| 2017-08-05 08:23:51 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17060195 |
| | W. P. B. PERMIT: 17021052 |
| | ADD: 5444 N HAVERHILL RD. FUEL TANK AT STADIUM |
| | MAINTENANCE SHOP |
| | CONT: CYPRESS CONSTRUCTION GROUP |
| | TEL: 954-533-1199 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: FRI. / SAT. AUGUST 5/ 2017 |
| | ACTION: DENIED |
| | |
| | 1A) ON THE ORIGINAL PERMIT NUMBER 17021052 THERE WAS NO |
| | BUILDING REVIEW. ON THE ORIGINAL PLANS FOR THIS |
| | STRUCTURES THEY WERE A ROOFED OVER OPEN STRUCTURE UNDER |
| | THE PRIME PERMIT 16020418 SEE SHEET 0602-62.612. UNDER |
| | THE PERMIT 17021052 THE PLANS SHOW WHAT CANNOT BE |
| | DEFINED, SINCE THE REMAINDER OF THE BUILDING IS NOT |
| | INCLUDED. THE AREA SHOWN WITH THE (2) 500 GALLON TANKS |
| | CANNOT BE DETERMINED IF THIS IN THE LAST BAY OF THE |
| | BUILDING OR THE OPEN WALLED IN AREA NEXT TO THE |
| | BUILDING? |
| | |
| | 1B) THE PLANS SHOWS THE FRONT ENCLOSED AND DOORS OR |
| | GATES INSTALLED. THIS IS BEYOND THE SCOPE OF A PCC |
| | LICENSE; A CGC CAN ENCLOSE THE STRUCTURE. FLORIDA |
| | STATUTE 489.105(A). |
| | |
| | 2) PLANS ARE SILENT AS TO THE BUILDING CLASSIFICATION |
| | AND IF FIRE SPRINKLERED OR NOT AND OCCUPANCY TYPE. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLE 503). |
| | FIRE SPRINKLERED OR NOT? |
| | FIRE RATING OF WALLS AND DOORS |
| | |
| | 3) FUEL TANK WIND LOAD CALCULATIONS WERE SUBMITTED |
| | PLEASE PROVIDE ADDITIONAL INFORMATION EVEN IN THIS |
| | REVISION SHEET 0927-1 P$-003 SHOWS (2) 500 GALLON TANKS |
| | WITHIN THE BUILDING? 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 4) THE SUBMITTED WIND CALCULATIONS SHEET 3 OF 9 SHOWS |
| | WHAT APPEARS TO BE A COPY OF A SCANNED PAPER |
| | SIGNED AND SEALED DOCUMENT. FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY |
| | CREATED OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE |
| | SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED |
| | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. |
| | |
| | 5) PLEASE SUBMIT MSDS SHEETS FOR BOTH THE GASOLINE AND |
| | DIESEL FUELS TO CONFIRM THE CLASS OF COMBUSTIBILITY, |
| | AND REQUIREMENTS. FOR THIS REVIEW WE WILL USE THE |
| | FOLLOWING ASSUMPTIONS; |
| | GASOLINE FUEL TO BE A CLASS 1A FLAMMABLE LIQUID, ALL |
| | GRADES OF FUEL. |
| | DIESEL FUEL TO BE A CLASS 3 FLAMMABLE LIQUID. (USING |
| | DIESEL GRADE # 2). |
| | PLEASE SHOW COMPLIANCE WITH: 2014 FBC-B 414.1.3 |
| | INFORMATION REQUIRED. A REPORT SHALL BE SUBMITTED TO |
| | THE BUILDING OFFICIAL IDENTIFYING THE MAXIMUM EXPECTED |
| | QUANTITIES OF HAZARDOUS MATERIALS TO BE STORED, USED IN |
| | A CLOSED SYSTEM AND USED IN AN OPEN SYSTEM, AND |
| | SUBDIVIDED TO SEPARATELY ADDRESS HAZARDOUS MATERIAL |
| | CLASSIFICATION CATEGORIES BASED ON TABLES 307.1(1) AND |
| | 307.1(2). THE METHODS OF PROTECTION FROM SUCH HAZARDS, |
