Plan Review Details - Permit 17060212
Plan Review Stops For Permit 17060212
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-09-15 Cont ID  
Sent By cthroop Date 2017-09-15 Time 14:09 Rev Time 0.00
Received By cthroop Date 2017-09-15 Time 11:24 Sent To G
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By cthroop Date 2017-06-29 Time 14:03 Rev Time 0.00
Received By cthroop Date 2017-06-29 Time 13:45 Sent To  
Notes
2017-06-29 14:10:27BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
  
 2. PROVIDE SHOP DRAWINGS OF PRE-ENGINEERED STAIRS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 3. PROVIDE ICC-ES REPORT AND MANUFACTURERS INSTALLATION
 INSTRUCTION FOR THE PROPOSED INSULATION. DESIGNER TO
 SELECT PRODUCT THAT WILL ACHEIVE THE PRESCRIPTIVE R-30
 LEVEL OF INSULATION.
  
 R402.1.1 INSULATION AND FENESTRATION CRITERIA.
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF TABLE R402.1.1 BASED ON THE CLIMATE
 ZONE SPECIFIED IN CHAPTER 3.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-05-18 Cont ID  
Sent By ppetty Date 2018-05-18 Time 08:51 Rev Time 0.00
Received By ppetty Date 2018-05-18 Time 08:45 Sent To  
Notes
2018-05-18 08:51:24FOUR TIMES FEE FOR PLAN REVIEW ADDED, SEE BELOW.
 CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 PLEASE READ COMMENTS IN THEIR ENTIRETY AND RESPOND TO
 ALL ITEMS.
  
 1 CORRECTED
 2. CORRECTED
 3. CORRECTED
 4. CORRECTED
 5. CORRECTED
 6 CORRECTED
 7. CORRECTED.
  
 SINCERELY,
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-11-03 Cont ID  
Sent By jpearson Date 2017-11-03 Time 15:40 Rev Time 0.00
Received By jpearson Date 2017-11-03 Time 15:40 Sent To  
Notes
2017-11-03 15:36:36FOUR TIMES FEE FOR PLAN REVIEW ADDED, SEE BELOW.
 CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 PLEASE READ COMMENTS IN THEIR ENTIRETY AND RESPOND TO
 ALL ITEMS. THERE ARE A TOTAL OF 7 COMMENTS. THE
 RESPONSE LETTER PROVIDED STATED THE PREVIOUS COMMENTS
 WERE ADDRESSED, BUT THE FOLLOWING ITEMS REMAIN
 INCORRECT.
  
 1. PREVIOUS COMMENT # 10. PROVIDE CARBON MONOXIDE
 ALARMS AS REQUIRED PER CODE. FBC RE315.1 CO ALARMS ARE
 REQUIRED WITHING 10 FEET OF EACH SLEEPING AREA. SEE
 REFERENCED CODE AND PROVIDE CORRECTION. FBC R315.1
 2. PREVIOUS COMMENT # 11. SHOW GFCI PROTECTED OUTLET
 FOR GARAGE DOOR OPENER. NEC 210.8; FBC RE3902.2
 3. PREVIOUS COMMENT # 12. 400 AMP SERVICE IS SHOWN WITH
 3/0 WIRE FEEDING THE SERVICE. 3/0 WIRE IS NOT RATED FOR
 A 400 AMP SERVICE. PROVIDE CORRECTION. NEC
 310.15(B)(7),(16), FBC RE3603
  
 NEW COMMENTS BASED ON SUBMITTED PLANS:
  
 4. SHEET E-1 REFERENCED ON COVER SHEET IS NOT INCLUDED
 IN PLANS. PROVIDE FULL SET OF PLANS FOR REVIEW. FBC
 107.2.1, 107.3.5
 5. PROVIDE AFCI PROTECTION AS NOTED: ALL 120-VOLT,
 SINGLE PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS
 SUPPLYING OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION. NEC 210.12; FBC RE3902.12
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-09-07 Cont ID  
Sent By jpearson Date 2017-09-07 Time 13:15 Rev Time 0.00
Received By jpearson Date 2017-09-07 Time 13:15 Sent To  
Notes
2017-09-07 13:15:46CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 PREVIOUS COMMENTS NOT ADDRESSED SATISFACTORILY:
  
 "9. AHU-1 SHOWS A 60 AMP FEED. THE PANEL SCHEDULE
 STATES THIS IS A 17.5KW HEAT LOAD, WHICH EQUALS 72.92
 AMPS JUST FOR THE HEAT. PROVIDE CORRECT WIRE AND
 BREAKER SIZING. NEC 240.4, 310.15(B)(16), 440.34; FBC
 RE3702.11" THE DATA PROVIDED ON SHEET M-2 STATES THAT
 AHU-1 WILL HAVE 10KW HEAT AND AHU-2 WILL HAVE 8KW HEAT.
 CORRECT DISCREPANCY AND PROVIDE CORRECT WIRE AND
 BREAKER SIZES FOR THESE UNITS. NEC 240.4,
 310.15(B)(16), 440.34; FBC RE3702.11
 "10. PROVIDE CARBON MONOXIDE ALARMS AS REQUIRED PER
 CODE. FBC RE315.1" CO ALARMS ARE REQUIRED WITHING 10
 FEET OF EACH SLEEPING AREA. SEE REFERENCED CODE AND
 PROVIDE CORRECTION. FBC R315.1
 "11. WILL THERE BE A GARAGE DOOR OPENER, WHICH NEEDS AN
 OUTLET? CLARIFY AND/OR CORRECT. FBC 107.2.1" GARAGE
 DOOR OPENER IS NOW SHOWN, BUT THERE IS NOT A GFCI
 PROTECTED OUTLET FOR THE UNIT. PROVIDE CORRECTION. NEC
 210.8; FBC RE3902.2
 "12. PROVIDE DETAIL ON HOW THE FEED FROM TWO 200 AMP
 PANELS WILL BE TIED INTO ONE 200 AMP SERVICE. FBC
 107.2.1; NEC 110.3" 400 AMP SERVICE IS SHOWN WITH 3/0
 WIRE FEEDING THE SERVICE. 3/0 WIRE IS NOT RATED FOR A
 400 AMP SERVICE. PROVIDE CORRECTION. NEC
 310.15(B)(7),(16), FBC RE3603
  
 NEW COMMENTS BASED ON SUBMITTED PLANS:
  
