Plan Review Details - Permit 17060192
Plan Review Stops For Permit 17060192
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-12-21 Cont ID  
Sent By aclange Date 2017-12-21 Time 15:02 Rev Time 0.00
Received By aclange Date 2017-12-21 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-11-01 Cont ID  
Sent By aclange Date 2017-10-31 Time 14:10 Rev Time 0.00
Received By aclange Date 2017-10-31 Time 11:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-09-13 Cont ID  
Sent By shill Date 2017-09-13 Time 17:40 Rev Time 0.00
Received By shill Date 2017-09-13 Time 16:58 Sent To  
Notes
2017-09-13 17:40:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 17060191 3 STORY APARTMENT BUILDING
 17060189 6 STORY APARTMENT BUILDING
 17060192 CLUBHOUSE (BLDG F)
  
 1. ALL PAGES HAVE AN INCORRECT ADDRESS AND NOT ALL ARE
 CONSISTENT WITH EACH OTHER (DIFFERENT INCORRECT
 ADDRESSES). FBC 107, PLEASE CORRECT THE ADDRESS ON EACH
 PAGE.
  
 2ND REVIEW, SHEET SP HAS A DIFFERENT ADDRESS THAN THE
 OTHER PAGES. CHECK ALL.
  
 2. OK
  
 3. SHEET LS DECLARES A3 OCCUPANCY, OFFICE SHOULD BE
 BUSINESS, PLEASE REVISE.
  
 2ND REVIEW, THIS BUILDING IS MIXED OCCUPANCY, A3 AND B.
 REVISE IN ALL APPLICABLE LOCATIONS OR REVISE PLAN TO
 INCLUDE APPLICABLE EXCEPTION.
  
 4-8. OK
  
 NEW COMMENT:
  
 9. ADDRESS PLUMBING & FIRE'S COMMENTS AS THEY ARE
 APPLICABLE FOR BUILDING REVIEW.
  
  
 10. PROVIDE THE SOILS REPORT, FBC 107.
  
 **********************************************
 INTERNAL USE ONLY
  
 17060192 BUILDING DATA FOR C.O./REPORTING
  
 USC-404 318 ... - NEW: ATHLETIC/SOCIAL CLUBS
 SQUARE FEET - 5090
  
 CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B
 UNITS: 1
 FLOORS: 2
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 5090
 SQ FT FOOTPRINT: 3330
 SQ FT ROOF: 5090
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 98
 PROP USE: CLUB/PRKG
 SPRINKLER SYS? N
 SPRK REQ'D? N
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED A2
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-05 Cont ID  
Sent By shill Date 2017-07-05 Time 15:02 Rev Time 0.00
Received By shill Date 2017-07-05 Time 14:30 Sent To  
Notes
2017-07-05 15:02:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 17060191 3 STORY APARTMENT BUILDING
 17060189 6 STORY APARTMENT BUILDING
 17060192 CLUBHOUSE (BLDG F)
  
 1. ALL PAGES HAVE AN INCORRECT ADDRESS AND NOT ALL ARE
 CONSISTENT WITH EACH OTHER (DIFFERENT INCORRECT
 ADDRESSES). FBC 107, PLEASE CORRECT THE ADDRESS ON EACH
 PAGE.
  
 2. FS471.0195, THE DBPR RECORD FOR THE FOLLOWING
 ENGINEER(S) DO NOT REFLECT THAT THE ADVANCED FLORIDA
 BUILDING CODE COURSE HAS BEEN COMPLETED. EMAIL THE
 CERTIFICATE TO FBPE AND REQUEST THAT THE DBPR RECORD BE
 UPDATED. NOTE THAT IT IS POSSIBLE THAT THE COURSE WAS
 COMPLETED AND THE WEBSITE IS NOT CURRENT.
  
 SANTIAGO ARANEGUI, PE
 JOE SPASOVSKI, PE
  
 PERMIT ISSUANCE WILL NOT BE DELAYED DUE TO THIS
 COMMENT. HOWEVER, FLORIDA STATUTE REQUIRES THAT:
 LOCAL JURISDICTIONS SHALL BE RESPONSIBLE FOR NOTIFYING
 THE BOARD WHEN DESIGN DOCUMENTS ARE SUBMITTED FOR
 BUILDING CONSTRUCTION PERMITS BY PERSONS WHO ARE NOT IN
 COMPLIANCE WITH THIS SECTION.
  
 3. SHEET LS DECLARES A3 OCCUPANCY, OFFICE SHOULD BE
 BUSINESS, PLEASE REVISE.
  
 4. S1.0, DESIGN PRESSURES DO NOT STATE ULTIMATE OR ASD
 FOR COMPONENT AND CLADDING PRESSURES, FBC 107. WIND
 DESIGN CRITERIA SHOULD INCLUDE BOTH (SEE FBC B
 1603.1.4), ONLY ASD WIND SPEED WAS INCLUDED, C&C
 PRESSURES APPEAR TO BE ASD BUT NOT STATED AS SUCH,
 PLEASE CLARIFY.
  
 5. S1.0, ROOF LIVE LOAD IS 20PSF; FBC B TABLE 1607.1
 REQUIRES 300 CONCENTRATED FOR "ALL ROOF SURFACES
 SUBJECT TO MAINTENANCE WORKERS". RTU EQUIPMENT SHOWN.
 EITHER REVISE DESIGN CRITERIA FOR THIS ROOF SECTION OR
 PROVIDE RATIONALE FOR 20PSF LIVE LOAD.
  
 6. IT APPEARS THAT NOT ALL LAP SPLICES WERE SPECIFIED
 ON THE PLAN FOR THE FOUNDATION; REVISE PLAN OR ADVISE
 WHERE THIS CAN BE LOCATED, FBC 107, FBC B CHAPTER 19.
  
 7. AS THIS IS NEW CONSTRUCTION, APPLY FOR AN
 ENGINEERING PERMIT; 561-494-1040. ENGINEERING
 DEPARTMENT APPROVAL IS REQUIRED PRIOR TO PERMIT
 ISSUANCE. CONTACT THEM DIRECTLY REGARDING REQUIREMENTS.
 IF YOU HAVE ALREADY APPLIED, PROVIDE THE APPLICATION
 NUMBER. I WAS UNABLE TO LOCATE AN ENGINEERING
 APPLICATION FOR THIS PARCEL ID.
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 8. A SEPARATE ROOF PERMIT IS REQUIRED. NO ROOF COVERING
 PRODUCT APPROVAL WAS SUBMITTED. THIS MAY BE SUBMITTED
 AT TIME OF ROOF PERMIT APPLICATION.
  
 FBC 1609, AT THIS TIME, APPLICANT MAY INDICATE WHICH
 APPROVED ASSEMBLY IS PROPOSED. IF THIS IS DONE NOW
 (ROOF PRODUCT APPROVAL SUBMITTED AND ASSEMBLY
 SELECTED), THE ROOF SUB PERMIT WILL BE ISSUED AT TIME
 OF SUB PERMIT APPLICATION WITHOUT ADDITIONAL
 INFORMATION REQUIRED.
  
 IF APPLICANT DOES NOT PROVIDE THIS INFORMATION AT THIS
 TIME, THIS PERMIT WILL BE ISSUED WITH PROVISO THAT, AT
 TIME OF ROOF SUB PERMIT APPLICATION, A PRODUCT APPROVAL
 REVIEWED BY DESIGNER OF RECORD IS TO BE SUBMITTED AND
 THE APPROVED ASSEMBLY IS TO BE SELECTED. A PLAN REVIEW
 WILL BE REQUIRED AT THAT TIME.
  
 **********************************************
 INTERNAL USE ONLY
  
 17060192 BUILDING DATA FOR C.O./REPORTING
  
 USC-404 318 ... - NEW: ATHLETIC/SOCIAL CLUBS
 SQUARE FEET - 5090
  
 CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B
 UNITS: 1
 FLOORS: 2
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 5090
 SQ FT FOOTPRINT: 3330
 SQ FT ROOF: 5090
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 98
 PROP USE: CLUB/PRKG
 SPRINKLER SYS? N
 SPRK REQ'D? N
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED A2
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-05 Cont ID  
Sent By jpearson Date 2017-09-05 Time 12:55 Rev Time 0.00
Received By jpearson Date 2017-09-05 Time 12:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By jpearson Date 2017-06-29 Time 09:01 Rev Time 0.00
Received By jpearson Date 2017-06-29 Time 09:01 Sent To  
Notes
2017-06-29 09:06:09CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SUBMIT PLAN WITH CORRECT ADDRESS. FBC 107.2.1
 2. THIS PLAN INCLUDES THE SITE LIGHTING. PROVIDE NOTE
 THAT STATES SITE LIGHTING WILL BE UNDER SEPARATE
 PERMIT. FBC 105.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2017-10-05 Cont ID  
Sent By squinone Date 2017-10-05 Time   Rev Time 0.00
Received By squinone Date 2017-10-05 Time   Sent To  
Notes
2017-10-05 15:13:451) NO CIVIL PLANS WERE INCLUDED WITH THIS SUBMITTAL.
 CIVIL PLANS ARE UNDER REVIEW THROUGH ENGINEERING PLAN
 REVIEW, E17060013.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-07-05 Cont ID  
Sent By shill Date 2017-07-05 Time 14:31 Rev Time 0.00
Received By shill Date 2017-07-05 Time 14:31 Sent To  
Notes
2017-07-05 14:31:17AS THIS IS NEW CONSTRUCTION, APPLY FOR AN ENGINEERING
 PERMIT; 561-494-1040.
  
