Plan Review Details - Permit 17060191
Plan Review Stops For Permit 17060191
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-11-03 Cont ID  
Sent By aclange Date 2017-11-03 Time 11:10 Rev Time 0.00
Received By aclange Date 2017-11-03 Time 11:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-18 Cont ID  
Sent By shill Date 2017-08-18 Time 08:15 Rev Time 0.00
Received By shill Date 2017-08-14 Time 17:07 Sent To  
Notes
2017-08-18 08:15:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 17060191 3 STORY APARTMENT BUILDING
 17060189 6 STORY APARTMENT BUILDING
 17060192 CLUBHOUSE (BLDG F)
  
 COMMENTS FROM PREVIOUS LIST:
  
 1-2. OK
  
 3. SEE COMMENT FROM PREVIOUS LIST. 2ND REVIEW, PLANS
 HAVE BEEN REVISED TO STATE "THIS PLANS COMPLY WITH
 FLORIDA ACCESSIBILITY CODE(1ST LEVEL) & FAIR HOUSING
 ACT (ENTIRE BUILDING)". APPLICANT MAY EXCEED MINIMUM
 CODE BUT, IF PLAN STATES THAT INTENT IS TO COMPLY WITH
 A MORE STRINGENT REQUIREMENT, DESIGN MUST COMPLY.
  
 MINIMUM REQUIREMENT IS FAIR HOUSING COMPLIANCE ON THE
 GROUND FLOOR, NO ADA COMPLIANCE REQUIRED.
  
 SINCE THE PLAN STATES THAT THE INTENT IS FOR THE DESIGN
 TO COMPLY WITH ADA ON THE FIRST FLOOR, NOTE THAT THE
 FOLLOWING ITEMS DO NOT COMPLY WITH FLORIDA
 ACCESSIBILITY: BATHROOM DOOR LACKS 18" MANEUVERING
 CLEARANCE PULL SIDE FBC A TABLE 404.2.4; THE SLIDING
 GLASS DOOR TRACK DOES NOT COMPLY WITH ADA ACCESSIBLE
 ROUTE. OTHER ITEMS, SUCH AS REACH RANGES, NOT REVIEWED
 AS DESIGN INTENT IS NOT CLEAR.
  
 YOU MAY FIND THE FOLLOWING WEBSITE HELPFUL:
  
 HTTPS://PORTAL.HUD.GOV/HUDPORTAL/HUD?SRC=/PROGRAM_OFFIC
 ES/FAIR_HOUSING_EQUAL_OPP/DISABILITIES/ACCESSIBILITYR
  
 ADA IS GENERALLY APPLICABLE TO PLACES OF PUBLIC
 ACCOMODATION, NOT LONG TERM HOUSING. IT IS RECOMMENDED
 TO REVISE PLAN TO NOTE FAIR HOUSING COMPLIANCE, FIRST
 FLOOR, AND REMOVE ADA REFERENCES. EVEN FAIR HOUSING
 REFERENCE FOR FLOORS OTHER THAN THE GROUND FLOOR IS
 CONFUSING AS THERE IS NO ELEVATOR. IT IS RECOMMENDED TO
 REMOVE THE REFERENCE REGARDING FAIR HOUSING COMPLIANCE
 ON FLOORS ABOVE THE GROUND FLOOR.
  
 4. OK
  
 5. FBC B 1803, PROVIDE THE GEOTECHNICAL INVESTIGATION
 REPORT (S1.0 ARDAMAN & ASSOC 2/10/17). THIS IS AREA IS
 KNOWN TO HAVE THE POTENTIAL OF POOR SOILS.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THE SOILS ARE
 WITH THE FULL SET. EACH PERMIT REQUIRES DOCUMENTS TO
 SHOW COMPLIANCE FOR THE PERMIT; EACH PERMIT IS
 TRAVELLING SEPARATELY. UNTIL ONE PERMIT IS ISSUED, THE
 SOILS REPORT WHICH WAS SUBMITTED WITH ONE OF THE TWO
 OTHER PERMITS IS NOT A PART OF THE PUBLIC RECORD.
 PLEASE PROVIDE THREE COPIES OF THE SOILS REPORT WITH
 EACH PERMIT APPLICATION. ONE PERMIT APPLICATION SHOULD
 INCLUDE ORIGINAL SIGNED AND SEALED SOILS REPORTS; THE
 SOILS REPORTS SUBMITTED WITH THE OTHER TWO ASSOCIATED
 PERMITS MAY BE PHOTOCOPIES.
  
 I ATTEMPTED TO LOCATE THE SOILS REPORT WHICH WAS
 SUBMITTED WITH ANOTHER PERMIT APPLICATION. IT APPEARS
 THAT THE OTHER APPLICATIONS HAVE BEEN CHECKED OUT FOR
 REVIEW BY ANOTHER REVIEWER, SO REVIEW OF THE FOUNDATION
 AND THE SOILS REPORT IS NOT POSSIBLE AT THIS TIME.
 STRUCTURAL REVIEW INCLUDES VERIFICATION OF THE SOILS
 ENGINEER'S RECOMMENDATIONS.
  
