Plan Review Details - Permit 17060102
Plan Review Stops For Permit 17060102
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-06-07 Cont ID  
Sent By jwitmer Date 2017-06-07 Time 16:28 Rev Time 0.00
Received By jwitmer Date 2017-06-07 Time 14:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-07 Cont ID  
Sent By jpearson Date 2017-06-07 Time 10:37 Rev Time 0.00
Received By jpearson Date 2017-06-07 Time 10:37 Sent To  
Notes
2017-06-07 10:51:56CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. THE PROJECT ADDRESS ON THE PERMIT APPLICATION IS
 DIFFERENT THAN LISTED ON PLANS. THE ADDRESS AND PARCEL
 NUMBER LISTED ON PERMIT APPLICATION IS FOR A HOOTERS
 RESTAURANT. PLEASE CLARIFY/CORRECT. FBC 107.2.1
 2. INDICATE ON PLANS COMPLIANCE WITH THE REQUIRED
 GROUNDING OF RECEPTACLES AND EQUIPMENT IN PATIENT CARE
 AREAS. NEC 517.13
 3. CONFIRM SIZE OF PANEL A. THE PANEL SCHEDULE STATES
 THAT THIS NEEDS TO BE VERIFIED. PROVIDE CONFIRMATION SO
 THAT DETERMINATION CAN BE MADE THAT THE PANEL SIZE WILL
 BE SUFFICIENT FOR ADDITIONAL LOADS TO BE ADDED. NEC
 408.30, FBC 107.2.1
 4. PROVIDE REQUIRED SHOW WINDOW OUTLETS AND CIRCUIT.
 NEC 210.62
 5. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY
 FBC C401.2 AND ASHREA 90.1: 8.4.2
 6. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE AND
 VALUE OF WORK. FBC 105.1, 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-14 Cont ID  
Sent By scaldero Date 2017-06-14 Time 15:32 Rev Time 0.00
Received By scaldero Date 2017-06-14 Time 15:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-28 Cont ID  
Sent By lmarchan Date 2017-06-28 Time 11:55 Rev Time 0.00
Received By lmarchan Date 2017-06-02 Time 12:12 Sent To  
Notes
2017-06-05 12:13:09B08

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-12 Cont ID  
Sent By ccole Date 2017-06-12 Time 10:17 Rev Time 0.00
Received By ccole Date 2017-06-12 Time 09:41 Sent To  
Notes
2017-06-12 15:51:561ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060102
 6/12/17
  
 RESULTS: DENIED
  
 1) SUBMIT A MECHANICAL SUB-PERMIT APPLICATION FOR
 ALTMAN BROTHERS, OR PROVIDE A SHOP DRAWING STAMP ON THE
 PLANS FROM THE ARCHITECT OF RECORD- PLEASE SEE SECTION
 105.3.1.2 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-14 Cont ID  
Sent By gjohnson Date 2017-06-14 Time 12:51 Rev Time 0.00
Received By gjohnson Date 2017-06-14 Time 12:51 Sent To  
Notes
2017-06-14 12:53:461ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. JOB ADDRESS IN TITLE BLOCK IS IN CORRECT PLEASE
 CLARIFY. PER WPB AMEND TO FBC.107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  