 ENGINEERING DEPARTMENT APPROVAL IS REQUIRED PRIOR TO
 PERMIT ISSUANCE. CONTACT THEM DIRECTLY REGARDING
 REQUIREMENTS. IF YOU HAVE ALREADY APPLIED, PROVIDE THE
 APPLICATION NUMBER. I WAS UNABLE TO LOCATE AN
 ENGINEERING APPLICATION FOR THIS PARCEL ID.
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-11-02 Cont ID  
Sent By wjolin Date 2017-11-02 Time 09:23 Rev Time 0.00
Received By wjolin Date 2017-11-02 Time 09:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-08-16 Cont ID  
Sent By wjolin Date 2017-08-16 Time 14:01 Rev Time 0.00
Received By wjolin Date 2017-08-16 Time 14:01 Sent To  
Notes
2017-08-16 14:01:462201 NORTH AUSTRALIAN AVENUE - CLUBHOUSE (2191 NORTH
 AUSTRALIAN AVE)
 PERMIT #17060192
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PERMIT INDICATES THE ADDRESS OF THE CLUBHOUSE IS 2191
 NORTH AUSTRALIAN AVENUE; HOWEVER, THE PLANS INDICATE AN
 ADDRESS OF 2201 NORTH AUSTRALIAN AVENUE.
  
 SHEET LS:
 REPEAT COMMENT - NOTE #6 STATES, "AN NFPA 13 COMPLIANT
 SPRINKLER SYSTEM IS REQUIRED FOR THIS STRUCTURE";
 HOWEVER, THE CLUBHOUSE SCOPE OF WORK STATES THIS IS A
 NON-SPRINKLERED BUILDING.
  
 REPEAT COMMENT - PROVIDE A FURNITURE/EQUIPMENT PLAN
 JUSTIFYING THE USAGE OF THE 15 AND 50 SQ.FT. PER PERSON
 OCCUPANT LOAD FACTORS.
  
 REPEAT COMMENT - HOW IS THE CLUBHOUSE FIRE AND LIFE
 SAFETY AFFECTED BY THE COVERED PATIO AND POOL AREA? NO
 INFORMATION SUBMITTED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-28 Cont ID  
Sent By wjolin Date 2017-06-28 Time 15:45 Rev Time 0.00
Received By wjolin Date 2017-06-28 Time 15:09 Sent To  
Notes
2017-06-28 15:31:242201 NORTH AUSTRALIAN AVENUE - CLUBHOUSE
 PERMIT #17060192
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS:
  
 PLAN SCALE IS INCORRECTLY INDICATED AS 1/4"=1'-0".
  
 NOTE #6 STATES, "AN NFPA 13 COMPLIANT SPRINKLER SYSTEM
 IS REQUIRED FOR THIS STRUCTURE"; HOWEVER, THE CLUBHOUSE
 SCOPE OF WORK STATES THIS IS A NON-SPRINKLERED
 BUILDING.
  
 PROVIDE A FURNITURE/EQUIPMENT PLAN JUSTIFYING THE USAGE
 OF THE 15 AND 50 SQ.FT. PER PERSON OCCUPANT LOAD
 FACTORS.
  
 THE TWO NORTH ARROW COMPASSES ON THE PLAN CONFLICT WITH
 EACHOTHER.
  
 HOW IS THE CLUBHOUSE FIRE AND LIFE SAFETY AFFECTED BY
 THE COVERED PATIO AND POOL AREA? NO INFORMATION
 SUBMITTED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET A-11: SEVERAL WALLS INDICATE A FIRE RESISTANCE
 RATING; HOWEVER, ONLY DOOR #10 INDICATES IT HAS A FIRE
 RATING.
  
 GENERAL: NO CIVIL PLANS SUBMITTED.
  