 1. SHEET E-1 REFERENCED ON COVER SHEET IS NOT INCLUDED
 IN PLANS. PROVIDE FULL SET OF PLANS FOR REVIEW. FBC
 107.2.1, 107.3.5
 2. PROVIDE AFCI PROTECTION AS NOTED: ALL 120-VOLT,
 SINGLE PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS
 SUPPLYING OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION. NEC 210.12; FBC RE3902.12
 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-22 Cont ID  
Sent By jpearson Date 2017-06-22 Time 07:16 Rev Time 0.00
Received By jpearson Date 2017-06-22 Time 07:16 Sent To  
Notes
2017-06-22 08:09:47CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ACCURATE LOAD CALCULATION WITH ALL LOADS
 INCLUDED. CURRENTLY, A/C-2 OR AHU-2 IS NOT INCLUDED.
 NEC 220; FBC RE3602.2
 2. PROVIDE GFCI PROTECTED OUTLET ON 2ND FLOOR BALCONY.
 NEC 210.52(E)(3); FBC RE3901.7
 3. PROVIDE NOTE FOR LIGHTS LOCATED IN TUB/SHOWER AREAS
 TO BE "SUITABLE FOR DAMP LOCATIONS". NEC 410.10(A); FBC
 RE4003.11
 4. PROVIDE CORRECTION FOR BATHROOM GFCI OUTLETS. BATH 1
 AND 2 HAVE RECEPTACLES AND LIGHTING ON THE SAME
 CIRCUIT. CODE STATES: "A MINIMUM OF ONE 20 AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS". NEC 210.11(C)(3); FBC RE3703.4
 5. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12
 6. PLAN APPEARS TO SHOW AN OUTLET IN THE SHOWER AREA OF
 BATH 1. PROVIDE CORRECTION AND/OR CLARIFICATION. FBC
 107.2.1; NEC 406.9(C); FBC RE4002.11
 7. PANEL A, CIRCUIT 17 IS LABELED AS A 15 AMP CIRCUIT.
 CODE REQUIRES A 20 AMP CIRCUIT. LIGHTING NOT PERMITTED
 ON SAME CIRCUIT. PROVIDE CORRECTION. NEC 210.11(C),
 210.52(B); FBC RE3901.3
 8. AHU-2 SHOWS A CIRCUIT THAT IS #6 WIRE ON A 60 AMP
 BREAKER. #6 ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL
 WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE CORRECTION.
 NEC 334.80; FBC RE3705.4.4
 9. AHU-1 SHOWS A 60 AMP FEED. THE PANEL SCHEDULE STATES
 THIS IS A 17.5KW HEAT LOAD, WHICH EQUALS 72.92 AMPS
 JUST FOR THE HEAT. PROVIDE CORRECT WIRE AND BREAKER
 SIZING. NEC 240.4, 310.15(B)(16), 440.34; FBC RE3702.11
 10. PROVIDE CARBON MONOXIDE ALARMS AS REQUIRED PER
 CODE. FBC R315.1
 11. WILL THERE BE A GARAGE DOOR OPENER, WHICH NEEDS AN
 OUTLET? CLARIFY AND/OR CORRECT. FBC 107.2.1
 12. PROVIDE DETAIL ON HOW THE FEED FROM TWO 200 AMP
 PANELS WILL BE TIED INTO ONE 200 AMP SERVICE. FBC
 107.2.1; NEC 110.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-05-22 Cont ID  
Sent By gjohnson Date 2018-05-22 Time 16:11 Rev Time 0.00
Received By gjohnson Date 2018-05-22 Time 16:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-10-30 Cont ID  
Sent By gjohnson Date 2017-10-30 Time 13:25 Rev Time 0.00
Received By gjohnson Date 2017-10-30 Time 13:25 Sent To  
Notes
2017-10-30 13:28:511ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. ONE PLAN SET DID NOT HAVE THE CORRECTED PLUMBING
 PAGES PLEASE PROVIDE TWO COMPLETE SET OF PLANS. PER WPB
 AMEND TO FBC 107.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-09-19 Cont ID  
Sent By gjohnson Date 2017-09-19 Time 11:22 Rev Time 0.00
Received By gjohnson Date 2017-09-19 Time 11:22 Sent To  
Notes
2017-09-19 12:02:491ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-3 STATES FBC FG TABLE 402.4(2) WAS USED FOR
 SIZING THE SYSTEM THAT TABLE IS FOR A .5 LB SYSTEM
 UNDER THE GAS SYSTEM INFO IT CALLS OUT A 2LB SYSTEM
 PLEASE CLARIFY IF IT IS A .5LB OR 2LB SYSTEM. PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHT P-2 NOTES A TANKLESS PROPANE WATER HEATER PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT P-1 DETAIL SHOWS A TANK TYPE HEATER SHT P-2+3
 SHOWS A TANKLESS WATER HEATER PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 4. THE MANUAL FOR GAS RANGE DOES NOT LIST BTU LOAD OR
 THE STANDARDS THAT IT MEETS SHALL MEET ANSI Z21.1, ANSI
 Z21.58 OR ANSI Z83.11 PER FBC FG 623.1
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304. FOR FIRE PLACES AND
 RANGE
  
 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS SERVING FIRE PLACES PER
 FBC-2014 FUEL GAS CODE SEC. 502 THRU 505.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-06-20 Cont ID  
Sent By gjohnson Date 2017-06-20 Time 11:08 Rev Time 0.00
Received By gjohnson Date 2017-06-20 Time 11:08 Sent To  
Notes
2017-06-20 11:26:451ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. TYPE OF GAS, (LP OR NATURAL). THE PLAN SHOWS BOTH
 PROPANE AND NATURAL PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 3.SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402. THERE ARE CONFLICTING MEASUREMENTS PLEASE
 CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 4.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 5. IS THIS A 5LB SYSTEM RESIDENTIAL SYSTEMS ARE
 TYPICALLY 2LB OR .05LB PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 6. YOU HAVE NOTED ON THE RISER DIAGRAM THE USE OF ANSUL
 VALVES ON EVERY APPLIANCE PLEASE PROVIDE MANUFACTURE
 SPEC FOR THESE VALVES WE DO NOT TYPICALLY SEE THESE ON
 RESIDENTIAL SYSTEMS IS THIS A FIRE SUPPRESSION SYSTEM
 VALVE PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2017-06-19 Cont ID  
Sent By fmittner Date 2017-06-19 Time 13:36 Rev Time 0.00
Received By fmittner Date 2017-06-19 Time 13:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2018-06-07 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-29 Time 16:17 Sent To  
Notes
2018-05-30 16:17:45RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-05-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-04 Time 14:15 Sent To  
Notes
2018-05-07 14:15:49R25