 6. OK
  
 7. CLARIFY ZONE 3 DIMENSION AND DIMENSION OF OVERHANG
 OF ROOF OVER THE STAIR, FBC 107 (NORTH AND SOUTH
 OVERHANGS).
  
 2ND REVIEW, RESPONSE LETTER REFERS TO SHEET A-1.5.
 PLEASE SEE A-1.5 AND A-3.3. THE STAIRS HAVE A ROOF WITH
 NO PARAPET; OVERHANG PRESSURES APPEAR APPLICABLE FOR A
 PORTION OF THE STAIR ROOF, BUT IT APPEARS THAT A
 PORTION OF ZONE 3 ROOF IS NOT OVERHANG. IF ANY PORTION
 OF ZONE 3 IS NOT OVERHANG, THEN ZONE 3 ROOF DESIGN
 PRESSURE SPECIFIED ON SHEET S1.0 (-77.6PSF, SAME AS
 ZONE 2 PRESSURES) APPEARS TOO LOW FOR THE STAIR ROOF
 (OK FOR APARTMENT ROOF). PLEASE REVISE PLAN TO CLARIFY.
 IF YOU WISH TO DISCUSS, OR DISAGREE, PLEASE CONTACT ME.
  
 8-10. OK
  
 11. A 2 HOUR PARTITION IS SHOWN BETWEEN UNITS, BUT FIRE
 RESISTANCE OF THE WALL BETWEEN THE UNITS ON THE
 BALCONIES AND PORCHES IS NOT CLEAR, REVISE PLAN TO
 CLARIFY, FBC 107. PLEASE ALSO REVISE LANGUAGE FROM
 "SEPARATION" TO "PARTITION" (FBC B 708).
  
 RESPONSE STATES THAT SHEETS WERE REVISED, BUT PLAN DOES
 NOT SHOW A RATED WALL BETWEEN THE UNIT BALCONIES. IF
 DOR DOES NOT AGREE WITH COMMENT, PLEASE CONTACT ME TO
 DISCUSS PRIOR TO RESUBMITTAL. IF DOR AGREES, PLEASE
 REVISE THE EXTERIOR WALL BETWEEN THE UNITS ON THE
 BALCONIES TO INDICATE MINIMUM 1 HOUR; THIS CAN BE A
 NOTE, NO DETAIL REQUIRED. THE UL WALL DETAIL IS NOT
 APPLICABLE TO THE BALCONY LOCATION AS THE UL WALL
 DETAIL HAS AN INTERIOR AND EXTERIOR SIDE. BALCONY WALL
 HAS TWO EXTERIOR SIDES.
  
 12. FBC B 1503.4, FBC B 1503.4.1, FBC P 1106.4, SHEET
 A-1.5, IT DOES NOT APPEAR THAT 50% OF THE STAIR WALL
 WAS INCLUDED IN THE CALCULATIONS; REVISE PLAN TO
 INCLUDE OR CLARIFY. ALSO PROVIDE PARAPET CALCS; IT IS
 NOT CLEAR IF THE HIGHER WALL OVER THE BALCONY AREAS WAS
 INCLUDED IN PARAPET CALCS.
  
 13. REGARDING THE ENERGY CALCS: PLEASE CORRECT COUNTY
 (STATES BROWARD) IF ENERGY CALCS ARE REVISED DUE TO
 ANOTHER COMMENTS; OTHERWISE ENERGY CALCS APPEAR
 COMPLIANT.
  
 14. OK
  
 15. FBC B 1207.2, 1207.3, PROVIDE TEST REPORTS FOR THE
 FLOORING UNDERLAYMENT (STC/IIC). REVISE PLAN TO INCLUDE
 REQUIREMENT FOR ACOUSTIC INSULATION. NOTE THAT SPEC
 SHEETS ARE NOT ACCEPTABLE; ACTUAL TEST REPORTS ARE
 REVIEWED. IT IS LIKELY THAT THE MANUFACTURER WILL BE
 REQUIRED TO DO A COMPARATIVE ANALYSIS AS IT IS UNLIKELY
 THAT THE UNDERLAYMENT WAS TESTED WITH HOLLOW CORE (MOST
 TESTS ARE DONE WITH A CONCRETE SLAB).
  
 2ND REVIEW, PLAN HAS BEEN REVISED IN AN ACCEPTABLE
 MANNER. PLEASE ALSO REVISE COVER PAGE "TO BE SUBMITTED
 AT A LATER TIME OR UNDER SEPARATE PERMITS" - PLEASE ADD
 "FLOORING UNDERLAYMENT STC/IIC TEST REPORTS" TO THIS
 LIST. SEE ALSO ADVISORY UNDER ITEM #16.
  
 HOWEVER, RESPONSE LETTER STILL REFERS TO "CSM". THIS IS
 A BRAND, NO TEST REPORTS HAVE BEEN PROVIDED. IT IS NOT
 CLEAR IF THIS PRODUCT CAN BE USED.
  
 16. FBC 720.2, PROVIDE A COPY OF THE FLAME SPREAD TEST
 FOR THE PROPOSED FLOORING UNDERLAYMENT.
  
 2ND REVIEW, RESPONSE IS THAT CSM PRODUCT WILL BE
 PROVIDED AT A LATER DATE. THIS IS ACCEPTABLE; PLEASE
 REVISE THE FRONT PAGE TO ADD "FLOORING UNDERLAYMENT
 FLAME SPREAD REPORT". HOWEVER:
  
 HOWEVER, RESPONSE LETTER STILL REFERS TO "CSM". THIS IS
 A BRAND, NO TEST REPORTS HAVE BEEN PROVIDED. IT IS NOT
 CLEAR IF THIS PRODUCT CAN BE USED.
  
