OR CORRECT.
  
  
  
 4) NOT COMPLIED WITH
  
 SHEET FP 202 B - THERE IS AN INCORRECT FIRE CODE
 EDITION (07) REFERENCE WITH THE DESIGN AREA REDUCTION
 CALL OUT INFORMATION.
  
 PLEASE CORRECT TO THE CURRENT, 2010 EDITION, OF NFPA
 13.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-12 Cont ID  
Sent By pleduc Date 2017-06-12 Time   Rev Time 0.00
Received By pleduc Date 2017-06-12 Time 08:50 Sent To M
Notes
2017-06-12 10:48:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FP 201 A - THERE IS A NOTE IN THE UPS ROOM,
 193 AND IM, 109, INDICATING "ANSUL SAPPHIRE SYSTEM TO
 BE PROVIDED BY OTHERS".
  
 PER NFPA 13,
  
 8.15.10 ELECTRICAL EQUIPMENT.
 8.15.10.1 UNLESS THE REQUIREMENTS OF 8.15.10.3 ARE MET,
 SPRINKLER PROTECTION SHALL BE REQUIRED IN ELECTRICAL
 EQUIPMENT ROOMS.
 8.15.10.2 HOODS OR SHIELDS INSTALLED TO PROTECT
 IMPORTANT ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE
 SHALL BE NONCOMBUSTIBLE.
 8.15.10.3 SPRINKLERS SHALL NOT BE REQUIRED IN
 ELECTRICAL EQUIPMENT ROOMS WHERE ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY.
 (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED.
 (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED
 ENCLOSURE INCLUDING PROTECTION FOR PENETRATIONS.
 (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN
 THE ROOM.
  
  
 PLEASE PROVIDED DOCUMENTATION THAT THIS ROMM MEETS ALL
 OF REQUIRED CONDITIONS.
  
 IF NOT, PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION.
 SHOULD A WET SYSTEM NOT BE THE PREFERRED SYSTEM, A DRY
 SYSTEM WITH PREACTION THAT BACKS UP THE ANSUL SYSTEM
 MAY BE CONSIDERED.
  
  
 2) SHEET FP 202, 202 A & 202 B - THERE IS A NOTE IN THE
 IM ROOM, 233, INDICATING "ANSUL SAPPHIRE SYSTEM TO BE
 PROVIDED BY OTHERS".
  
 PER NFPA 13,
  
 8.15.10 ELECTRICAL EQUIPMENT.
 8.15.10.1 UNLESS THE REQUIREMENTS OF 8.15.10.3 ARE MET,
 SPRINKLER PROTECTION SHALL BE REQUIRED IN ELECTRICAL
 EQUIPMENT ROOMS.
 8.15.10.2 HOODS OR SHIELDS INSTALLED TO PROTECT
 IMPORTANT ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE
 SHALL BE NONCOMBUSTIBLE.
 8.15.10.3 SPRINKLERS SHALL NOT BE REQUIRED IN
 ELECTRICAL EQUIPMENT ROOMS WHERE ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY.
 (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED.
 (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED
 ENCLOSURE INCLUDING PROTECTION FOR PENETRATIONS.
 (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN
 THE ROOM.
  
  
 PLEASE PROVIDED DOCUMENTATION THAT THIS ROMM MEETS ALL
 OF REQUIRED CONDITIONS.
  
 IF NOT, PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION.
 SHOULD A WET SYSTEM NOT BE THE PREFERRED SYSTEM, A DRY
 SYSTEM WITH PREACTION THAT BACKS UP THE ANSUL SYSTEM
 MAY BE CONSIDERED.
  
  
  
 3) SHEET FP 200 - THERE IS AN INDICATION WITHIN THE
 CALC AREA B BOX OF 1589 SQ. FT.. THIS INDICATIONDOES
 NOT MATCH THE SQ. FT. INDICATION ON SHEET FP 202 B OR
 THE HYDRALIC CALCULATION SUBMITTAL.
  
 PLEASE REVIEW AND CLRIFY OR CORRECT.
  
  
  
 4) SHEET FP 202 B - THERE IS AN INCORRECT FIRE CODE
 EDITION (07) REFERENCE WITH THE DESIGN AREA REDUCTION
 CALL OUT INFORMATION.
  
 PLEASE CORRECT TO THE CURRENT, 2010 EDITION, OF NFPA
 13.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-04-26 Cont ID  
Sent By hmoser Date 2018-04-26 Time 09:11 Rev Time 0.00
Received By hmoser Date 2018-04-18 Time 10:46 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-15 Cont ID  
Sent By cpuell Date 2017-11-15 Time 11:43 Rev Time 0.00
Received By cpuell Date 2017-11-13 Time 16:14 Sent To  
Notes
2017-11-13 16:14:12ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-15 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-07 Time 13:27 Sent To  
Notes
2017-08-08 13:27:37RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-20 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-06 Time 13:17 Sent To  
Notes
2017-06-07 13:17:50ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2018-04-26 Cont ID  
Sent By hmoser Date 2018-04-26 Time 09:10 Rev Time 0.00
Received By hmoser Date 2018-04-26 Time 09:10 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2017-11-13 Cont ID  
Sent By lmarchan Date 2017-11-13 Time 16:13 Rev Time 0.00
Received By lmarchan Date 2017-11-13 Time 16:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-15 Cont ID  
Sent By ccole Date 2017-08-15 Time 11:06 Rev Time 0.00
Received By ccole Date 2017-08-15 Time 11:06 Sent To  
Notes
2017-08-15 11:20:402ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17060221
 8/15/17
  
 1) COMPLY WITH FIRE DEPT. REVIEW COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-20 Cont ID  
Sent By ccole Date 2017-06-20 Time 07:21 Rev Time 0.00
Received By ccole Date 2017-06-20 Time 07:16 Sent To  
Notes
2017-06-20 07:24:071ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060221
 6/20/17
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE BACK
 FLOW PREVENTER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  