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-11-22 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-12 Time 15:16 Sent To  
Notes
2017-10-13 15:18:00R04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-13 Cont ID  
Sent By lmarchan Date 2017-10-13 Time 15:07 Rev Time 0.00
Received By lmarchan Date 2017-08-16 Time 15:09 Sent To  
Notes
2017-08-17 15:10:01R28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-29 Cont ID  
Sent By cthroop Date 2017-06-29 Time 14:01 Rev Time 0.00
Received By cthroop Date 2017-06-06 Time 14:02 Sent To  
Notes
2017-06-07 14:04:14R29

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2018-06-07 Cont ID  
Sent By ccole Date 2018-06-07 Time 09:28 Rev Time 0.00
Received By ccole Date 2018-06-07 Time 07:22 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-05-23 Cont ID  
Sent By ccole Date 2018-05-23 Time 08:15 Rev Time 0.00
Received By ccole Date 2018-05-22 Time 17:44 Sent To I
Notes
2018-05-23 08:40:464TH REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17060212
 5/22/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE FOLLOWING REVIEW IS BASED ON THE NEW MECHANICAL
 PLANS AND SPECIFICATIONS SUBMITTED. THE VOIDED PLANS
 WERE NOT RETURNED WITH THE NEW PLAN SHEETS.
  
 1) SHEET M-2: THE RETURN TRANSFER DUCTS FROM THE
 BEDROOMS ARE UNDERSIZED PER SECTION M1602.4 ITEMS 1 & 2
 FBC-14 RESIDENTIAL. BECASUE ALL BEDROOMS ARE MASTER
 SUITES CONTAINING BATHS AND CLOSET, AND EACH IS BEING
 SUPPLIED BY A 16" X 10" DUCT, THEN EACH WILL REQUIRE A
 TRANSFER DUCT WITH A MINIMUM CROSS SECTION AREA OF 240
 SQ. INCHES,
  
 2) THE SUBMITTAL FOR THE EXHAUST HOOD INDICATES A
 MAXIMUM EXHAUST RATE OF 900 CFMS WHICH WILL REQUIRE
 MAKEUP AIR TO BE PROVIDED PER SECTION M1503.4. THE
 MAKEUP AIR SYSTEM SHALL BE EQUIPPED WITH A MEANS OF
 CLOSURE, AND SHALL BE AUTOMATICALLY CONTROLLED TO START
 AND OPERATE SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  
 3) THE AHRI CERTIFICATES DO NOT MATCH WITH THE NEW 4
 AND 2.5-TON AC SYSTEMS SELECTED AND SHOWN IN THE
 SCHEDULES ON M-2.
  
 4) THE RESCHECK ENERGY EFFICIENCY CERTIFICATE DOES NOT
 PROVIDE ANY COMPLIANCE DATA FOR THE AC SYSTEMS OR THE
 WATER HEATER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-11-22 Cont ID  
Sent By ccole Date 2017-11-22 Time 10:33 Rev Time 0.00
Received By ccole Date 2017-11-22 Time 10:33 Sent To  
Notes
2017-11-22 10:48:553RD REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17060212
 11/22/17
  
 PLAN REVIEW RESULTS: DENIED
  
 COMMENTS 4, 5, & 6 FROM THE PREVIOUS (2ND) REVIEW HAVE
 NOT BEEN ADDRESSED COMPLETELY. THOSE COMMENTS ARE
 PRINTED BELOW
  
 1) AS PREVIOUSLY REQUESTED IN THE FIRST REVIEW,
 INDICATE HOW COMBUSTION AIR IS BEING PROVIDED FOR THE
 GAS FIREPLACE (COMMENT #4). THE SUBMITTED INSTALLATION
 GUIDELINES ARE INDICATING THE UNIT IS " DESIGNED TO
 OPERATE WITH ALL COMBUSTION AIR BEING SIPHONED FROM THE
 OUTSIDE OF THE BUILDING" (PAGE 5). PLEASE PROVIDE
 DETAILS ON THE PLAN INDICATING COMPLIANCE.
  
 2) AS PREVIOUSLY REQUESTED PROVIDE A VENTING PLAN FOR
 THE FIREPLACE (COMMENT #5). PLEASE SEE PAGE 14 WHICH
 SHOWS A LIST OF ACCEPTABLE VENT SYSTEMS AND SUBMIT THE
 SPECIFICATIONS AND INSTALLATION GUIDELINES.
  