| | INCLUDING BUT NOT LIMITED TO CONTROL AREAS, FIRE |
| | PROTECTION SYSTEMS AND GROUP H OCCUPANCIES SHALL BE |
| | INDICATED IN THE REPORT AND ON THE CONSTRUCTION |
| | DOCUMENTS. THE OPINION AND REPORT SHALL BE PREPARED BY |
| | A QUALIFIED PERSON, FIRM OR CORPORATION APPROVED BY THE |
| | BUILDING OFFICIAL AND PROVIDED WITHOUT CHARGE TO THE |
| | ENFORCING AGENCY. |
| | |
| | FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP |
| | H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING |
| | THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO |
| | AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF |
| | EVERY BUILDING AND STRUCTURE. |
| | |
| | 6) DEPENDING ON THE AMOUNT OF FLAMMABLE LIQUIDS BEING |
| | STORED, IF INDOORS OR OUTSIDE SHOW COMPLIANCE WITH; |
| | 2014 FBC 414.2 CONTROL AREAS. |
| | CONTROL AREAS SHALL COMPLY WITH SECTIONS 414.2.1 |
| | THROUGH 414.2.5 AND THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | [F] 414.2.1 CONSTRUCTION REQUIREMENTS. CONTROL AREAS |
| | SHALL BE SEPARATED FROM EACH OTHER BY FIRE BARRIERS |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR |
| | HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 711, OR BOTH. |
| | |
| | [F] 414.2.2 PERCENTAGE OF MAXIMUM ALLOWABLE QUANTITIES. |
| | THE PERCENTAGE OF MAXIMUM ALLOWABLE QUANTITIES OF |
| | HAZARDOUS MATERIALS PER CONTROL AREA PERMITTED AT EACH |
| | FLOOR LEVEL WITHIN A BUILDING SHALL BE IN ACCORDANCE |
| | WITH TABLE 414.2.2. |
| | |
| | 7) SHEET 0927-1 P4-003 SHOWS WHAT APPEARS TO BE A |
| | DOUBLE WALL TANK AND LEAK DETECTOR PLEASE PROVIDE THE |
| | MANUFACTURERS CUT SHEETS FOR THIS TANK SYSTEM IN |
| | ACCORDANCE WITH FBC-B 414.5.4. |
| | |
| | 8) DEPICTED ON SHEET 0927-1 P4-003 IT APPEARS THE PUMP |
| | AND DISPENSER WITH HOSE IS ON TOP OF THE 500 GALLON |
| | TANK. BOTH TANKS ARE WELL WITHIN THE STRUCTURE, PLEASE |
| | PROVIDE HOW COMPLIANCE WITH DISPENSING OF FUEL WILL |
| | OCCUR AND IN COMPLIANCE WITH FBC-B 414.7.2 414.7.2 |
| | DISPENSING, USE AND HANDLING. WHERE IS THE EMERGENCY |
| | SHUT OFF LOCATED? |
| | |
| | 9) DEPICTED ON SHEET 0927-1 P4-003 IS NOTE # 3, |
| | PETROVEND FUEL SYSTEM CONTROL PANEL AND CARD READER |
| | PLEASE PROVIDE COMPLIANCE WITH 414.7.3 SUPERVISION AND |
| | MONITORING. |
| | |
| | 10A) IF THE DISPENSING SYSTEMS ARE INSIDE THEY WILL |
| | NEED TO COMPLY WITH 414.5 INSIDE STORAGE, DISPENSING |
| | AND USE. THE INSIDE STORAGE, DISPENSING AND USE OF |
| | HAZARDOUS MATERIALS SHALL BE IN ACCORDANCE WITH |
| | SECTIONS 414.5.1 THROUGH 414.5.4 OF THIS CODE AND THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 10B) IF THE DISPENSING SYSTEMS ARE OUTSIDE THEY WILL |
| | NEED TO COMPLY WITH 414.6 OUTDOOR STORAGE, DISPENSING |
| | AND USE. THE OUTDOOR STORAGE, DISPENSING AND USE OF |
| | HAZARDOUS MATERIALS SHALL BE IN ACCORDANCE WITH THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |