Plan Review Details - Permit 17060195
Plan Review Stops For Permit 17060195
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-08-22 Cont ID  
Sent By shill Date 2018-08-22 Time 11:45 Rev Time 0.00
Received By shill Date 2018-08-22 Time 11:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-21 Cont ID  
Sent By shill Date 2018-07-21 Time 09:48 Rev Time 0.00
Received By shill Date 2018-07-21 Time 09:48 Sent To  
Notes
2018-07-21 09:48:48PROVISO:
  
 4) 4TH REQUEST. THE SUBMITTED WIND CALCULATIONS SHEET 3
 OF 9 SHOWS WHAT APPEARS TO BE A COPY OF A SCANNED PAPER
 SIGNED AND SEALED DOCUMENT. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEE'S SIGNATURE
 SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 SEE SIGNATURE REVIEW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-05-24 Cont ID  
Sent By shill Date 2018-05-24 Time 11:07 Rev Time 0.00
Received By shill Date 2018-05-24 Time 11:07 Sent To  
Notes
2018-05-24 11:08:182014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17060195
 W. P. B. PERMIT: 17021052
 ADD: 5444 N HAVERHILL RD. FUEL TANK AT STADIUM
 MAINTENANCE SHOP
 CONT: CYPRESS CONSTRUCTION GROUP
 TEL: 954-533-1199
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: THURS. MARCH 22/ 2018
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) 3RD REQUEST. THE SUBMITTED WIND CALCULATIONS SHEET 3
 OF 9 SHOWS WHAT APPEARS TO BE A COPY OF A SCANNED PAPER
 SIGNED AND SEALED DOCUMENT. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEE'S SIGNATURE
 SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 TITLE BLOCK IN COMPLIANCE WITH FAC61G15-23.002 IS ALSO
 REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-22 Cont ID  
Sent By jwitmer Date 2018-03-22 Time 14:07 Rev Time 0.00
Received By jwitmer Date 2018-03-22 Time 13:23 Sent To  
Notes
2018-03-22 14:06:592014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17060195
 W. P. B. PERMIT: 17021052
 ADD: 5444 N HAVERHILL RD. FUEL TANK AT STADIUM
 MAINTENANCE SHOP
 CONT: CYPRESS CONSTRUCTION GROUP
 TEL: 954-533-1199
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. MARCH 22/ 2018
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) 2ND REQUEST. THE SUBMITTED WIND CALCULATIONS SHEET 3
 OF 9 SHOWS WHAT APPEARS TO BE A COPY OF A SCANNED PAPER
 SIGNED AND SEALED DOCUMENT. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEE'S SIGNATURE
 SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
 5-10) COMPLIED.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2017-08-05 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2017-08-04 Time 09:12 Sent To  
Notes
2017-08-05 08:23:512014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17060195
 W. P. B. PERMIT: 17021052
 ADD: 5444 N HAVERHILL RD. FUEL TANK AT STADIUM
 MAINTENANCE SHOP
 CONT: CYPRESS CONSTRUCTION GROUP
 TEL: 954-533-1199
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: FRI. / SAT. AUGUST 5/ 2017
 ACTION: DENIED
  
 1A) ON THE ORIGINAL PERMIT NUMBER 17021052 THERE WAS NO
 BUILDING REVIEW. ON THE ORIGINAL PLANS FOR THIS
 STRUCTURES THEY WERE A ROOFED OVER OPEN STRUCTURE UNDER
 THE PRIME PERMIT 16020418 SEE SHEET 0602-62.612. UNDER
 THE PERMIT 17021052 THE PLANS SHOW WHAT CANNOT BE
 DEFINED, SINCE THE REMAINDER OF THE BUILDING IS NOT
 INCLUDED. THE AREA SHOWN WITH THE (2) 500 GALLON TANKS
 CANNOT BE DETERMINED IF THIS IN THE LAST BAY OF THE
 BUILDING OR THE OPEN WALLED IN AREA NEXT TO THE
 BUILDING?
  
 1B) THE PLANS SHOWS THE FRONT ENCLOSED AND DOORS OR
 GATES INSTALLED. THIS IS BEYOND THE SCOPE OF A PCC
 LICENSE; A CGC CAN ENCLOSE THE STRUCTURE. FLORIDA
 STATUTE 489.105(A).
  