 ***PLEASE BE ADVISED THAT, TO MY KNOWLEDGE, ONLY ONE
 PRODUCT HAS THE THREE TEST REPORTS REQUIRED (STC, IIC,
 FLAME SPREAD) - MOST PRODUCTS DO NOT HAVE A FLAME
 SPREAD TEST WITHOUT TILE ON THE FLAME SIDE IN THE
 STEINER TUNNEL - THIS IS NOT ACCEPTABLE FOR A LVT
 INSTALLATION. MANY PRODUCTS DO NOT HAVE AN STC/IIC
 WITHOUT DROPPED GYPSUM CEILING, ALSO NOT ACCEPTABLE***
  
 I AM CONCERNED AS THIS APPLICATION IS "TBD" (NO
 CONTRACTOR) AND ALSO IS PRIVATE PROVIDER. A C.O. WILL
 NOT BE ISSUED UNLESS THE THREE TEST REPORTS FOR THE
 FLOORING UNDERLAYMENT HAVE BEEN PROVIDED AND THE JOB
 INSPECTOR HAS CONFIRMED THAT THE CORRECT UNDERLAYMENT
 (SUBMITTED AND REVIEWED) HAS BEEN INSTALLED.
  
 HOW DOES APPLICANT (ARCHITECT, DEVELOPER, OR OWNER)
 PROPOSE TO CONVEY THIS INFORMATION TO THE FUTURE
 CONTRACTOR? THIS IS A RESTRICTIVE REQUIREMENT WHICH IS
 NOT ENFORCED IN ALL JURISDICTIONS, SO CONTRACTOR MAY BE
 UNFAMILIAR WITH THE REQUIREMENT. WE HAVE FOUND THAT
 MOST PRODUCTS DO NOT HAVE THE THREE TEST REPORTS WHICH
 DEMONSTRATE CODE COMPLIANCE.
  
 IS IT POSSIBLE TO HAVE APPLICANT'S PRODUCT OF CHOICE'S
 TECHNICAL REPRESENTATIVE CONTACT ME DIRECTLY SO WE CAN
 WORK THROUGH THIS TO AVOID POTENTIAL FUTURE ISSUES?
  
 17. OK
  
 18. THIS PERMIT WILL BE ISSUED WITH PROVISO, A SEPARATE
 ROOF PERMIT IS REQUIRED. A ROOF PRODUCT APPROVAL WAS
 SUBMITTED, FIBERTITE SINGLE PLY ROOF SYSTEMS OVER
 LIGHTWEIGHT CONCRETE DECKS (NOA 15-1026.04).
  
 AT TIME OF ROOF SUB PERMIT APPLICATION, THE APPROVED
 ASSEMBLY IS TO BE SELECTED. A PLAN REVIEW WILL BE
 REQUIRED AT THAT TIME.
  
 19. FS 553.80, A 4X FEE WILL BE CHARGED (AS REQUIRED BY
 LAW) IF COMMENTS ARE NOT ADDRESSED A THIRD TIME (#7,
 #11).
  
  
  
 ************************************
 INTERNAL USE ONLY
 17060191 BUILDING DATA FOR C.O./REPORTING
  
 USC-404 105 - NEW: RES FIVE OR MORE UNITS
 SQUARE FEET - 11429
  
 CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B
 UNITS: 12
 FLOORS: 3
 BEDROOMS: 24
 ROOMS: 48
 SQ FT LIVABLE: 11429
 SQ FT FOOTPRINT: 3452
 SQ FT ROOF: 3452
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 58
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 12
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By shill Date 2017-06-29 Time 17:45 Rev Time 0.00
Received By shill Date 2017-06-29 Time 08:21 Sent To  
Notes
2017-06-29 16:59:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 17060191 3 STORY APARTMENT BUILDING
 17060189 6 STORY APARTMENT BUILDING
 17060192 CLUBHOUSE (BLDG F)
  
 1. ALL PAGES HAVE AN INCORRECT ADDRESS AND NOT ALL ARE
 CONSISTENT WITH EACH OTHER (DIFFERENT INCORRECT
 ADDRESSES). FBC 107, PLEASE CORRECT THE ADDRESS ON EACH
 PAGE.
  
 2. FS471.0195, THE DBPR RECORD FOR THE FOLLOWING
 ENGINEER(S) DO NOT REFLECT THAT THE ADVANCED FLORIDA
 BUILDING CODE COURSE HAS BEEN COMPLETED. EMAIL THE
 CERTIFICATE TO FBPE AND REQUEST THAT THE DBPR RECORD BE
 UPDATED. NOTE THAT IT IS POSSIBLE THAT THE COURSE WAS
 COMPLETED AND THE WEBSITE IS NOT CURRENT.
  
 SANTIAGO ARANEGUI, PE
 JOE SPASOVSKI, PE
  
 PERMIT ISSUANCE WILL NOT BE DELAYED DUE TO THIS
 COMMENT. HOWEVER, FLORIDA STATUTE REQUIRES THAT:
 LOCAL JURISDICTIONS SHALL BE RESPONSIBLE FOR NOTIFYING
 THE BOARD WHEN DESIGN DOCUMENTS ARE SUBMITTED FOR
 BUILDING CONSTRUCTION PERMITS BY PERSONS WHO ARE NOT IN
 COMPLIANCE WITH THIS SECTION.
  