 GENERAL: PER NFPA 241 SECTION 8.7.2.3, WHERE
 UNDERGROUND WATER MAINS AND HYDRANTS ARE TO BE
 PROVIDED, THEY SHALL BE INSTALLED, TESTED, APPROVED,
 AND IN SERVICE PRIOR TO VERTICAL CONSTRUCTION WORK.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-12-21 Cont ID  
Sent By aclange Date 2017-12-21 Time 15:03 Rev Time 0.00
Received By aclange Date 2017-12-20 Time 14:56 Sent To  
Notes
2017-12-21 09:12:35IMPACT FEES ROUTED TO ACLANGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-03 Cont ID  
Sent By aclange Date 2017-11-03 Time 11:24 Rev Time 0.00
Received By cpuell Date 2017-10-19 Time 10:54 Sent To  
Notes
2017-10-26 12:03:13C32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-11 Cont ID  
Sent By shill Date 2017-10-11 Time 08:25 Rev Time 0.00
Received By shill Date 2017-08-07 Time 15:38 Sent To  
Notes
2017-08-07 15:38:46C32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-05 Cont ID  
Sent By shill Date 2017-07-05 Time 15:03 Rev Time 0.00
Received By shill Date 2017-06-05 Time 13:46 Sent To  
Notes
2017-06-06 13:46:51C29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-12-21 Cont ID  
Sent By aclange Date 2017-12-21 Time 13:34 Rev Time 0.00
Received By aclange Date 2017-12-21 Time 13:34 Sent To  
Notes
2017-12-21 13:36:2912/21/17
 PALM BEACH COUNTY IMPACT FEES PAID. $527,017.05
 RECEIPT NO: 2017-1220-331

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-11-01 Cont ID  
Sent By aclange Date 2017-11-01 Time 13:05 Rev Time 0.00
Received By aclange Date 2017-11-01 Time 09:39 Sent To  
Notes
2017-11-01 13:05:25BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-07-05 Cont ID  
Sent By shill Date 2017-07-05 Time 14:30 Rev Time 0.00
Received By shill Date 2017-07-05 Time 14:30 Sent To  
Notes
2017-07-05 14:30:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
  
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE HAVE BEEN PAID ARE REQUIRED TO BE
 SUBMITTED. THIS IS TO BE DONE AFTER REVIEWS HAVE PASSED
 AND PLANS ARE STAMPED BY THE CITY, BUT BEFORE PERMIT
 ISSUANCE.
  
 CONTACT 561-233-5025 FOR MORE INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-09-05 Cont ID  
Sent By ccole Date 2017-09-05 Time 15:05 Rev Time 0.00
Received By ccole Date 2017-09-05 Time 14:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-30 Cont ID  
Sent By ccole Date 2017-06-30 Time 12:15 Rev Time 0.00
Received By ccole Date 2017-06-30 Time 12:15 Sent To  
Notes
2017-06-30 12:37:041ST REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION
 CODES
 PERMIT #17060192
 6/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE NOTE AT RTU #1 TO SET THE O/A INTAKE
 TO 140 CFMS IS INCORRECT AND IN CONFLICT WITH THE
 VENTILATION CALCULATION TABLE WHICH IS SPECIFYING 426
 CFMS FOR THE RECREATION RM. PLEASE INCLUDE THE LOBBY IN
 THE CALCULATIONS.
  
 2) M-1: THE VENTILATION CALCULATION FOR THE GYM IS NOT
 IN COMPLIANCE WITH TABLE 403.3 WHICH REQUIRES 0.30 CFMS
 PER SF FOR A GYM, HOWEVER THE CLASSIFICAIONS FOR THIS
 SPACE MAY BE CLOSER TO HEALTH CLUB/AEROBICS ROOMS WITH
 REQUIRES AN OCCUPANT DENSITY CALCULATION OF 40 PERSONS
 PER SF. OR 22 PERSONS LOAD IN THE 550 SF. THE CALC
 WOULD THEN RESULT TO 22 PERSONS X 20 CFMS= 440 CFMS +
 ,06 X550= 33 CFMS FOR A TOTAL OF 473 CFMS FOR THE
 SPACE. PLEASE CORRECT ACCORDINGLY.
  
