Plan Review Details - Permit 17060078
Plan Review Stops For Permit 17060078
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-06-13 Cont ID  
Sent By cpuell Date 2017-06-13 Time 09:54 Rev Time 0.00
Received By jleahy Date 2017-06-05 Time 12:30 Sent To  
Notes
2017-06-05 12:32:31CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED CUT SHEETS FOR THE EQUIPMENT SHOWING LISTINGS.
 110.3 NEC 2011 PRIOR TO THE INSTALLATION OF THE
 EQUIPMENT.
  
 ONE NOTE ON SERVICE MAIN STATED IF NOT INTERGRAL WITH
 THE EQUIPMENT SUPPLY DISCONNECT.
 IF INTERGRAL WITH THE EQUIPMENT THEN THE DISCONNECT
 WOULD HAVE TO BE SERVICE ENTERANCE RATED
 230.66 NEC 2011
  
 THE GROUNDING ELECTRODE CONDUCTOR SHOWS ALUMINUM WIRE
 IT IS NOT ALLOWED TO CONNECT TO THE GROUND ROD OR BE
 WITHIN 18" OF EARTH. 250.64 (A)

Review Stop ENG-CON ENGINEERING ROW CONSTRUCTION
Rev No 1 Status N Date 2017-06-12 Cont ID  
Sent By jleahy Date 2017-06-13 Time 16:33 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-13 Cont ID  
Sent By cpuell Date 2017-06-13 Time 09:54 Rev Time 0.00
Received By jleahy Date 2017-06-02 Time 10:23 Sent To E
Notes
***NONE***