 3) REFER TO SECTION 1503.4 FBC-14 RESIDENTIAL AND
 PROVIDE A MAKEUP AIR SYSTEM FOR THE NEW AIRFLOW RANGE
 HOOD.
  
  
 2ND REVIEW FBC-2014 RESIDENTIAL MECHANICAL
  
 4) THE PLUMBING PLANS ARE INDICATING A GAS FIREPLACE IN
 THE MASTER BEDROOM AND A NEW GAS RANGE IN THE KITCHEN.
 PLEASE SUBMIT PRODUCT DATA SHEETS FOR BOTH APPLIANCES-
 SECTIONS G2434 & G2435. PLEASE NOTE COMBUSTION AIR
 SHALL BE REQUIRED IN ACCORDANCE WITH MANUFACTURER'S
 SPECIFICATIONS AND THE SECTION 304 FBC-14 FUEL GAS.
  
 5) PROVIDE A VENTING PLAN FOR THE GAS FIREPLACE WHICH
 SHOWS THE TYPE AND SIZE OF VENT FLUE, THE VENT FLUE
 RUN, AND THE TERMINATION LOCATION- SECTION G2427.
 SUBMIT SPECS FOR THE VENT FLUE.
  
 6) REFER TIO SECTION M1503 AND CLARIFY IF A NEW RANGE
 HOOD WILL BE INSTALLED OVER THE NEW GAS RANGE, AND
 PROVIDE EXHAUST VENTILATION DETAILS AND PRODUCT SPEC
 SHEETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-09-15 Cont ID  
Sent By ccole Date 2017-09-15 Time 08:41 Rev Time 0.00
Received By ccole Date 2017-09-15 Time 08:11 Sent To  
Notes
2017-09-15 09:00:091ST REVIEW FBC-2014 RESDIENTIAL MECHANICAL
 PERMIT #17060212
 9/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-2: THE 12" TRANSFER DUCT FROM THE MASTER BEDROOM
 IS UNDERSIZED. REFER TO SECTION M1602.4 EXCEPTIONS 1 &
 3, FBC-14 RESIDENTIAL: THE PLAN SHOWS A 10"X16" DUCT
 ENTERING THE MASTER SUITE WHICH, PER THE CODE SECTIONS,
 REQUIRES A TRANSFER DUCT TO SIZED AT 1-1/2 TIMES THE
 CROSS SECTIONAL AREA OF THE 10"X16" DUCT. THE MINIMUM
 TRANSFER DUCT SIZE THEREFORE MUST BE 16".
  
 2) M-2: AS PREVIOUSLY REQUESTED, SHOW THE CONDENSATE
 PIPING RUNS AND DISCHARGE LOCATIONS. SUBMIT SPECS FOR
 THE CONDENSATE PUMPS (IF APPLICABLE)- SECTION M1411.3
  
 3) M-2: AS PREVIOUSLY REQUESTED, PROVIDE INSTALLATION
 DETAILS FOR THE EXTERIOR CONDENSERS- SEE SECTIONS
 M1305.1.4.1 AND M1401.4 .
  
 4) THE PLUMBING PLANS ARE INDICATING A GAS FIREPLACE IN
 THE MASTER BEDROOM AND A NEW GAS RANGE IN THE KITCHEN.
 PLEASE SUBMIT PRODUCT DATA SHEETS FOR BOTH APPLIANCES-
 SECTIONS G2434 & G2435. PLEASE N0OTE COMBUSTION AIR
 SHALL BE REQUIRED IN ACCORDANCE WITH MANUFACTURER'S
 SPECIFICATIONS AND THE SECTION 304 FBC-14 FUEL GAS.
  
 5) PROVIDE A VENTING PLAN FOR THE GAS FIREPLACE WHICH
 SHOWS THE TYPE AND SIZE OF VENT FLUE, THE VENT FLUE
 RUN, AND THE TERMINATION LOCATION- SECTION G2427.
 SUBMIT SPECS FOR THE VENT FLUE.
  