 3) M-1: CLARIFY IF THE AC CLOSETS ARE BOTH OPEN PLENUM
 CLOSETS AS SHOWN IN THE DETAIL ON M2, AND INDICATE WHAT
 TYPE OF DOOR WILL ENCLOSE THE AHU #3 CLOSET- IT IS NOT
 SHOWN ON THE ARCHITECTURAL PLANS. DOOR #5 WHICH
 ENCLOSES THE AHU #2 CLOSET IS A WOOD DOOR WHICH IS
 COMPLIANT IF THE RETURN IS DUCTED DIRECTLY TO THE AHU.
 OTHERWISE A NON-COMBUSTIBLE DOOR IS REQUIRED PER
 SECTIONS
 SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION, AND
 SECTION 602 FBC-14 MECHANICAL.
  
 4) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR THE
 RTU AND CONDENSER INSTALLATIONS- SEE SECTION 301.15
 FBC-14 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING.
  
 5) M-2: CORRECT NOTE #3 AT THE AHU MOUNTING DETAIL
 WHICH IS REFERENCING A RESIDIENTIAL CODE SECTION, AND
 SEE SECTION C403.2.7.3.3 WHICIH REQUIRES A MINIMUM 4"
 CLEARANCE SPACE AROUND THE AIR HANDLER.
  
 6) ENERGYGAUGE COMPLIANCE SUBMITTAL: A) THE
 OWNER/AGENT'S SIGNATURE IS MISSING- PAGE 3. B) THE
 DESIGNER OR ENGINEER'S MANDATORY REQUIREMENTS CHECKLIST
 NOT COMPLETED- PAGE 8.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-11-03 Cont ID  
Sent By gjohnson Date 2017-11-03 Time 09:27 Rev Time 0.00
Received By gjohnson Date 2017-11-01 Time 17:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-09-06 Cont ID  
Sent By gjohnson Date 2017-09-06 Time 15:32 Rev Time 0.00
Received By gjohnson Date 2017-09-06 Time 15:32 Sent To  
Notes
2017-09-06 16:15:571ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT HAS NOT COMPLIED 3. TOILET PAPER
 DISPERSER SHALL COMPLY WITH FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 NEW COMMENTS:
  
 1. THE WATER FOUNTAIN IS REQUIRED TO COMPLY WITH FBC
 ACC 307 PROTRUDING OBJECTS
  
 2. GRAB BARS SHALL BE MEASURED FROM FINISH FLOOR TO THE
 TOP OF THE GRIPPING SURFACE, PER FBC ACC 609.4
  
 3.SHOW CLEAR FLOOR SPACE FOR SINK IN COFFEE ROOM. PER
 FBC ACC 606.2
  
 4. SHT. A-3.1 SHOWS TOTAL ROOF SQFT OF 1526FT SHT. P-3
 SHOWS 1470SQFT PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-03 Cont ID  
Sent By gjohnson Date 2017-07-03 Time 12:42 Rev Time 0.00
Received By gjohnson Date 2017-06-30 Time 18:06 Sent To  
Notes
2017-07-03 13:13:581ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE INDICATE ON PLAN THAT THIS SHALL COMPLY WITH
 FLORIDA BUILDING CODE, ACCESSIBILITY, 5TH EDITION
 (2014)
  
 2.THE GRAB BARS SHALL COMPLY WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
 PLEASE CLARIFY THE FIGURE ON THE PLAN IS UN CLEAR.
  
 3. TOILET PAPER DISPERSER SHALL COMPLY WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 4. ON THE SANITARY RISER DIAGRAM THE FLOOR DRAINS ARE
 NOT VENTED PROPERLY THEY SHOULD CONNECT TO A VENTED
 BRANCH DRAIN NOT THE BUILDING DRAIN. PER FBC PL 901.2.1
  
 5. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PLEASE PROVIDE A NOTE ON THE PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 6. PROVIDE STORM RISER DIAGRAM. PER WPB AMEN TO FBC
 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2017-09-13 Cont ID  
Sent By shill Date 2017-09-13 Time 17:38 Rev Time 0.00
Received By shill Date 2017-09-13 Time 17:37 Sent To  
Notes
2017-09-13 17:39:34NO ROOF PRODUCT APPROVAL SUBMITTED
 A SEPARATE ROOF PERMIT IS REQUIRED. APPLICANT IS TO
 SUBMIT PRODUCT APPROVAL, REVIEWED BY DESIGNER OF
 RECORD, AND ENGINEERING IF REQUIRED.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-09-13 Time   Rev Time 0.00
Received By pgreilic Date 2017-09-13 Time 15:23 Sent To  
Notes
2017-09-13 15:23:51PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-06-27 Time   Rev Time 0.00
Received By pgreilic Date 2017-06-23 Time 15:01 Sent To  
Notes
2017-06-28 11:34:05PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved