| Plan Review Stops For Permit 17060192 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2017-12-21 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-12-21 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-12-21 |
Time |
07:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-11-01 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-10-31 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-10-31 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-09-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-13 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-13 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2017-09-13 17:40:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 17060191 3 STORY APARTMENT BUILDING | | | 17060189 6 STORY APARTMENT BUILDING | | | 17060192 CLUBHOUSE (BLDG F) | | | | | | 1. ALL PAGES HAVE AN INCORRECT ADDRESS AND NOT ALL ARE | | | CONSISTENT WITH EACH OTHER (DIFFERENT INCORRECT | | | ADDRESSES). FBC 107, PLEASE CORRECT THE ADDRESS ON EACH | | | PAGE. | | | | | | 2ND REVIEW, SHEET SP HAS A DIFFERENT ADDRESS THAN THE | | | OTHER PAGES. CHECK ALL. | | | | | | 2. OK | | | | | | 3. SHEET LS DECLARES A3 OCCUPANCY, OFFICE SHOULD BE | | | BUSINESS, PLEASE REVISE. | | | | | | 2ND REVIEW, THIS BUILDING IS MIXED OCCUPANCY, A3 AND B. | | | REVISE IN ALL APPLICABLE LOCATIONS OR REVISE PLAN TO | | | INCLUDE APPLICABLE EXCEPTION. | | | | | | 4-8. OK | | | | | | NEW COMMENT: | | | | | | 9. ADDRESS PLUMBING & FIRE'S COMMENTS AS THEY ARE | | | APPLICABLE FOR BUILDING REVIEW. | | | | | | | | | 10. PROVIDE THE SOILS REPORT, FBC 107. | | | | | | ********************************************** | | | INTERNAL USE ONLY | | | | | | 17060192 BUILDING DATA FOR C.O./REPORTING | | | | | | USC-404 318 ... - NEW: ATHLETIC/SOCIAL CLUBS | | | SQUARE FEET - 5090 | | | | | | CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B | | | UNITS: 1 | | | FLOORS: 2 | | | BEDROOMS: | | | ROOMS: | | | SQ FT LIVABLE: 5090 | | | SQ FT FOOTPRINT: 3330 | | | SQ FT ROOF: 5090 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 98 | | | PROP USE: CLUB/PRKG | | | SPRINKLER SYS? N | | | SPRK REQ'D? N | | | BATHRMS: | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED A2 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-07-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-05 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-05 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2017-07-05 15:02:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 17060191 3 STORY APARTMENT BUILDING | | | 17060189 6 STORY APARTMENT BUILDING | | | 17060192 CLUBHOUSE (BLDG F) | | | | | | 1. ALL PAGES HAVE AN INCORRECT ADDRESS AND NOT ALL ARE | | | CONSISTENT WITH EACH OTHER (DIFFERENT INCORRECT | | | ADDRESSES). FBC 107, PLEASE CORRECT THE ADDRESS ON EACH | | | PAGE. | | | | | | 2. FS471.0195, THE DBPR RECORD FOR THE FOLLOWING | | | ENGINEER(S) DO NOT REFLECT THAT THE ADVANCED FLORIDA | | | BUILDING CODE COURSE HAS BEEN COMPLETED. EMAIL THE | | | CERTIFICATE TO FBPE AND REQUEST THAT THE DBPR RECORD BE | | | UPDATED. NOTE THAT IT IS POSSIBLE THAT THE COURSE WAS | | | COMPLETED AND THE WEBSITE IS NOT CURRENT. | | | | | | SANTIAGO ARANEGUI, PE | | | JOE SPASOVSKI, PE | | | | | | PERMIT ISSUANCE WILL NOT BE DELAYED DUE TO THIS | | | COMMENT. HOWEVER, FLORIDA STATUTE REQUIRES THAT: | | | LOCAL JURISDICTIONS SHALL BE RESPONSIBLE FOR NOTIFYING | | | THE BOARD WHEN DESIGN DOCUMENTS ARE SUBMITTED FOR | | | BUILDING CONSTRUCTION PERMITS BY PERSONS WHO ARE NOT IN | | | COMPLIANCE WITH THIS SECTION. | | | | | | 3. SHEET LS DECLARES A3 OCCUPANCY, OFFICE SHOULD BE | | | BUSINESS, PLEASE REVISE. | | | | | | 4. S1.0, DESIGN PRESSURES DO NOT STATE ULTIMATE OR ASD | | | FOR COMPONENT AND CLADDING PRESSURES, FBC 107. WIND | | | DESIGN CRITERIA SHOULD INCLUDE BOTH (SEE FBC B | | | 1603.1.4), ONLY ASD WIND SPEED WAS INCLUDED, C&C | | | PRESSURES APPEAR TO BE ASD BUT NOT STATED