 3. SHEET A1.1 (AND OTHER PAGES), FBC A FAIR HOUSING,
 REVISE PLAN TO SHOW COMPLIANCE WITH REQUIREMENTS. THERE
 IS A GENERAL NOTE STATING "THIS PLANS COMPLY WITH THE
 FLORIDA ACCESSIBILITY CODE & FAIR HOUSING ACT" (SIC).
  
 IT IS NOT CLEAR WHAT THAT MEANS. THE FBC IS A MINIMUM
 CODE, DESIGNER/OWNER/APPLICANT CAN ELECT TO EXCEED THE
 MINIMUM REQUIREMENTS OF THE FLORIDA BUILDING CODE. WHEN
 DESIGNER DECLARES THAT HE/SHE IS EXCEEDING CODE VIA THE
 PERMIT DOCUMENTS, THE DESIGN CRITERIA DECLARED BY THE
 DESIGNER IS ENFORCED.
  
 DOES APPLICANT WISH FOR FLORIDA ACCESSIBILITY CODE TO
 BE APPLIED TO THIS PERMIT? NOTE THAT VERTICAL
 ACCESSIBILITY WAS NOT PROVIDED, PLAN DOES NOT COMPLY
 WITH MANEUVERING CLEARANCE REQUIREMENTS. THESE ITEMS
 ARE NOT REQUIRED FOR FAIR HOUSING, BUT ARE REQUIRED FOR
 COMPLIANCE WITH FBC ACCESSIBLIITY.
  
 EITHER REVISE THE STATEMENT, OR REVISE THE PLAN TO SHOW
 COMPLIANCE WITH ACCESSIBILITY.
  
 4. REVISE THE PLAN TO SHOW FAIR HOUSING COMPLIANCE. FOR
 INSTANCE, BATHROOMS ARE NOT IDENTIFIED AS SPECIFICATION
 A OR SPECIFICATION B, CLEAR FLOOR SPACE AND MANEUVERING
 CLEARANCE NOT MARKED, GRAB BAR BACKING DETAIL NOT
 PROVIDED.
  
 5. FBC B 1803, PROVIDE THE GEOTECHNICAL INVESTIGATION
 REPORT. THIS IS AREA IS KNOWN TO HAVE THE POTENTIAL OF
 POOR SOILS.
  
 6. S1.0, DESIGN PRESSURES DO NOT STATE ULTIMATE OR ASD
 FOR COMPONENT AND CLADDING PRESSURES, FBC 107. WIND
 DESIGN CRITERIA SHOULD INCLUDE BOTH (SEE FBC B
 1603.1.4), ONLY ASD WIND SPEED WAS INCLUDED, C&C
 PRESSURES APPEAR TO BE ASD BUT NOT STATED AS SUCH,
 PLEASE CLARIFY.
  
 7. CLARIFY ZONE 3 DIMENSION AND DIMENSION OF OVERHANG
 OF ROOF OVER THE STAIR, FBC 107 (NORTH AND SOUTH
 OVERHANGS).
  
 8. S1.0, ROOF LIVE LOAD IS 20PSF; FBC B TABLE 1607.1
 REQUIRES 300 CONCENTRATED FOR "ALL ROOF SURFACES
 SUBJECT TO MAINTENANCE WORKERS". RTU EQUIPMENT SHOWN.
 EITHER REVISE DESIGN CRITERIA FOR THIS ROOF SECTION OR
 PROVIDE RATIONALE FOR 20PSF LIVE LOAD.
  
 9. IT APPEARS THAT NOT ALL LAP SPLICES WERE SPECIFIED
 ON THE PLAN FOR THE FOUNDATION; REVISE PLAN OR ADVISE
 WHERE THIS CAN BE LOCATED, FBC 107, FBC B CHAPTER 19.
  
 10. FBC B 420.3, PROVIDE A DETAIL SHOWING COMPLIANCE
 WITH THE 1 HOUR SEPARATION REQUIREMENT FOR THE
 FLOOR/CEILING ASSEMBLIES BETWEEN UNITS. REVISE THE PLAN
 TO SHOW THE 1 HOUR (MINIMUM) FLOOR/CEILING ASSEMBLY.
  
 11. A 2 HOUR PARTITION IS SHOWN BETWEEN UNITS, BUT FIRE
 RESISTANCE OF THE WALL BETWEEN THE UNITS ON THE
 BALCONIES AND PORCHES IS NOT CLEAR, REVISE PLAN TO
 CLARIFY, FBC 107. PLEASE ALSO REVISE LANGUAGE FROM
 "SEPARATION" TO "PARTITION" (FBC B 708).
  
 12. DETAIL 1-A1.6 REFERS TO PLUMBING DRAWINGS FOR DRAIN
 SIZE, UNABLE TO LOCATE. REVISE PLAN TO INCLUDE ROOF
 DRAIN INFORMATION (SIZES, CALCULATIONS), FBC B 1503.4,
 AND OVERFLOW SCUPPER SIZING INFORMATION FBC B 1503.4.1.
  
 13. ENERGY CALCS REQUIRED, FBC EC R103.
  
 14. A1.1 NOTE 3 STATES THAT NFPA 13 SPRINKLERS WILL BE
 INSTALLED, BUT FS2 PROPOSES NFPA13R, PLEASE CORRELATE.
  
 15. FBC B 1207.2, 1207.3, PROVIDE TEST REPORTS FOR THE
 FLOORING UNDERLAYMENT (STC/IIC). REVISE PLAN TO INCLUDE
 REQUIREMENT FOR ACOUSTIC INSULATION. NOTE THAT SPEC
 SHEETS ARE NOT ACCEPTABLE; ACTUAL TEST REPORTS ARE
 REVIEWED. IT IS LIKELY THAT THE MANUFACTURER WILL BE
 REQUIRED TO DO A COMPARATIVE ANALYSIS AS IT IS UNLIKELY
 THAT THE UNDERLAYMENT WAS TESTED WITH HOLLOW CORE (MOST
 TESTS ARE DONE WITH A CONCRETE SLAB).
  
 CSM CRACK SUPPRESSION & SOUND CONTROL SPEC SHEET WAS
 PROVIDED. PLEASE SEND TEST REPORTS VIA EMAIL FOR
 PRELIMINARY REVIEW. WHEN REVISING PLAN TO INCLUDE
 UNDERLAYMENT REQUIREMENT, IT IS ADVISED THAT YOU DO NOT
 SPEC A PRODUCT.
  
 16. FBC 720.2, PROVIDE A COPY OF THE FLAME SPREAD TEST
 FOR THE PROPOSED FLOORING UNDERLAYMENT.
  
 17. AS THIS IS NEW CONSTRUCTION, APPLY FOR AN
 ENGINEERING PERMIT; 561-494-1040. ENGINEERING
 DEPARTMENT APPROVAL IS REQUIRED PRIOR TO PERMIT
 ISSUANCE. CONTACT THEM DIRECTLY REGARDING REQUIREMENTS.
 IF YOU HAVE ALREADY APPLIED, PROVIDE THE APPLICATION
 NUMBER. I WAS UNABLE TO LOCATE AN ENGINEERING
 APPLICATION FOR THIS PARCEL ID.
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 18. A SEPARATE ROOF PERMIT IS REQUIRED. A ROOF PRODUCT
 APPROVAL WAS SUBMITTED, FIBERTITE SINGLE PLY ROOF
 SYSTEMS OVER LIGHTWEIGHT CONCRETE DECKS (NOA
 15-1026.04).
  
 FBC 1609, AT THIS TIME, APPLICANT MAY INDICATE WHICH
 APPROVED ASSEMBLY IS PROPOSED. IF THIS IS DONE NOW, THE
 ROOF SUB PERMIT WILL BE ISSUED WITHOUT ANY OTHER
 INFORMATION REQUIRED.
  
 IF APPLICANT DOES NOT PROVIDE THIS INFORMATION AT THIS
 TIME, THIS PERMIT WILL BE ISSUED WITH PROVISO THAT, AT
 TIME OF ROOF SUB PERMIT APPLICATION, THE APPROVED
 ASSEMBLY IS TO BE SELECTED. A PLAN REVIEW WILL BE
 REQUIRED AT THAT TIME.
  
 ************************************
 INTERNAL USE ONLY
 17060191 BUILDING DATA FOR C.O./REPORTING
  
 USC-404 105 - NEW: RES FIVE OR MORE UNITS
 SQUARE FEET - 11429
  
 CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B
 UNITS: 12
 FLOORS: 3
 BEDROOMS: 24
 ROOMS: 48
 SQ FT LIVABLE: 11429
 SQ FT FOOTPRINT: 3452
 SQ FT ROOF: 3452
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 58
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-05 Cont ID  
Sent By jpearson Date 2017-09-05 Time 13:41 Rev Time 0.00
Received By jpearson Date 2017-09-05 Time 13:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By jpearson Date 2017-06-29 Time 09:57 Rev Time 0.00
Received By jpearson Date 2017-06-29 Time 09:57 Sent To  
Notes
2017-06-29 10:00:22CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SUBMIT PLANS WITH CORRECT ADDRESS. FBC 107.2.1
 2. PROVIDE LOAD CALCULATION FOR ENTIRE BUILDING TO
 DETERMINE MAIN SERVICE IS ADEQUATELY SIZED. NEC 230.79
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2017-10-05 Cont ID  
Sent By squinone Date 2017-10-05 Time   Rev Time 0.00
Received By squinone Date 2017-10-05 Time   Sent To  
Notes
2017-10-05 15:11:511) NO CIVIL PLANS WERE INCLUDED WITH THIS SUBMITTAL.
 CIVIL PLANS ARE UNDER REVIEW THROUGH ENGINEERING PLAN
 REVIEW, E17060013.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By shill Date 2017-06-29 Time 14:03 Rev Time 0.00
Received By shill Date 2017-06-29 Time 14:03 Sent To  
Notes
2017-06-29 14:03:50AS THIS IS NEW CONSTRUCTION, APPLY FOR AN ENGINEERING
 PERMIT; 561-494-1040.
  
 ENGINEERING DEPARTMENT APPROVAL IS REQUIRED PRIOR TO
 PERMIT ISSUANCE. CONTACT THEM DIRECTLY REGARDING
 REQUIREMENTS. IF YOU HAVE ALREADY APPLIED, PROVIDE THE
 APPLICATION NUMBER. I WAS UNABLE TO LOCATE AN
 ENGINEERING APPLICATION FOR THIS PARCEL ID.
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-18 Cont ID  
Sent By wjolin Date 2017-08-18 Time 09:58 Rev Time 0.00
Received By wjolin Date 2017-08-18 Time 09:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-21 Cont ID  
Sent By wjolin Date 2017-06-21 Time 11:57 Rev Time 0.00
Received By wjolin Date 2017-06-21 Time 11:21 Sent To  
Notes
2017-06-21 11:57:172171 NORTH AUSTRALIAN AVENUE - 3 STORY APARTMENTS
 PERMIT #17060191
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO CIVIL PLANS SUBMITTED.
  
 PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER
 MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE
 INSTALLED, TESTED, APPROVED, AND IN SERVICE PRIOR TO
 VERTICAL CONSTRUCTION WORK.
  
 WILL ANY CONSTRUCTION TRAILERS BE LOCATED ON SITE? THE
 CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION TRAILERS
 LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO "SINGLE
 WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC SPRINKLER
 SYSTEM OR COMPLY WITH THE SEPARATION REQUIREMENTS OF
 NFPA 241. TEMPORARY CONSTRUCTION TRAILERS OR MODULAR
 BUILDINGS WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE
 FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-12-21 Cont ID  
Sent By aclange Date 2017-12-21 Time 10:13 Rev Time 0.00
Received By aclange Date 2017-12-20 Time 09:10 Sent To  
Notes
2017-12-21 09:10:53IMPACT FEES ROUTED TO ACLANGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-03 Cont ID  
Sent By aclange Date 2017-11-03 Time 11:10 Rev Time 0.00
Received By aclange Date 2017-10-19 Time 10:41 Sent To  
Notes
2017-10-26 10:42:04C29
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-11 Cont ID  
Sent By shill Date 2017-10-11 Time 06:26 Rev Time 0.00
Received By shill Date 2017-08-07 Time 15:36 Sent To  
Notes
2017-08-07 15:36:55C29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-06 Cont ID  
Sent By gjohnson Date 2017-07-06 Time 12:20 Rev Time 0.00
Received By gjohnson Date 2017-06-05 Time 13:43 Sent To  
Notes
2017-06-06 13:43:43C04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-12-21 Cont ID  
Sent By aclange Date 2017-12-21 Time 10:13 Rev Time 0.00
Received By aclange Date 2017-12-21 Time 09:59 Sent To  
Notes
2017-12-21 10:02:32IMPACT FEES PAID.
 RECEIPT NO: 2017-1220-331
 DATE: 12/20/17
 $527,017.05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-11-03 Cont ID  
Sent By aclange Date 2017-11-03 Time 11:10 Rev Time 0.00
Received By aclange Date 2017-11-03 Time 11:10 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By shill Date 2017-06-29 Time 09:48 Rev Time 0.00
Received By shill Date 2017-06-29 Time 09:48 Sent To  
Notes
2017-06-29 09:50:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
  
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE HAVE BEEN PAID ARE REQUIRED TO BE
 SUBMITTED. THIS IS TO BE DONE AFTER REVIEWS HAVE PASSED
 AND PLANS ARE STAMPED BY THE CITY, BUT BEFORE PERMIT
 ISSUANCE.
  
 CONTACT 561-233-5025 FOR MORE INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-09-05 Cont ID  
Sent By ccole Date 2017-09-05 Time 16:38 Rev Time 0.00
Received By ccole Date 2017-09-05 Time 15:46 Sent To  
Notes
2017-12-13 08:38:58MECHANICAL PROVISO:
  
 BLOWER DOOR TESTING AND REPORT REQUIRED.
  
 CCOLE- 9/7/17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-30 Cont ID  
Sent By ccole Date 2017-06-30 Time 15:15 Rev Time 0.00
Received By ccole Date 2017-06-30 Time 14:08 Sent To  
Notes
2017-06-30 15:47:291ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 PERMIT #17060191
 6/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 APARTMENTS IN COMPLIANCE WITH TABLE 403.3 OR TABLE 6-1
 ASHRAE 62.1. INDICATE THE REQUIRED AND PROVIDE
 VENTILATION RATES.
  
 2) THE LOUVERED AC CLOSETS DOORS SHALL BE
 NON-COMBUSTIBLE PER SECTION R403.2.2 FBC-14 ENERGY
 CONSERVATION. THE DOOR SCHEDULE ON SHEET A-7.1
 INDICATES WOOD DOORS.
  
 3) THE ENERGYGAUGE FORM R405-2014 IS SPECIFYING A WORST
 CASE METHOD. PLEASE SEE SECTION R405.4.2 EXCEPTION:
 MULTIPLE ORIENTATIONS. WHEN AN OTHERWISE IDENTICAL
 BUILDING MODEL IS OFFERED IN MULTIPLE ORIENTATIONS,
 COMPLIANCE FOR ANY ORIENTATION SHALL BE PERMITTED BY
 DOCUMENTING THAT THE BUILDING MEETS THE PERFORMANCE
 REQUIREMENTS IN EACH OF THE FOUR CARDINAL (NORTH, EAST,
 SOUTH AND WEST) ORIENTATIONS. PLEASE PROVIDE THE
 DOCUMENTATION INCLUDING THE MANUAL J WORKSHEETS TO
 VALIDATE THE WORST CASE METHOD.
  
 4) PLEASE VERIFY WITH MEASUREMENTS OR NOTES ON THE
 PLANS THAT THE DRYER AND BATH EXHAUST OUTLETS ARE NOT
 WITHIN THE REQUIREDE 3' CLEARANCE DISTANCE TO THE
 WINDOW OPENINGS- SECTION 501.3.1 (ITEM #3).
  