 6) REFER TIO SECTION M1503 AND CLARIFY IF A NEW RANGE
 HOOD WILL BE INSTALLED OVER THE NEW GAS RANGE, AND
 PROVIDE EXHAUST VENTILATION DETAILS AND PRODUCT SPEC
 SHEETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By ccole Date 2017-06-29 Time 10:11 Rev Time 0.00
Received By ccole Date 2017-06-29 Time 10:11 Sent To  
Notes
2017-06-29 10:18:551ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL , ENERGY
 CONSERVATION CODES
 PERMIT #17060212
 6/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO R101.4.5 ENERGY CONSERVATION: THE
 PREVIOUSLY UNCONDITIONED RESIDENCE THAT IS NOW BECOMING
 CONDITIONED SPACE SHALL BE BROUGHT INTO FULL COMPLIANCE
 WITH THE CODE. PLEASE SEE SECTION R101.5.1 AND SUBMIT
 AN ENERGY COMPLIANCE FORM.
  
 2) SHEET M-2: THE AC CALC PASTED ON THE PLAN SHEET ARE
 NOT CONSISTENT WITH THE AC SYSTEMS SPECIFIED ON THE
 PLANS. THE CALCULATION WHICH IS TITLED "SYSTEM #1" ARE
 INDICATING A COOLING LOAD OF APPROXIMATELY 25,000 BTUH,
 HOWEVER THE PLANS ARE INDICATING SYSTEM 1 AT 60,000
 BTUH AND SYSTEM 2 AT 42,000 BTUH- SEE SECTION R403.6.1
 FBC-14 ENERGY CONSERVATION AND PROVIDE COMPLETE AC
 CALCULATIONS INCLUDING THE MANUAL J WORKSHEETS.
  
 3) M-2: THE1ST FLOOR MAIN RETURN GRILL SHALL NOT BE
 LOCATED IN THE KITCHEN- SECTION M1602 ITEM #4 FBC-14
 RESDIENTIAL. PLEASE RELOCATE THE GRILL AND PROVIDE IT'S
 DIMENSIONS.
  
 4) M-2: AHU-1 LOCATED IN THE GARAGE SHALL BE PROTECTED
 FROM VEHICAL IMPACT- SECTION M1307.3.1 FBC-14
 RESIDENTIAL.
  
 5) M-2: PROVIDE THE DIMENSIONS OF THE SECOND FLOOR MAIN
 RETURN GRILL IN THE HALLWAY,
  
 6) M-2: PROVIDE THE SIZE OF THE TRANSFER DUCT AT THE
 18X10 RETURN FRILL IN THE SECOND FLOOR MASTER BEDROOM.
 PLEASE SEE SECTION M1602.4 EXCEPTIONS 1, 2, & 3 TO SIZE
 THE RETURN COMPONENTS IN COMPLIANCE WITH THE CODE.
  
 7) M-2: SHOW THE CONDENSATE PIPING RUNS AND DISCHARGE
 LOCATIONS. SUBMIT SPECS FOR THE CONDENSATE PUMPS (IF
 APPLICABLE).
  
 8) M-2: THE DRYER EXHAUST DUCT SHALL HAVE A SMOOTH
 INTERIOR FINISH AND BE MINIMUM 28 GAUGE- SECTION
 M1502.4.1. FLEX DUCTS ARE NOT PERMITTED.
  
 9) M-2: PROVIDE INSTALLATION DETAILS FOR THE EXTERIOR
 CONDENSERS- SEE SECTIONS M1305.1.4.1 AND M1401.4 .
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-05-22 Cont ID  
Sent By gjohnson Date 2018-05-22 Time 16:10 Rev Time 0.00
Received By gjohnson Date 2018-05-22 Time 16:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-10-30 Cont ID  
Sent By gjohnson Date 2017-10-30 Time 13:29 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
2017-10-30 13:29:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. ONE PLAN SET DID NOT HAVE THE CORRECTED PLUMBING
 PAGES PLEASE PROVIDE TWO COMPLETE SET OF PLANS. PER WPB
 AMEND TO FBC 107.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-06-20 Cont ID  
Sent By gjohnson Date 2017-06-20 Time 10:50 Rev Time 0.00
Received By gjohnson Date 2017-06-20 Time 09:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-09-15 Cont ID  
Sent By cthroop Date 2017-09-15 Time 14:09 Rev Time 0.00
Received By cthroop Date 2017-09-15 Time 11:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By cthroop Date 2017-06-29 Time 14:01 Rev Time 0.00
Received By cthroop Date 2017-06-29 Time 14:01 Sent To  
Notes
2017-06-29 14:02:55BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM
 COMPONENTS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.