AS SUCH, | | | PLEASE CLARIFY. | | | | | | 5. S1.0, ROOF LIVE LOAD IS 20PSF; FBC B TABLE 1607.1 | | | REQUIRES 300 CONCENTRATED FOR "ALL ROOF SURFACES | | | SUBJECT TO MAINTENANCE WORKERS". RTU EQUIPMENT SHOWN. | | | EITHER REVISE DESIGN CRITERIA FOR THIS ROOF SECTION OR | | | PROVIDE RATIONALE FOR 20PSF LIVE LOAD. | | | | | | 6. IT APPEARS THAT NOT ALL LAP SPLICES WERE SPECIFIED | | | ON THE PLAN FOR THE FOUNDATION; REVISE PLAN OR ADVISE | | | WHERE THIS CAN BE LOCATED, FBC 107, FBC B CHAPTER 19. | | | | | | 7. AS THIS IS NEW CONSTRUCTION, APPLY FOR AN | | | ENGINEERING PERMIT; 561-494-1040. ENGINEERING | | | DEPARTMENT APPROVAL IS REQUIRED PRIOR TO PERMIT | | | ISSUANCE. CONTACT THEM DIRECTLY REGARDING REQUIREMENTS. | | | IF YOU HAVE ALREADY APPLIED, PROVIDE THE APPLICATION | | | NUMBER. I WAS UNABLE TO LOCATE AN ENGINEERING | | | APPLICATION FOR THIS PARCEL ID. | | | | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 8. A SEPARATE ROOF PERMIT IS REQUIRED. NO ROOF COVERING | | | PRODUCT APPROVAL WAS SUBMITTED. THIS MAY BE SUBMITTED | | | AT TIME OF ROOF PERMIT APPLICATION. | | | | | | FBC 1609, AT THIS TIME, APPLICANT MAY INDICATE WHICH | | | APPROVED ASSEMBLY IS PROPOSED. IF THIS IS DONE NOW | | | (ROOF PRODUCT APPROVAL SUBMITTED AND ASSEMBLY | | | SELECTED), THE ROOF SUB PERMIT WILL BE ISSUED AT TIME | | | OF SUB PERMIT APPLICATION WITHOUT ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | IF APPLICANT DOES NOT PROVIDE THIS INFORMATION AT THIS | | | TIME, THIS PERMIT WILL BE ISSUED WITH PROVISO THAT, AT | | | TIME OF ROOF SUB PERMIT APPLICATION, A PRODUCT APPROVAL | | | REVIEWED BY DESIGNER OF RECORD IS TO BE SUBMITTED AND | | | THE APPROVED ASSEMBLY IS TO BE SELECTED. A PLAN REVIEW | | | WILL BE REQUIRED AT THAT TIME. | | | | | | ********************************************** | | | INTERNAL USE ONLY | | | | | | 17060192 BUILDING DATA FOR C.O./REPORTING | | | | | | USC-404 318 ... - NEW: ATHLETIC/SOCIAL CLUBS | | | SQUARE FEET - 5090 | | | | | | CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B | | | UNITS: 1 | | | FLOORS: 2 | | | BEDROOMS: | | | ROOMS: | | | SQ FT LIVABLE: 5090 | | | SQ FT FOOTPRINT: 3330 | | | SQ FT ROOF: 5090 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 98 | | | PROP USE: CLUB/PRKG | | | SPRINKLER SYS? N | | | SPRK REQ'D? N | | | BATHRMS: | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED A2 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-09-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-09-05 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-09-05 |
Time |
12:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-06-29 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-06-29 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-29 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2017-06-29 09:06:09 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS: | | | | | | 1. SUBMIT PLAN WITH CORRECT ADDRESS. FBC 107.2.1 | | | 2. THIS PLAN INCLUDES THE SITE LIGHTING. PROVIDE NOTE | | | THAT STATES SITE LIGHTING WILL BE UNDER SEPARATE | | | PERMIT. FBC 105.3 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2017-10-05 |
|
|
Cont ID |
|
| Sent By |
squinone |
Date |
2017-10-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
squinone |
Date |
2017-10-05 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-10-05 15:13:45 | 1) NO CIVIL PLANS WERE INCLUDED WITH THIS SUBMITTAL. | | | CIVIL PLANS ARE UNDER REVIEW THROUGH ENGINEERING PLAN | | | REVIEW, E17060013. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2017-07-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-05 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-05 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2017-07-05 14:31:17 | AS THIS IS NEW CONSTRUCTION, APPLY FOR AN ENGINEERING | | | PERMIT; 561-494-1040. | | | | | | ENGINEERING DEPARTMENT APPROVAL IS REQUIRED PRIOR TO | | | PERMIT ISSUANCE. CONTACT THEM DIRECTLY REGARDING | | | REQUIREMENTS. IF YOU HAVE ALREADY APPLIED, PROVIDE THE | | | APPLICATION NUMBER. I WAS UNABLE TO LOCATE AN | | | ENGINEERING APPLICATION FOR THIS PARCEL ID. | | | | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-11-02 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-11-02 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-11-02 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2017-08-16 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-08-16 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-08-16 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2017-08-16 14:01:46 | 2201 NORTH AUSTRALIAN AVENUE - CLUBHOUSE (2191 NORTH | | | AUSTRALIAN AVE) | | | PERMIT #17060192 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PERMIT INDICATES THE ADDRESS OF THE CLUBHOUSE IS 2191 | | | NORTH AUSTRALIAN AVENUE; HOWEVER, THE PLANS INDICATE AN | | | ADDRESS OF 2201 NORTH AUSTRALIAN AVENUE. | | | | | | SHEET LS: | | | REPEAT COMMENT - NOTE #6 STATES, "AN NFPA 13 COMPLIANT | | | SPRINKLER SYSTEM IS REQUIRED FOR THIS STRUCTURE"; | | | HOWEVER, THE CLUBHOUSE SCOPE OF WORK STATES THIS IS A | | | NON-SPRINKLERED BUILDING. | | | | | | REPEAT COMMENT - PROVIDE A FURNITURE/EQUIPMENT PLAN | | | JUSTIFYING THE USAGE OF THE 15 AND 50 SQ.FT. PER PERSON | | | OCCUPANT LOAD FACTORS. | | | | | | REPEAT COMMENT - HOW IS THE CLUBHOUSE FIRE AND LIFE | | | SAFETY AFFECTED BY THE COVERED PATIO AND POOL AREA? NO | | | INFORMATION SUBMITTED. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-06-28 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-06-28 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-06-28 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2017-06-28 15:31:24 | 2201 NORTH AUSTRALIAN AVENUE - CLUBHOUSE | | | PERMIT #17060192 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET LS: | | | | | | PLAN SCALE IS INCORRECTLY INDICATED AS 1/4"=1'-0". | | | | | | NOTE #6 STATES, "AN NFPA 13 COMPLIANT SPRINKLER SYSTEM | | | IS REQUIRED FOR THIS STRUCTURE"; HOWEVER, THE CLUBHOUSE | | | SCOPE OF WORK STATES THIS IS A NON-SPRINKLERED | | | BUILDING. | | | | | | PROVIDE A FURNITURE/EQUIPMENT PLAN JUSTIFYING THE USAGE | | | OF THE 15 AND 50 SQ.FT. PER PERSON OCCUPANT LOAD | | | FACTORS. | | | | | | THE TWO NORTH ARROW COMPASSES ON THE PLAN CONFLICT WITH | | | EACHOTHER. | | | | | | HOW IS THE CLUBHOUSE FIRE AND LIFE SAFETY AFFECTED BY | | | THE COVERED PATIO AND POOL AREA? NO INFORMATION | | | SUBMITTED. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS | | | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A | | | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. | | | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF | | | OCCUPANTS PERMITTED FOR EACH ROOM. | | | | | | SHEET A-11: SEVERAL WALLS INDICATE A FIRE RESISTANCE | | | RATING; HOWEVER, ONLY DOOR #10 INDICATES IT HAS A FIRE | | | RATING. | | | | | | GENERAL: NO CIVIL PLANS SUBMITTED. | | | | | | GENERAL: PER NFPA 241 SECTION 8.7.2.3, WHERE | | | UNDERGROUND WATER MAINS AND HYDRANTS ARE TO BE | | | PROVIDED, THEY SHALL BE INSTALLED, TESTED, APPROVED, | | | AND IN SERVICE PRIOR TO VERTICAL CONSTRUCTION WORK. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-12-21 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-12-21 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-12-20 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2017-12-21 09:12:35 | IMPACT FEES ROUTED TO ACLANGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-11-03 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-11-03 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-10-19 |
Time |
10:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-10-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-11 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-07 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-07-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-05 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-05 |