 5) SHEET M-3: CONTRARY TO THE NOTE ON THE ROOF PLAN
 THERE ARE NO STRUCTURAL DETAILS FOR MOUNTING THE AC
 STANDS AND CONDENSER TO THE ROOF STRUCTURE. PLEASE
 PROVIDE THE WIND LOAD DESIGN CRITERIA AND STRUCTURAL
 DETAILS PER SECTION 301.15 FBC-14 MECHANICAL.
 ADDITIONALLY, THE ENGINEER OF RECORD SHALL CIRCLE,
 HIGHLIGHT, OR OTHERWISE MARKUP THE AC STAND NOA TO SHOW
 THE APPLICABLE INSTALLATION DETAILS. PLEASE INDICATE
 THE STAND CONFIGURATION, STAND ANCHORING TO THE ROOF,
 AND CONDENSER ANCHORING TO THE STAND.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-10-30 Cont ID  
Sent By gjohnson Date 2017-10-30 Time 17:17 Rev Time 0.00
Received By gjohnson Date 2017-10-30 Time 15:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-09-05 Cont ID  
Sent By gjohnson Date 2017-09-05 Time 10:10 Rev Time 0.00
Received By gjohnson Date 2017-09-01 Time 15:24 Sent To  
Notes
2017-09-05 11:32:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT 1. ONLY THE GROUND FLOOR UNITS WILL BE
 REQUIRED TO COMPLY TO THE FHA AS A MIN CODE REQUIREMENT
 THE PLAN IS STATING THAT THE FIRST FLOOR WILL COMPLY
 WITH THE FLORIDA ACCESSIBILITY CODE AND FLOORS 2 AND 3
 WILL COMPLY WITH FHA IS THIS CORRECT PLEASE CLARIFY.
 ALSO SEE BUILDING 1. COMMENT .
  
 PREVIOUS COMMENT 2. WHAT IS WORKFORCE HOUSING IS THIS
 PROJECT FEDERALLY FUNDED. PER WPB AMEND TO FBC 107.2.1
  
 PREVIOUS COMMENT 13, SHT. P-1 THE SANITARY PLAN FOR 2ND
 AND 3RD FLOOR THE APARTMENTS ARE LABELED 101-104 PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 PREVIOUS COMMENT 14. PROVIDE MANUFACTURE SPECIFICATIONS
 FOR SUB WATER METER AND BACK FLOW . PER WPB AMEND TO
 FBC 107.2.1
  
 NEW COMMENTS:
  
 1. SHT. A6.3 DETAIL 3(A) THE END OF THE GRAB BAR
 BACKING SHALL BEGIN AT THE FRONT EDGE OF THE TUB AND
 EXTEND 24" TO BACK WALL . PER FHA DESIGN MANUAL PG. 6.9
  
 2.SHT. A6.3 SHOW GRAB BAR BACKING AT FOOT OF TUB. PER
 FHA DESIGN MANUAL PG.6.8
  
 3. SHT. A6.3 DETAIL 3(B) THE GRAB BAR BACKING ON BACK
 WALL OF TUB SHALL BEGIN 6" MAX FROM THE TOP OF THE TUB
 AND EXTEND A MIN OF 38" TO THE TOP. PER FHA DESIGN
 MANUAL PG. 6.9
  
 4. IT DOES NOT APPEAR THAT HALF OF THE AREA OF THE
 PARAPET AND WALLS ARE INCLUDED IN THE SQFT DRAIN BY
 ROOF DRAINS PLEASE CLARIFY. PER FBC PL 1106.5 PARAPET
 WALL SCUPPER LOCATION.
 PARAPET WALL ROOF DRAINAGE SCUPPER AND OVERFLOW SCUPPER
 LOCATION SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 1503.4 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 5. PLEASE PROVIDE A NOTE ON THE PLAN STATING THAT
 SEPARATE PERMITS ARE REQUIRED FOR ALL BACKFLOW
 PREVENTER'S. PER WPB AMEND TO FBC 107.2.1 AND UTILITIES
 DEPT
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-06 Cont ID  
Sent By gjohnson Date 2017-07-06 Time 10:44 Rev Time 0.00
Received By gjohnson Date 2017-07-05 Time 09:40 Sent To  
Notes
2017-07-06 11:39:591ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. ONLY THE GROUND FLOOR UNITS WILL BE REQUIRED TO
 COMPLY TO THE FHA
  
 2. WHAT IS WORKFORCE HOUSING IS THIS PROJECT FEDERALLY
 FUNDED. PER WPB AMEND TO FBC 107.2.1
  
 3. PLEASE CLARIFY ON THE PLAN WHICH DESIGN
 SPECIFICATION A OR B THAT YOU WILL BE USING ON EACH
 UNIT. PER FHA
  
 4. PLEASE INDICATE ON THE PLAN WHICH DOCUMENT THE FHA
 DESIGN MANUAL OR THE FHA GUIDELINES FOUND IN FBC ACC,
 YOU WILL BE USING TO DESIGN THE ELEMENTS TO COMPLY WITH
 THE FHA . PER WPB AMEND TO FBC 107.2.1
  
 5. SHOW THE CLEAR FLOOR SPACE FOR THE FIXTURES IN THE
 BATHROOM AND KITCHEN. PER FHA
  
 6. PROVIDE MOUNTING HEIGHT DIMENSIONS FOR THE GRAB BAR
 BACK AT THE TOILET AND TUB. PER FHA
  
 7. PROVIDE RISER DIAGRAM FOR ROOF DRAINS PER WPB AMEND
 TO FBC 107.3.5.1.3(13)
  
 8. PLEASE SHOW ON THE PLANS THE SQUARE FOOTAGE BEING
 DRAINED BY EACH ROOF DRAIN . PER WPB AMEND TO FBC
 107.2.1
  
 9. PROVIDE COMPLIANCE WITH FBC PL 1108.1 SECONDARY
 (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS.
 WHERE ROOF DRAINS ARE REQUIRED, SECONDARY (EMERGENCY
 OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED
 WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE
 ROOF IN SUCH A MANNER THAT WATER WILL BE ENTRAPPED IF
 THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON.
  
 10. TERMINATION OF THE PAN DRAINS SHALL COMPLY WITH FBC
 PL 504.7.2 PAN DRAIN TERMINATION.
 THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER
 A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR
 DRAIN OR EXTEND TO THE EXTERIOR OF THE BUILDING AND
 TERMINATE NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE
 THAN 24 INCHES (610 MM) ABOVE THE ADJACENT GROUND
 SURFACE.
  
 11. SHOW ALL CLEAN OUTS ON RISER PER FBC PL 708.3.4
 BASE OF STACK.
 A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH WASTE
 OR SOIL STACK.
  
 708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
 THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. THE CLEANOUT
 SHALL BE EITHER INSIDE OR OUTSIDE THE BUILDING WALL AND
 SHALL BE BROUGHT UP TO THE FINISHED GROUND LEVEL OR TO
 THE BASEMENT FLOOR LEVEL. AN APPROVED TWO-WAY CLEANOUT
 IS ALLOWED TO BE USED AT THIS LOCATION TO SERVE AS A
 REQUIRED CLEANOUT FOR BOTH THE BUILDING DRAIN AND
 BUILDING SEWER. THE CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER SHALL NOT BE REQUIRED
 IF THE CLEANOUT ON A 3-INCH (76 MM) OR LARGER DIAMETER
 SOIL STACK IS LOCATED WITHIN A DEVELOPED LENGTH OF 10
 FEET (3048 MM) OF THE BUILDING DRAIN AND BUILDING SEWER
 CONNECTION. THE MINIMUM SIZE OF THE CLEANOUT AT THE
 JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER SHALL
 COMPLY WITH SECTION 708.7.
  
 12. PROVIDE RISER FOR WATER HEATER PAN DRAIN. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 13, SHT. P-1 THE SANITARY PLAN FOR 2ND AND 3RD FLOOR
 THE APARTMENTS ARE LABELED 101-104 PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 14. PROVIDE MANUFACTURE SPECIFICATIONS FOR SUB WATER
 METER AND BACK FLOW . PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2017-06-29 Cont ID  
Sent By shill Date 2017-06-29 Time 12:33 Rev Time 0.00
Received By shill Date 2017-06-29 Time 12:33 Sent To  
Notes
2017-06-29 12:33:53****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 A SEPARATE ROOF PERMIT IS REQUIRED. A ROOF PRODUCT
 APPROVAL WAS SUBMITTED, FIBERTITE SINGLE PLY ROOF
 SYSTEMS OVER LIGHTWEIGHT CONCRETE DECKS (NOA
 15-1026.04).
  
 AT TIME OF ROOF SUB PERMIT APPLICATION, THE APPROVED
 ASSEMBLY IS TO BE SELECTED. A PLAN REVIEW WILL BE
 REQUIRED AT THAT TIME.
  
 IF ROOFING CONTRACTOR ELECTS TO PROPOSE A DIFFERENT
 PRODUCT THAN THE ONE ALREADY SUBMITTED, DESIGNER OF
 RECORD IS TO REVIEW AND APPROVE THE ROOF PRODUCT
 APPROVAL PRIOR TO SUBMITTAL TO THE CITY.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status N Date 2017-11-03 Cont ID  
Sent By aclange Date 2017-11-03 Time 11:11 Rev Time 0.00
Received By aclange Date 2017-11-03 Time 11:11 Sent To  
Notes
2017-11-03 11:13:04NOT A THRESHOLD BUILDING. WILL NOT BE USING A PRIVATE
 PROVIDER OR THRESHOLD INSPECTOR ON THIS BUILDING.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status N Date 2017-06-29 Cont ID  
Sent By shill Date 2017-06-29 Time 17:46 Rev Time 0.00
Received By shill Date 2017-06-29 Time 17:45 Sent To  
Notes
2017-06-29 08:48:31NOTICE TO BUILDING OFFICIAL OF USE OF PRIVATE PROVIDER
 ROUTED TO DHARVEY DESK 6/29/17
 REQUEST IS FOR PLAN REVIEW AND INSPECTIONS
  
 GFA INTERNATIONAL, INC.
 PAUL H. DANFORTH, PE
 [email protected]
 561-347-0070
  
 PLAN REVIEW AUDIT PERFORMED PER DH/SAK
  
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-08-22 Time   Rev Time 0.00
Received By pgreilic Date 2017-08-18 Time 16:43 Sent To  
Notes
2017-08-22 11:34:50PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-06-27 Time   Rev Time 0.00
Received By pgreilic Date 2017-06-23 Time 15:11 Sent To  
Notes
2017-06-27 09:50:45PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]