Plan Review Details - Permit 17060176
Plan Review Stops For Permit 17060176
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-06-08 Cont ID  
Sent By jwitmer Date 2017-06-08 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2017-06-08 Time 08:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-17 Cont ID  
Sent By jleahy Date 2017-07-17 Time 17:06 Rev Time 0.00
Received By jleahy Date 2017-07-17 Time 17:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-07-12 Cont ID  
Sent By ccole Date 2017-07-12 Time 08:46 Rev Time 0.00
Received By jleahy Date 2017-07-12 Time 07:14 Sent To M
Notes
2017-07-12 07:15:30FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ONE SET MISSING PAGE E-3

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By jleahy Date 2017-06-29 Time 17:49 Rev Time 0.00
Received By jleahy Date 2017-06-29 Time 17:34 Sent To  
Notes
2017-06-29 18:21:10FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PAGE E-1
  
 FOR ALL MODULAR FURNITURE
  
 ASHREA 90.1 8.4.2 AUTOMATIC RECEPTACLE CONTROL. AT
 LEAST 50% OF ALL 125 VOLT 15- AND 20-AMPERE
 RECEPTACLES, INCLUDING THOSE
 INSTALLED IN MODULAR PARTITIONS, INSTALLED IN THE
 FOLLOWING SPACE TYPES: A. PRIVATE OFFICES B. OPEN
 OFFICES C. COMPUTER CLASSROOMS
 SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL DEVICE THAT
 SHALL FUNCTION ON: A. A SCHEDULED BASIS USING A
 TIME-OF-DAY OPERATED CONTROL
 DEVICE THAT TURNS RECEPTACLES OFF AT SPECIFIC
 PROGRAMMED TIMES?AN INDEPENDENT PROGRAM SCHEDULE SHALL
 BE PROVIDED FOR AREAS OF NO
 MORE THAN 25,000 FT2 BUT NOT MORE THAN ONE FLOOR, OR B.
 AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF
 WITHIN 30 MINUTES OF ALL
 OCCUPANTS LEAVING A SPACE, OR C. A SIGNAL FROM ANOTHER
 CONTROL OR ALARM SYSTEM THAT INDICATES THE AREA IS
 UNOCCUPIED. EXCEPTIONS:
 RECEPTACLES FOR THE FOLLOWING SHALL NOT REQUIRE AN
 AUTOMATIC CONTROL DEVICE: A. RECEPTACLES SPECIFICALLY
 DESIGNATED FOR EQUIPMENT
 REQUIRING 24 HOUR OPERATION. B. SPACES WHERE AN
 AUTOMATIC SHUTOFF WOULD ENDANGER THE SAFETY OR SECURITY
 OF THE ROOM OR BUILDING
 OCCUPANT(S)
  
 LOUNGE ROOM
 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL
 ALL OUTLETS INSTALLED WITHIN 6' OF THE SINK.
 (B) OTHER THAN DWELLING UNITS (5) SINKS WHERE
 RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT)
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-13 Cont ID  
Sent By pleduc Date 2017-06-13 Time   Rev Time 0.00
Received By pleduc Date 2017-06-12 Time 16:27 Sent To  
Notes
2017-06-12 16:59:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-17 Cont ID  
Sent By jleahy Date 2017-07-17 Time 17:06 Rev Time 0.00
Received By jleahy Date 2017-07-13 Time 13:46 Sent To  
Notes
2017-07-17 13:46:29RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-12 Cont ID  
Sent By ccole Date 2017-07-12 Time 08:46 Rev Time 0.00
Received By ccole Date 2017-07-07 Time 13:49 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-30 Cont ID  
Sent By jleahy Date 2017-06-30 Time 07:02 Rev Time 0.00
Received By jleahy Date 2017-06-30 Time 07:02 Sent To  
Notes
2017-06-06 11:57:52C08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-06-08 Cont ID  
Sent By jwitmer Date 2017-06-08 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2017-06-08 Time 08:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-07-12 Cont ID  
Sent By ccole Date 2017-07-12 Time 08:46 Rev Time 0.00
Received By ccole Date 2017-07-12 Time 08:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-20 Cont ID  
Sent By ccole Date 2017-06-20 Time 16:37 Rev Time 0.00
Received By ccole Date 2017-06-20 Time 16:37 Sent To  
Notes
2017-06-20 16:42:491ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060176
 6/20/17
  
 PLAN REVIEW RESULT: DENIED.
  
 1) M-201: SHOW THE LOCATION(S) OF REQUIRED SMOKE
 DETECTORS IN THE RETURN AIR SYSTEM(S)- SEE SECTIONS
 606.2.1 & 606.2.2.
  
 2) M-201: SHOW THE LOCATIONS OF THE REQUIRED OUTSIDE
 AIR DAMPERS FOR THE SYSTEMS- SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-06-08 Cont ID  
Sent By tklarge Date 2017-06-08 Time 10:13 Rev Time 0.00
Received By tklarge Date 2017-06-08 Time 10:13 Sent To  
Notes
***NONE***