Time |
13:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2017-12-21 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-12-21 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-12-21 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2017-12-21 13:36:29 | 12/21/17 | | | PALM BEACH COUNTY IMPACT FEES PAID. $527,017.05 | | | RECEIPT NO: 2017-1220-331 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2017-11-01 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-11-01 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-11-01 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2017-11-01 13:05:25 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | | IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-07-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-05 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-05 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2017-07-05 14:30:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED. | | | | | | THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING | | | THAT FEES DUE HAVE BEEN PAID ARE REQUIRED TO BE | | | SUBMITTED. THIS IS TO BE DONE AFTER REVIEWS HAVE PASSED | | | AND PLANS ARE STAMPED BY THE CITY, BUT BEFORE PERMIT | | | ISSUANCE. | | | | | | CONTACT 561-233-5025 FOR MORE INFORMATION. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-09-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-09-05 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-09-05 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-06-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-06-30 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-06-30 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2017-06-30 12:37:04 | 1ST REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION | | | CODES | | | PERMIT #17060192 | | | 6/30/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: THE NOTE AT RTU #1 TO SET THE O/A INTAKE | | | TO 140 CFMS IS INCORRECT AND IN CONFLICT WITH THE | | | VENTILATION CALCULATION TABLE WHICH IS SPECIFYING 426 | | | CFMS FOR THE RECREATION RM. PLEASE INCLUDE THE LOBBY IN | | | THE CALCULATIONS. | | | | | | 2) M-1: THE VENTILATION CALCULATION FOR THE GYM IS NOT | | | IN COMPLIANCE WITH TABLE 403.3 WHICH REQUIRES 0.30 CFMS | | | PER SF FOR A GYM, HOWEVER THE CLASSIFICAIONS FOR THIS | | | SPACE MAY BE CLOSER TO HEALTH CLUB/AEROBICS ROOMS WITH | | | REQUIRES AN OCCUPANT DENSITY CALCULATION OF 40 PERSONS | | | PER SF. OR 22 PERSONS LOAD IN THE 550 SF. THE CALC | | | WOULD THEN RESULT TO 22 PERSONS X 20 CFMS= 440 CFMS + | | | ,06 X550= 33 CFMS FOR A TOTAL OF 473 CFMS FOR THE | | | SPACE. PLEASE CORRECT ACCORDINGLY. | | | | | | 3) M-1: CLARIFY IF THE AC CLOSETS ARE BOTH OPEN PLENUM | | | CLOSETS AS SHOWN IN THE DETAIL ON M2, AND INDICATE WHAT | | | TYPE OF DOOR WILL ENCLOSE THE AHU #3 CLOSET- IT IS NOT | | | SHOWN ON THE ARCHITECTURAL PLANS. DOOR #5 WHICH | | | ENCLOSES THE AHU #2 CLOSET IS A WOOD DOOR WHICH IS | | | COMPLIANT IF THE RETURN IS DUCTED DIRECTLY TO THE AHU. | | | OTHERWISE A NON-COMBUSTIBLE DOOR IS REQUIRED PER | | | SECTIONS | | | SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION, AND | | | SECTION 602 FBC-14 MECHANICAL. | | | | | | 4) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR THE | | | RTU AND CONDENSER INSTALLATIONS- SEE SECTION 301.15 | | | FBC-14 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING. | | | | | | 5) M-2: CORRECT NOTE #3 AT THE AHU MOUNTING DETAIL | | | WHICH IS REFERENCING A RESIDIENTIAL CODE SECTION, AND | | | SEE SECTION C403.2.7.3.3 WHICIH REQUIRES A MINIMUM 4" | | | CLEARANCE SPACE AROUND THE AIR HANDLER. | | | | | | 6) ENERGYGAUGE COMPLIANCE SUBMITTAL: A) THE | | | OWNER/AGENT'S SIGNATURE IS MISSING- PAGE 3. B) THE | | | DESIGNER OR ENGINEER'S MANDATORY REQUIREMENTS CHECKLIST | | | NOT COMPLETED- PAGE 8. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-11-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-03 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-01 |
Time |
17:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-09-06 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-09-06 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-06 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2017-09-06 16:15:57 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | PREVIOUS COMMENT HAS NOT COMPLIED 3. TOILET PAPER | | | DISPERSER SHALL COMPLY WITH FBC ACC 604.7 DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE | | | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 | | | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND | | | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL | | | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES | | | NOT ALLOW CONTINUOUS PAPER FLOW. | | | | | | NEW COMMENTS: | | | | | | 1. THE WATER FOUNTAIN IS REQUIRED TO COMPLY WITH FBC | | | ACC 307 PROTRUDING OBJECTS | | | | | | 2. GRAB BARS SHALL BE MEASURED FROM FINISH FLOOR TO THE | | | TOP OF THE GRIPPING SURFACE, PER FBC ACC 609.4 | | | | | | 3.SHOW CLEAR FLOOR SPACE FOR SINK IN COFFEE ROOM. PER | | | FBC ACC 606.2 | | | | | | 4. SHT. A-3.1 SHOWS TOTAL ROOF SQFT OF 1526FT SHT. P-3 | | | SHOWS 1470SQFT PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-07-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-07-03 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-06-30 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2017-07-03 13:13:58 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE INDICATE ON PLAN THAT THIS SHALL COMPLY WITH | | | FLORIDA BUILDING CODE, ACCESSIBILITY, 5TH EDITION | | | (2014) | | | | | | 2.THE GRAB BARS SHALL COMPLY WITH FBC ACC 604.5.1 SIDE | | | WALL. | | | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) | | | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM | | | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM | | | FROM THE REAR WALL. | | | 604.5.2 REAR WALL. | | | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG | | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 | | | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. | | | 609.4 POSITION OF GRAB BARS. | | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | | THE GRIPPING SURFACE | | | PLEASE CLARIFY THE FIGURE ON THE PLAN IS UN CLEAR. | | | | | | 3. TOILET PAPER DISPERSER SHALL COMPLY WITH FBC ACC | | | 604.7 DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE | | | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 | | | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND | | | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL | | | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES | | | NOT ALLOW CONTINUOUS PAPER FLOW. | | | | | | 4. ON THE SANITARY RISER DIAGRAM THE FLOOR DRAINS ARE | | | NOT VENTED PROPERLY THEY SHOULD CONNECT TO A VENTED | | | BRANCH DRAIN NOT THE BUILDING DRAIN. PER FBC PL 901.2.1 | | | | | | 5. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW | | | PLEASE PROVIDE A NOTE ON THE PLAN. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 6. PROVIDE STORM RISER DIAGRAM. PER WPB AMEN TO FBC | | | 107.3.5.1.3(13) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2017-09-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-13 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-13 |
Time |
17:37 |
Sent To |
|
|
| Notes |
| 2017-09-13 17:39:34 | NO ROOF PRODUCT APPROVAL SUBMITTED | | | A SEPARATE ROOF PERMIT IS REQUIRED. APPLICANT IS TO | | | SUBMIT PRODUCT APPROVAL, REVIEWED BY DESIGNER OF | | | RECORD, AND ENGINEERING IF REQUIRED. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-09-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2017-09-13 |
Time |
15:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-06-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2017-06-23 |
Time |
15:01 |
Sent To |
|
|
| Notes |
|
|