 2) PLANS ARE SILENT AS TO THE BUILDING CLASSIFICATION
 AND IF FIRE SPRINKLERED OR NOT AND OCCUPANCY TYPE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 FIRE SPRINKLERED OR NOT?
 FIRE RATING OF WALLS AND DOORS
  
 3) FUEL TANK WIND LOAD CALCULATIONS WERE SUBMITTED
 PLEASE PROVIDE ADDITIONAL INFORMATION EVEN IN THIS
 REVISION SHEET 0927-1 P$-003 SHOWS (2) 500 GALLON TANKS
 WITHIN THE BUILDING? 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 4) THE SUBMITTED WIND CALCULATIONS SHEET 3 OF 9 SHOWS
 WHAT APPEARS TO BE A COPY OF A SCANNED PAPER
 SIGNED AND SEALED DOCUMENT. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE
 SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 5) PLEASE SUBMIT MSDS SHEETS FOR BOTH THE GASOLINE AND
 DIESEL FUELS TO CONFIRM THE CLASS OF COMBUSTIBILITY,
 AND REQUIREMENTS. FOR THIS REVIEW WE WILL USE THE
 FOLLOWING ASSUMPTIONS;
 GASOLINE FUEL TO BE A CLASS 1A FLAMMABLE LIQUID, ALL
 GRADES OF FUEL.
 DIESEL FUEL TO BE A CLASS 3 FLAMMABLE LIQUID. (USING
 DIESEL GRADE # 2).
 PLEASE SHOW COMPLIANCE WITH: 2014 FBC-B 414.1.3
 INFORMATION REQUIRED. A REPORT SHALL BE SUBMITTED TO
 THE BUILDING OFFICIAL IDENTIFYING THE MAXIMUM EXPECTED
 QUANTITIES OF HAZARDOUS MATERIALS TO BE STORED, USED IN
 A CLOSED SYSTEM AND USED IN AN OPEN SYSTEM, AND
 SUBDIVIDED TO SEPARATELY ADDRESS HAZARDOUS MATERIAL
 CLASSIFICATION CATEGORIES BASED ON TABLES 307.1(1) AND
 307.1(2). THE METHODS OF PROTECTION FROM SUCH HAZARDS,
 INCLUDING BUT NOT LIMITED TO CONTROL AREAS, FIRE
 PROTECTION SYSTEMS AND GROUP H OCCUPANCIES SHALL BE
 INDICATED IN THE REPORT AND ON THE CONSTRUCTION
 DOCUMENTS. THE OPINION AND REPORT SHALL BE PREPARED BY
 A QUALIFIED PERSON, FIRM OR CORPORATION APPROVED BY THE
 BUILDING OFFICIAL AND PROVIDED WITHOUT CHARGE TO THE
 ENFORCING AGENCY.
  
 FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP
 H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING
 THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO
 AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF
 EVERY BUILDING AND STRUCTURE.
  
 6) DEPENDING ON THE AMOUNT OF FLAMMABLE LIQUIDS BEING
 STORED, IF INDOORS OR OUTSIDE SHOW COMPLIANCE WITH;
 2014 FBC 414.2 CONTROL AREAS.
 CONTROL AREAS SHALL COMPLY WITH SECTIONS 414.2.1
 THROUGH 414.2.5 AND THE FLORIDA FIRE PREVENTION CODE.
  
 [F] 414.2.1 CONSTRUCTION REQUIREMENTS. CONTROL AREAS
 SHALL BE SEPARATED FROM EACH OTHER BY FIRE BARRIERS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH.
  
 [F] 414.2.2 PERCENTAGE OF MAXIMUM ALLOWABLE QUANTITIES.
 THE PERCENTAGE OF MAXIMUM ALLOWABLE QUANTITIES OF
 HAZARDOUS MATERIALS PER CONTROL AREA PERMITTED AT EACH
 FLOOR LEVEL WITHIN A BUILDING SHALL BE IN ACCORDANCE
 WITH TABLE 414.2.2.
  
 7) SHEET 0927-1 P4-003 SHOWS WHAT APPEARS TO BE A
 DOUBLE WALL TANK AND LEAK DETECTOR PLEASE PROVIDE THE
 MANUFACTURERS CUT SHEETS FOR THIS TANK SYSTEM IN
 ACCORDANCE WITH FBC-B 414.5.4.
  
 8) DEPICTED ON SHEET 0927-1 P4-003 IT APPEARS THE PUMP
 AND DISPENSER WITH HOSE IS ON TOP OF THE 500 GALLON
 TANK. BOTH TANKS ARE WELL WITHIN THE STRUCTURE, PLEASE
 PROVIDE HOW COMPLIANCE WITH DISPENSING OF FUEL WILL
 OCCUR AND IN COMPLIANCE WITH FBC-B 414.7.2 414.7.2
 DISPENSING, USE AND HANDLING. WHERE IS THE EMERGENCY
 SHUT OFF LOCATED?
  
 9) DEPICTED ON SHEET 0927-1 P4-003 IS NOTE # 3,
 PETROVEND FUEL SYSTEM CONTROL PANEL AND CARD READER
 PLEASE PROVIDE COMPLIANCE WITH 414.7.3 SUPERVISION AND
 MONITORING.
  
 10A) IF THE DISPENSING SYSTEMS ARE INSIDE THEY WILL
 NEED TO COMPLY WITH 414.5 INSIDE STORAGE, DISPENSING
 AND USE. THE INSIDE STORAGE, DISPENSING AND USE OF
 HAZARDOUS MATERIALS SHALL BE IN ACCORDANCE WITH
 SECTIONS 414.5.1 THROUGH 414.5.4 OF THIS CODE AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 10B) IF THE DISPENSING SYSTEMS ARE OUTSIDE THEY WILL
 NEED TO COMPLY WITH 414.6 OUTDOOR STORAGE, DISPENSING
 AND USE. THE OUTDOOR STORAGE, DISPENSING AND USE OF
 HAZARDOUS MATERIALS SHALL BE IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-07-23 Cont ID  
Sent By jleahy Date 2018-07-23 Time 08:01 Rev Time 0.00
Received By jleahy Date 2018-07-23 Time 08:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-05-10 Cont ID  
Sent By jleahy Date 2018-05-10 Time 10:46 Rev Time 0.00
Received By jleahy Date 2018-05-10 Time 10:45 Sent To  
Notes
2018-05-10 10:46:19NEED TO SUBMIT A DETAIL OF THE PUMP ELECTRIC AND THE
 CLASS LOCATIONS WHICH APPLY TO THE TANKS AND DISPENSER.
  
 PANELS ARE MOUNTED ON THE SIDE OF THE CAONTAINMENT AREA
 SHOW RISER DIAGRAM SHOWING WIRE SIZES, BREAKER SIZES,
 TYPE OF EQUIPMENT FOR THE LOCATION
 WIRING COMING INTO THE PANELS CLASS 1 DIV 1 OR 2 ???
  
 PLAN SHOWS NO ELECTRICAL INFORMATION

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-03-27 Cont ID  
Sent By jleahy Date 2018-03-27 Time 12:33 Rev Time 0.00
Received By jleahy Date 2018-03-27 Time 12:33 Sent To  
Notes
2018-03-27 12:41:47FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 I DO NOT SEE A PLAN SHOWING THE CLASS LOCATION
 SUBMITTED WITH YOUR PACKAGE.
  
 ON THE PLAN YOU WILL NEED TO SHOW(LAID OUT ON THE PLAN)
 THE CLASS LOCATION IN AND AROUND THE TANKS AND PUMPS.
  
 YOU STATE THAT THE LOCATION IS CLASS 1 DIV 1, WHAT
 ABOUT THE VENT STACK AREA?
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-04 Cont ID  
Sent By jleahy Date 2017-08-04 Time 09:44 Rev Time 0.00
Received By jleahy Date 2017-08-04 Time 09:44 Sent To  
Notes
2017-08-04 10:19:42FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NEED TO IDENTIFY THE CLASS LOCATION IN AND AROUND THE
 TANKS AND PUMP.
  
 500.4 GENERAL
 (A) DOCUMENTATION. A LL AREAS DESIGNATED AS HAZARDOUS
 (CLASSIFIED)
 LOCATIONS SHALL BE PROPERLY DOCUMENTED. THIS
 DOCUMENTATION
 SHALL BE AVAILABLE TO THOSE AUTHORIZED TO DESIGN,
 INSTALL, INSPECT,
 MAINTAIN, OR OPERATE ELECTRICAL EQUIPMENT AT THE
 LOCATION.
  
 NEED TO SHOW DISCONNECT, WIRE SIZES AND SEAL OFFS USED
 IN THIS INSTALLATION.
 NEED TO SHOW WHERE THESE ARE FED FROM CIRCUIT NUMBER
 AND LOCATION,

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-20 Cont ID  
Sent By pleduc Date 2018-03-20 Time   Rev Time 0.00
Received By pleduc Date 2018-03-20 Time 13:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-07-27 Cont ID  
Sent By wjolin Date 2017-07-27 Time 11:05 Rev Time 0.00
Received By wjolin Date 2017-07-27 Time 10:24 Sent To  
Notes
2017-07-27 11:04:595444 NORTH HAVERHILL ROAD - FUEL STORAGE AND DISPENSING
 TRACKING: 17060195
 PERMIT: 17021052
  
 DESIGN AND INSTALLATION SHALL CONFORM TO NFPA 1 - FIRE
 CODE: CHAPTER 42 - FUEL STORAGE AND REFUELING
  
 NFPA 1 - SECTION 42.5.2.3 FUEL DISPENSING SYSTEMS,
 INCLUDING DISPENSERS, HOSES, NOZZLES, BREAKAWAY
 FITTINGS, SWIVELS, FLEXIBLE CONNECTORS, DISPENSER
 EMERGENCY SHUTOFF VALVES, VAPOR RECOVERY SYSTEMS, AND
 PUMPS THAT ARE USED FOR ALCOHOL-BLENDED MOTOR FUELS
 SHALL BE LISTED OR APPROVED FOR THE SPECIFIC PURPOSE.
  
 NFPA 1 - SECTION 42.7.5.2 OPERATING INSTRUCTIONS SHALL
 BE CONSPICUOUSLY POSTED IN THE DISPENSING AREA. THE
 INSTRUCTIONS SHALL INCLUDE LOCATION OF EMERGENCY
 CONTROLS AND A REQUIREMENT THAT THE USER STAY OUTSIDE
 OF HIS/HER VEHICLE AND IN VIEW OF THE FUELING NOZZLE
 DURING DISPENSING. [30A:9.5.2]
  
 NFPA 1 SECTION 42.7.5.3 ADDITIONAL EMERGENCY
 INSTRUCTIONS SHALL BE CONSPICUOUSLY POSTED IN THE
 DISPENSER AREA. THE INSTRUCTIONS SHALL INCORPORATE THE
 FOLLOWING OR EQUIVALENT WORDING:
 EMERGENCY INSTRUCTIONS: IN CASE OF FIRE OR SPILL
 (1) USE EMERGENCY STOP BUTTON.
 (2) REPORT ACCIDENT BY CALLING (SPECIFY LOCAL FIRE
 NUMBER).REPORT LOCATION.
  
 NFPA 1 SECTION 42.7.2.5.4 SIGNS. WARNING SIGNS SHALL BE
 CONSPICUOUSLY POSTED IN THE DISPENSING AREA AND SHALL
 INCORPORATE THE FOLLOWING OR EQUIVALENT WORDING:
 WARNING:
 IT IS UNLAWFUL AND DANGEROUS TO DISPENSE GASOLINE INTO
 UNAPPROVED CONTAINERS.
 NO SMOKING.
 STOP MOTOR.
 NO FILLING OF PORTABLE CONTAINERS IN OR ON A MOTOR
 VEHICLE.
 PLACE CONTAINER ON GROUND BEFORE FILLING.
 DISCHARGE YOUR STATIC ELECTRICITY BEFORE FUELING BY
 TOUCHING A METAL SURFACE AWAY FROM THE NOZZLE.
 DO NOT RE-ENTER YOUR VEHICLE WHILE GASOLINE IS PUMPING.
 IF A FIRE STARTS, DO NOT REMOVE NOZZLE ? BACK AWAY
 IMMEDIATELY.
 DO NOT ALLOW INDIVIDUALS UNDER LICENSED AGE TO USE THE
 PUMP
  
 NFPA 1 SECTION 42.7.2.3.1 CLASS I OR CLASS II LIQUIDS
 SHALL NOT BE DISPENSED INTO PORTABLE CONTAINERS UNLESS
 THE CONTAINER IS CONSTRUCTED OF METAL OR IS APPROVED BY
 THE AHJ, HAS A TIGHT CLOSURE, AND IS FITTED WITH A
 SPOUT OR SO DESIGNED THAT THE CONTENTS CAN BE POURED
 WITHOUT SPILLING. THE HOSE NOZZLE VALVE SHALL BE
 MANUALLY HELD OPEN DURING THE DISPENSING OPERATION.
  
 NO PRODUCT DATA SUBMITTED FOR THE FUEL TANKS, PUMP,
 DISPENSER, STAIRS OR WORK PLATFORM.
  
 NO INFORMATION PROVIDED HOW THE STORAGE TANKS AND
 REFUELING VEHICLE WILL BE BONDED AND GROUNDED.
  
 HOW WILL THE STORAGE TANKS BE PROTECTED FROM VEHICULAR
 DAMAGE? IT APPEARS THE MOWERS, CARTS AND ATVS WOULD BE
 ENTERING INTO THE ROOFED STRUCTURE TO BE REFUELED.
  
 NO PORTABLE FIRE EXTINGUISHERS PROVIDED TO PROTECT THE
 HAZARD. NFPA 1 - SECTION 42.7.2.5. 2 EXTINGUISHERS FOR
 OUTSIDE MOTOR FUEL DISPENSING AREAS SHALL BE PROVIDED
 ACCORDING TO THE EXTRA (HIGH) HAZARD REQUIREMENTS FOR
 CLASS B HAZARDS, EXCEPT THAT THE MAXIMUM TRAVEL
 DISTANCE TO AN 80 B:C EXTINGUISHER SHALL BE PERMITTED
 TO BE 100 FEET.
  
 PROVIDE NO SMOKING OR OPEN FLAME WEATHERPROOF SIGNAGE.
  
 PROVIDE NFPA 704 DIAMOND PLACARD INDICATING THE HAZARDS
 OF THE FUELS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WPB FIRE RESCUE
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-08-22 Cont ID  
Sent By shill Date 2018-08-22 Time 11:45 Rev Time 0.00
Received By shill Date 2018-08-08 Time 13:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-23 Cont ID  
Sent By jleahy Date 2018-07-23 Time 08:01 Rev Time 0.00
Received By jleahy Date 2018-07-16 Time 09:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-24 Cont ID  
Sent By shill Date 2018-05-24 Time 11:08 Rev Time 0.00
Received By shill Date 2018-05-03 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-17 Cont ID  
Sent By lmarchan Date 2018-04-17 Time 07:52 Rev Time 0.00
Received By lmarchan Date 2018-03-19 Time 13:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-05 Cont ID  
Sent By jwitmer Date 2017-08-05 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2017-06-28 Time 08:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-06 Cont ID  
Sent By ccole Date 2018-04-06 Time 11:43 Rev Time 0.00
Received By ccole Date 2018-04-06 Time 10:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By ccole Date 2017-07-28 Time 07:42 Rev Time 0.00
Received By ccole Date 2017-07-27 Time 17:47 Sent To  
Notes
2017-07-28 08:12:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060195
 7/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMPLY WITH FIRE AND PLUMBING PLAN REVIEW COMMENTS.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TANKS.
 INDICATE ON THE PLAN COMPLIANCE WITH SECTION 4.3.5.1(1)
 & (2) NFPA 30A FOR FIRE RESISTIVE PROTECTION AND
 EMERGENCY VENTING SIZING.
  
 3) SHOW COMPLIANCE WITH TABLE 4.3.2.4 NFPA 30A FOR
 MINIMUM SEPARATION REQUIREMENTS FOR THE TANKS TO
 NEAREST IMPORTANT BUILDING ON THE SAME PROPERTY, FROM
 LOT LINES, FROM THE PUBLIC WAY, AND BETWEEN TANKS.
 ADDITIONALLY SEPARATION COMPLIANCES ARE LISTED IN
 TABLES 22.4.1.1(A) & 22.4.1.1(B) NFPA 30- PLEASE SHOW
 COMPLIANCE.
  
 4) SHOW COMPLIANCE WITH SECTION 4.3.6.3 NFPA 30A FOR A
 MEANS TO PROVIDE AN AUDIBLE ALARM WHEN THE LIQUID LEVEL
 IN THE TANKS REACHES 90 PERCENT OF CAPACITY, AND FOR A
 MEANS TO AUTOMATCALLY STOP THE FLOW OF LIQUID INTO THE
 TANK WHEN THE LEVEL REACHES 98 PERCENT CAPACITY OR TO
 RESTRICT THE FLOW RATE OF 9.5 L/MIN (2.5 GPM) WHEN THE
 LIQUID IN THE TANK REACHES 95 PERCENT CAPACITY.
  
 5) THE FRONT GATES TO THE TANK BUILDING SHALL BE
 MINIMUM 6 FT. HIGH, SHALL HAVE A MINIMUM SEPARATION OF
 3 FT. TO THE TANKS, AND SHALL HAVE GATES THAT ARE
 SECURED AGAINST ENTRY. PLEASE PROVIDE DETAILS INCLUDING
 PLAN AND ELEVATION VIEWS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-17 Cont ID  
Sent By tklarge Date 2018-04-17 Time 06:11 Rev Time 0.00
Received By tklarge Date 2018-04-10 Time 05:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By tklarge Date 2017-07-26 Time 10:11 Rev Time 0.00
Received By tklarge Date 2017-07-24 Time 14:40 Sent To  
Notes
2017-07-24 15:03:101) SHOW THE SPACING BETWEEN THE FUEL TANKS. COMPLY WITH
 NFPA 30, SEC. 15.3 & TABLE 15.3.WPB AMEND. TO FBC SEC.
 107.2.1.
 2) LABEL ALL DROP PIPES ENTERING THE TANKS.( THERE IS A
 DROP PIPE IN THE GASOLINE TANK THAT IS LOCATED BETWEEN
 THE DISPENSER AND FUEL FILL PORT AND ALSO IN THE DIESEL
 TANK LOCATED IN THE LEFT SIDE OF THE TANK NEXT TO THE
 CLOCK GAUGE THAT IS NOT IDENTIFIED.)WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) SHOW THE SIZE OF ALL VENTS & THE WITHDRAWL
 CONNECTIONS / DROP TUBES ON EACH TANK. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR BOTH
 TANKS.WPB AMEND. TO FBC SEC. 107.2.1.
 5) INDICATE THE TYPE OF PIPE MATERIAL USED FOR THE TANK
 VENTS. MATERIALS SHALL COMPLY WITH NFPA 30 SEC. 27.4.1
 & ASME B31.
 6) EACH CONNECTION TO AN ABOVE GROUND TANK THROUGH
 WHICH LIQUID CAN NORMALLY FLOW SHALL BE PROVIDED WITH
 AN INTERNAL OR AN EXTERNAL VALVE LOCATED AS CLOSE AS
 PRACTICAL TO THE SHELL OF THE TANK PER NFPA 30
 SEC.22.13.2. ( REFER TO DISPENSER LINES.
 7) INSTALLATION INSTRUCTIONS FOR ABOVE GROUND STORAGE
 TANKS. - FACTORY-BUILT ABOVEGROUND TANKS SHALL BE
 PROVIDED WITH INSTRUCTIONS FOR TESTING THE TANKS AND
 FOR INSTALLATION OF THE NORMAL AND EMERGENCY VENTS.
 NFPA 30 SEC. 22.16.
 8) SUBMIT A KEY PLAN AND SITE PLAN SHOWING THE LOCATION
 OF THE FUEL TANKS AND THE DISTANCES FROM ANY ADJOINING
 BUILDINGS. WPB AMEND. TO FBC SEC. 107.2.1.
 9) IF THESE TANKS WILL BE EXPOSED TO ANY TYPE OF
 VEHICULAR TRAFFIC THEN COLLISION PROTECTION SHALL BE
 PROVIDED PER NFPA 30 SEC.22.15. CLARIFY.
 10) STATIC ELECTRICITY. - MEANS SHALL BE PROVIDED TO
 MINIMIZE GENERATION OF STATIC ELECTRICITY PER NFPA 30
 SEC. 18.5.2.2. SUCH MEANS SHALL MEET THE REQUIREMENTS
 OF NFPA 30 SEC.6.5.4.
 11) SUBMIT MANUF. SPECIFICATIONS FOR THE HOSES,
 DISPENSERS, VALVES, ETC. PIPING, VALVES AND FITTINGS
 SHALL COMPLY WITH NFPA 30 CHAPTER 27.
 12) WHERE PUMPS ARE USED FOR LIQUID TRANSFER, MEANS
 SHALL BE PROVIDED TO DEACTIVATE LIQUID TRANSFER IN THE
 EVENT OF A LIQUID SPILL OR FIRE PER NFPA 30 SEC.
 18.5.2.3.
 13) IF HOSE IS USED IN THE TRANSFER OPERATION, IT SHALL
 BE EQUIPPED WITH A SELF-CLOSING VALVE WITHOUT A
 HOLD-OPEN LATCH IN ADDITION TO THE OUTLET VALVE. ONLY
 LISTED OR APPROVED HOSE SHALL
 BE USED. NFPA 30 SEC. 18.5.2.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2018-08-22 Cont ID  
Sent By shill Date 2018-08-22 Time 11:44 Rev Time 0.00
Received By shill Date 2018-08-22 Time 11:44 Sent To  
Notes
2018-08-22 11:45:23NEW FUEL OIL STORAGE TANK CALCS S&S SUBMITTED
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2018-07-21 Cont ID  
Sent By shill Date 2018-07-21 Time 09:53 Rev Time 0.00
Received By shill Date 2018-07-21 Time 09:53 Sent To  
Notes
2018-07-21 09:56:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FUEL TANK CALCULATIONS ARE NOT DIGITALLY SIGNED AND
 SEALED; PROVIDE A SIGNED, SEALED, DATED ORIGINAL IN
 ACCORDANCE WITH FS471 AND FAC61G15-23.002. CALCS DO NOT
 HAVE A TITLE BLOCK; PAPER CALCS ARE TO INCLUDE A TITLE
 BLOCK IN COMPLIANCE WITH FS471, FAC61G15-23.
  
 2. OTHER PAGES NOT DIGITALLY SIGNED AND SEALED ARE
 INCLUDED WITH THE MASTER, SIGNED & SEALED.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-05-24 Cont ID  
Sent By shill Date 2018-05-24 Time 11:08 Rev Time 0.00
Received By shill Date 2018-05-24 Time 11:08 Sent To  
Notes
2018-05-24 11:08:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FUEL TANK CALCULATIONS ARE NOT DIGITALLY SIGNED AND
 SEALED; PROVIDE A SIGNED, SEALED, DATED ORIGINAL IN
 ACCORDANCE WITH FS471 AND FAC61G15-23.002. CALCS DO NOT
 HAVE A TITLE BLOCK; PAPER CALCS ARE TO INCLUDE A TITLE
 BLOCK IN COMPLIANCE WITH FS471, FAC61G15-23.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-04-17 Cont ID  
Sent By tklarge Date 2018-04-17 Time 06:15 Rev Time 0.00
Received By tklarge Date 2018-04-17 Time 06:15 Sent To  
Notes
2018-04-17 06:16:27SHTS. A0-02 & A1-40 ARE NOT DIGITALLY SIGNED AND
 SEALED. T. LARGE
2018-04-06 11:47:43SHEETS A0-02 & A1-40: NO DIG/SIGS.
 SHEETS E1-00-6 & P4-003 OK
 CCOLE- 4/6/18

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-08-05 Cont ID  
Sent By jwitmer Date 2017-08-05 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2017-08-05 Time 08:25 Sent To  
Notes
***NONE***