Plan Review Details - Permit 17060065
Plan Review Stops For Permit 17060065
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-12-20 Cont ID  
Sent By jwitmer Date 2017-12-20 Time 08:55 Rev Time 0.00
Received By jwitmer Date 2017-12-19 Time 16:55 Sent To  
Notes
2017-12-19 17:31:182014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060065
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. DEC. 19/2017
  
 ACTION: BUILDING PROVISO
  
 1) RESIDENT INSPECTOR FORMS SUBMITTED ON 11/01/2017
 UNDER SUBMITTAL: 17110018 AND ROUTED TO KEN CONRAD BY
 JS.
  
 2) BUILDING PROVISO / DEFERRED SUBMITTALS: SHEET S121
 CONSTRUCTION NOTE NUMBER 1 INDICATES THE ARCHITECTURAL
 ALUMINUM CANOPY DECK, SOFFIT AND FASCIA ARE
 PRE-ENGINEERED. PLEASE SUBMIT TO THE DESIGNER OF RECORD
 FOR REVIEW, SHOP DRAWING STAMP OF APPROVAL BEFORE BEING
 FORWARDED TO THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) BUILDING PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS, ROOF TOP INTAKE AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
  
 SUBMITTED PRODUCT APPROVALS:
 FL 12400.3 FLUSH OUTSWING DOOR
 FL20701-R1 SWINGING EXTERIOR DOOR
 FL 16392-R2 1006 SERIES ELECTRIC STRIKE
 FL 14313-R5 CURTAIN WALL
 NOA 15-0226.03 STO THERM CI LM 180 CMU EFIS SYSTEM
  
 4) BUILDING PROVISO / DEFERRED SUBMITTAL: FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5) BUILDING PROVISO / DEFERRED SUBMITTAL: ROOFING: FOR
 ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 6) BUILDING PROVISO / DEFERRED SUBMITTAL / DELEGATE
 SESIGN ) SHEET M301 ROOF TOP CURB AND EQUIPMENT TIE
 DOWN NOTE:
 ALL SUPPORTS SHALL BE IN COMPLIANCE WITH FBC/FMC 2014
 AND THE HURRICANE CODES TO WITHSTAND WIND AND IMPACT
 LOADS AND DESIGNED BY A FLORIDA REGISTERED STRUCTURAL
 ENGINEER. SUBMIT CALCULATIONS FOR REVIEW. SEE
 STRUCTURAL DRAWINGS FOR THE WIND DESIGN CRITERIA,
 PLEASE PROVIDE. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED. LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-26 Cont ID  
Sent By jwitmer Date 2017-10-26 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2017-10-25 Time 13:02 Sent To  
Notes
2017-10-26 08:56:512014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060065
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. OCT. 26/2017
 ACTION: DENIED
  
  
 PLANS APPEAR TO BE CODE COMPLIANT, STAMPED NEED
 RESIDENT INSPECTOR FORMS TO PASS INTHE COMPUTER
 PROGRAM>
 10/26/2017
  
  
 1) COMPLIED.
  
 2) BUILDING PROVISO / DEFERRED SUBMITTALS: SHEET S121
 CONSTRUCTION NOTE NUMBER 1 INDICATES THE ARCHITECTURAL
 ALUMINUM CANOPY DECK, SOFFIT AND FASCIA ARE
 PRE-ENGINEERED. PLEASE SUBMIT TO THE DESIGNER OF RECORD
 FOR REVIEW, SHOP DRAWING STAMP OF APPROVAL BEFORE BEING
 FORWARDED TO THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2ND REVIEW. THE CONTRACTOR ELECTS TO USE A RESIDENT
 INSPECTOR FORMS WILL BE E-MAILED TO:
 [email protected] SENT 10/25/2017 04:28 PM.
  
 3A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
  
 3B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW MAY BE SCHEDULED.
  
 3C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 3E) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 AND
 GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 RESIDENT INSPECTORS. COMMENT # 14. 3 COPIES OF ALL SHOP
 DRAWINGS (HANDRAILS, PRECAST JOINT AND SLABS, PRODUCT
 APPROVALS, TRUSSES, BAR JOIST, ETC.) MUST BE SUBMITTED
 TO THE BUILDING DEPARTMENT. TWO REVIEWED SETS OF
 DOCUMENTS WILL BE RETURNED TO THE JOB SITE BEFORE ANY
 OF THE ABOVE ARE INSTALLED ON THE JOB.
  
 3F) INFORMATION ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 4)BUILDING PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS, ROOF TOP INTAKE AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 SUBMITTED PRODUCT APPROVALS:
 FL 12400.3 FLUSH OUTSWING DOOR
 FL20701-R1 SWINGING EXTERIOR DOOR
 FL 16392-R2 1006 SERIES ELECTRIC STRIKE
 FL 14313-R5 CURTAIN WALL
 NOA 15-0226.03 STO THERM CI LM 180 CMU EFIS SYSTEM
  
 5) BUILDING PROVISO / DEFERRED SUBMITTAL: FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6) BUILDING PROVISO / DEFERRED SUBMITTAL: ROOFING: FOR
 ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 7) BUILDING PROVISO / DEFERRED SUBMITTAL / DELEGATE
 SESIGN ) SHEET M301 ROOF TOP CURB AND EQUIPMENT TIE
 DOWN NOTE:
 ALL SUPPORTS SHALL BE IN COMPLIANCE WITH FBC/FMC 2014
 AND THE HURRICANE CODES TO WITHSTAND WIND AND IMPACT
 LOADS AND DESIGNED BY A FLORIDA REGISTERED STRUCTURAL
 ENGINEER. SUBMIT CALCULATIONS FOR REVIEW. SEE
 STRUCTURAL DRAWINGS FOR THE WIND DESIGN CRITERIA,
 PLEASE PROVIDE. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED. LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-27 Cont ID  
Sent By jwitmer Date 2017-06-27 Time 16:31 Rev Time  
Received By jwitmer Date 2017-06-24 Time 09:46 Sent To  
Notes
2017-06-27 16:31:262014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060065
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 27/2017
 ACTION: DENIED
  
 1) THE PLANS INDICATE NEW ADDITIONS TO THE HOSPITAL BUT
 THERE WAS NO SOILS REPORT SUBMITTED THIS REVIEW. 2014
 FBC-B 803.5.2 QUESTIONABLE SOIL.
  
 2) SHEET S121 CONSTRUCTION NOTE NUMBER 1 INDICATES THE
 ARCHITECTURAL ALUMINUM CANOPY DECK, SOFFIT AND FASCIA
 ARE PRE-ENGINEERED. PLEASE SUBMIT TO THE DESIGNER OF
 RECORD FOR REVIEW, SHOP DRAWING STAMP OF APPROVAL
 BEFORE BEING FORWARDED TO THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) THE CANOPY, NEW X-RAY, RADIATION ROOMS, OFFICES AND
 TRAUMA UNIT ADDITIONS SHOW STEEL BEAMS & BOLTED
 CONNECTIONS OR WELDED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 IF THE CONTRACTOR PREFERS THE USE OF A RESIDENT
 INSPECTOR FOR THE EFFICIENCY OF THE JOB, PLEASE PROVIDE
 DOCUMENTATION IN THE COMMENT RESPONSE NARRATIVE. THIS
 WILL REQUIRE RESIDENT INSPECTORS FORMS, AND ALSO 3 SETS
 OF PLANS.
  
 4) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS, ROOF TOP INTAKE AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
 IF THE CONTRACTOR WISHES TO DEFER THE PRODUCT APPROVALS
 UNTIL AFTER PERMIT ISSUANCE PLEASE INFORM THROUGH THE
 COMMENT RESPONSE.
  
 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 8) SHEET A201, A231, A241 & A242 ALL SHOW THE
 INSTALLATION OF EFIS SYSTEMS. : PLEASE PROVIDE THE
 PRODUCT APPROVAL FOR THE SYSTEM TO BE INSTALLED. PLEASE
 ALSO PROVIDE THE MANUFACTURERS INSTALLATION BROCHURE
 PROVIDING COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 9) SHEET M301 ROOF TOP CURB AND EQUIPMENT TIE DOWN
 NOTE:
 ALL SUPPORTS SHALL BE IN COMPLIANCE WITH FBC/FMC 2014
 AND THE HURRICANE CODES TO WITHSTAND WIND AND IMPACT
 LOADS AND DESIGNED BY A FLORIDA REGISTERED STRUCTURAL
 ENGINEER. SUBMIT CALCULATIONS FOR REVIEW. SEE
 STRUCTURAL DRAWINGS FOR THE WIND DESIGN CRITERIA,
 PLEASE PROVIDE. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED. LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS.
  
  
 10) SHEET A811 DETAIL A10 DETAILS TO X-RAY ROOMS AND
 CONTROL ROOM AS WELL AS IN THE 4 TRAUMA UNITS.
 . FBC-B 465.5.1 SHIELDING. EACH X-RAY FACILITY SHALL
 HAVE PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS
 NEEDED TO ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A
 RADIATION DOSE IN EXCESS OF THE LIMITS SPECIFIED IN
 PART III OF CHAPTER 64E-5, FLORIDA ADMINISTRATIVE CODE.
 PLEASE SHOW COMPLIANCE WITH:
 10A) FBC-B 465.5.1.1 STRUCTURAL SHIELDING IN WALLS AND
 OTHER VERTICAL BARRIERS REQUIRED FOR PERSONNEL
 PROTECTION SHALL EXTEND WITHOUT BREACH FROM THE FLOOR
 TO A HEIGHT OF AT LEAST 7 FEET (2.1 M).
  
 10B) FBC-B 465.5.1.2 DOORS, DOOR FRAMES, WINDOWS AND
 WINDOW FRAMES SHALL HAVE THE SAME LEAD EQUIVALENT
 SHIELDING AS THAT REQUIRED IN THE WALL OR OTHER BARRIER
 IN WHICH THEY ARE INSTALLED.
  
 10C) FBC-B 465.5.1.3 PRIOR TO CONSTRUCTION, THE FLOOR
 PLANS AND EQUIPMENT ARRANGEMENT OF ALL NEW
 INSTALLATIONS, OR MODIFICATIONS OF EXISTING
 INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND
 ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE
 SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND
 APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER
 REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE
 FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
  
 10D) 465.5.1.3.1 THE PLANS SHALL SHOW, AS A MINIMUM,
 THE FOLLOWING.
  
 465.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM'S
 RADIATION PORT; THE PORT'S TRAVEL AND TRAVERSE LIMITS;
 GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY
 WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR'S
 BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL.
  
 465.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS
 OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS,
 FLOOR AND CEILING OF THE ROOM CONCERNED.
  
 465.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED.
  
 465.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT
 AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM
 CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE
 TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS
 MAY BE PRESENT.
  
 465.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT
 AND THE MAXIMUM TECHNIQUE FACTORS.
  
 465.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS
 WHICH WILL BE PERFORMED WITH THE EQUIPMENT.
  
 10E) 465.6 DOORS, INTERLOCKS, AND WARNING SYSTEMS.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12 ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-01-05 Cont ID  
Sent By jpearson Date 2018-01-05 Time 09:15 Rev Time 0.00
Received By jpearson Date 2018-01-05 Time 08:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-11-12 Cont ID  
Sent By jpearson Date 2017-11-12 Time 13:32 Rev Time 0.00
Received By jpearson Date 2017-11-12 Time 12:23 Sent To  
Notes
2017-11-12 13:32:12CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS: 2ND REVIEW. ITEMS CORRECTED
 ARE NOTED. REMAINING ITEMS HAVE ADDITIONAL COMMENTS IN
 PARENTHESES.
  
 1. CORRECTED.
 2.CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. WITH THE CURRENT LOAD CALCULATION PROVIDED, IT
 APPEARS GENERATOR #1 IS OVERLOADED. PANEL TESB SHOWS A
 DEMAND OF 1027.3 KVA AND THE GENERATOR IS RATED FOR
 1000. IF ANY CORRECTIONS TO LOAD CALCULATIONS FROM
 ABOVE COMMENTS RESULT IN ADDITIONAL LOAD, THEN THIS
 WILL INCREASE THE OVERLOAD. PROVIDE CLARIFICATION
 AND/OR CORRECTION. FBC 107.2.1, NEC 517.30(D) (RESPONSE
 PROVIDED STATED: "WILL COMPLY. EXISTING LOADS HAVE TO
 BE DEMANDED PROPERLY." GENERATOR MUST HAVE SUFFICIENT
 CAPACITY AND PROPER RATING TO MEET THE DEMAND PRODUCED
 BY THE LOAD OF THE ESSENTIAL SYSTEM AT ANY GIVEN TIME.
 PROVIDE ADDITIONAL DETAILS TO SHOW GENERATOR IS SIZED
 SUFFICIENTLY TO HANDLE THE LOAD, INCLUDE STARTING
 CURRENT REQUIRED OF FIRE PUMP.) NEC 517.30(D),
 695.3(D)(1)
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. INDICATE PANEL BOARD BONDING REQUIRED. NEC 517.14
 (NO RESPONSE PROVIDED.)
 17. CORRECTED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-27 Cont ID  
Sent By jpearson Date 2017-06-27 Time 10:00 Rev Time 0.00
Received By jpearson Date 2017-06-26 Time 08:37 Sent To  
Notes
2017-06-27 10:45:53CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. THE DEMAND AMPS/KVA FOR PANEL EGLB1 EXCEED THE
 CAPACITY OF TRANSFORMER T-EGLB1. PROVIDE CORRECTION.
 NEC 517.30(D); 230.79
 2. PROVIDE PANEL SCHEDULE FOR PANEL QDP-B. NEC 408.4;
 215.5; FBC 107.2.1
 3. SHEET E802, PANEL TDP1, LOAD CALCULATION PROVIDED
 SHOWS X-RAY LOAD WITH A 19.17% DEMAND FACTOR, AND
 RECEPTACLE LOAD WITH A 78.41% DEMAND FACTOR. PROVIDE
 CODE SECTION FROM THE NEC WHERE THESE DEMAND FACTORS
 ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS. NEC 220;
 FBC 107.2.1
 4. SHEET E805, PANEL XRH, LOAD CALCULATION PROVIDED
 SHOWS X-RAY LOAD WITH A 37.5% DEMAND FACTOR. PROVIDE
 CODE SECTION FROM THE NEC WHERE THESE DEMAND FACTORS
 ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS. NEC 220;
 FBC 107.2.1
 5. SEVERAL PANEL SCHEDULES SHOW THE LIGHTING DEMAND
 FACTOR AT 40% (EXAMPLE PANEL CGHC2 AND GHC2). THE NOTE
 AT THE BOTTOM OF TABLE 220.42 STATES THAT THIS DEMAND
 FACTOR SHOULD NOT BE USED WHERE IT IS LIKELY THE
 LIGHTING WILL BE ON AT THE SAME TIME, SUCH AS THE
 TRAUMA ROOMS. PROVIDE CLARIFICATION FOR THIS DEMAND
 FACTOR, INDICATING ANY AREAS WHERE LIGHTING WILL BE
 USED AT THE SAME TIME. FBC 107.2.1; NEC TABLE 220.42
 6. SHEET E801 AND E802, ISOLATION PANELS T1A, T1B, T2A,
 T2B, T3A, T3B, T4A, T4B: NOTE STATES THAT THE BRANCH
 CIRCUITS WILL BE ON A 2 POLE BREAKER, BUT THIS IS NOT
 REFLECTED IN THE PANEL SCHEDULE. PROVIDE CORRECTION TO
 ACCURATELY REFLECT THE PANEL LAYOUT. FBC 107.2.1; NEC
 408.4
 7. SHEET E803, PANEL EQH1, LOAD CALCULATION PROVIDED
 SHOWS THE MOTOR LOAD WITH A 118.49% DEMAND FACTOR, AND
 THE COOLING LOAD WITH A 85% DEMAND FACTOR. PROVIDE CODE
 SECTION FROM THE NEC WHERE THESE DEMAND FACTORS ARE
 LOCATED AND/OR CORRECT THE DEMAND FACTORS. NEC 220; FBC
 107.2.1
 8. SHEET E803, PANEL EQL1, LOAD CALCULATION PROVIDED
 SHOWS THE COOLING LOAD WITH A 85% DEMAND FACTOR.
 PROVIDE CODE SECTION FROM THE NEC WHERE THESE DEMAND
 FACTORS ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS.
 NEC 220; FBC 107.2.1
 9. SHEET E804, PANEL TMSB, LOAD CALCULATION PROVIDED
 SHOWS THE RECEPTACLE LOAD WITH A 51.04% DEMAND FACTOR,
 THE MOTOR LOAD WITH A 118.49% DEMAND FACTOR, THE
 COOLING LOAD WITH A 85% DEMAND FACTOR, AND THE X-RAY
 LOAD WITH A 19.17% DEMAND FACTOR. PROVIDE CODE SECTION
 FROM THE NEC WHERE THESE DEMAND FACTORS ARE LOCATED
 AND/OR CORRECT THE DEMAND FACTORS. NEC 220; FBC 107.2.1
 10. SHEET E804, PANEL TESB, LOAD CALCULATION PROVIDED
 SHOWS RECEPTACLE LOAD WITH A 51.06% DEMAND FACTOR, THE
 MOTOR LOAD WITH A 118.49% DEMAND FACTOR, THE COOLING
 LOAD WITH A 85% DEMAND FACTOR, AND THE X-RAY LOAD WITH
 A 19.17% DEMAND FACTOR. PROVIDE CODE SECTION FROM THE
 NEC WHERE THESE DEMAND FACTORS ARE LOCATED AND/OR
 CORRECT THE DEMAND FACTORS. NEC 220; FBC 107.2.1
 11. WITH THE CURRENT LOAD CALCULATION PROVIDED, IT
 APPEARS GENERATOR #1 IS OVERLOADED. PANEL TESB SHOWS A
 DEMAND OF 1027.3 KVA AND THE GENERATOR IS RATED FOR
 1000. IF ANY CORRECTIONS TO LOAD CALCULATIONS FROM
 ABOVE COMMENTS RESULT IN ADDITIONAL LOAD, THEN THIS
 WILL INCREASE THE OVERLOAD. PROVIDE CLARIFICATION
 AND/OR CORRECTION. FBC 107.2.1, NEC 517.30(D)
 12. SHEET E804, PANEL QDP, LOAD CALCULATION PROVIDED
 SHOWS THE MOTOR LOAD WITH A 118.49% DEMAND FACTOR.
 PROVIDE CODE SECTION FROM THE NEC WHERE THESE DEMAND
 FACTORS ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS.
 NEC 220; FBC 107.2.1
 13. PROVIDE AUTOMATIC LIGHTING CONTROLS FOR INTERIOR
 LIGHTING PER THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION. FBC C401.2.1, C405
 14. SHEET E901, LIGHTING CONTACTOR DETAIL SHOWS A
 PHOTOCELL CONTROLLING THE CONTACTOR. ENERGY CODE
 STATES: "EXTERIOR LIGHTING CONTROLS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS". PROVIDE
 CORRECTION. FBC C405.2.4
 15. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY
 FBC C401.2 AND ASHREA 90.1: 8.4.2
 16. INDICATE PANEL BOARD BONDING REQUIRED. NEC 517.14
 17. SHEETS V106, V206, V306, V406, V506, V606: INDICATE
 WHICH MODEL IS USED TO DETERMINE PROPER WIRING
 REQUIREMENTS. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-12-18 Cont ID  
Sent By pleduc Date 2017-12-18 Time   Rev Time 0.00
Received By pleduc Date 2017-12-18 Time 10:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By pleduc Date 2017-10-17 Time   Rev Time 0.00
Received By pleduc Date 2017-10-17 Time 10:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-08 Cont ID  
Sent By pleduc Date 2017-06-08 Time   Rev Time 0.00
Received By pleduc Date 2017-06-06 Time 13:08 Sent To  
Notes
2017-06-08 10:11:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET G 109 - THE LIFE SAFETY PLAN DOES NOT APPEAR
 TO INDICATED EXIT CONDITIONS DURING CONSTRUCTION. THE
 LIFE SAFETY PLAN MUST INDICATE HOW THE CONSTRUCTION
 AREA WILL BE PROTECTED/SEPARATED FROM REGULAR BUSINESS
 ACTIVITIES.
  
 WHAT EXITS WILL BE BLOCKED, HOW WILL THEY REROUTE
 PEOPLE, WHAT IS/ARE THE PROPOSED OCCUPANCY LOADS
 CHANGING BASED ON THE REROUTING, WILL FIRE ALARM
 DEVICES/NOTIFICATIONS BE AFFECTED BY THE CONSTRUCTION
 SEPARATIONS , NEW EXIT SIGNS, NEW EMERGENCY LIGHTING,
 ETC.
  
 PLEASE PROVIDE DETAILED INDICATIONS AND NARRATIVES
 RELATING TO THE ABOVE.
  
  
  
 2) SHEET G 109 - THERE IS A NOTE INDICATING EXISTING DE
 DOORS WILL BE REMOVED AT THE END OF PHASE 1A. HAVE
 THESE DOORS BEEN ELVALUATED FOR THEIR FUNCTION RELATING
 TO SMOKE CONTROL/BARRIERS?
  
 PLEASE REVIEW THE EXISTING LIFE SAFETY ENGINEERING
 SYSTEMS AND ENSURE THAT THESE DOORS CAN BE REMOVED AND
 PROVIDE AND APPLICATION NOTE OR LETTE FROM THE EOR.
  
  
  
  
 3) LIFE SAFETY SHEETS - IN ADDITION TO THE ABOVE
 COMMENT, DOES ANY OF THE PROPOSED CONSTRUCTION PHASES
 INTERFERE WITH THE EXISTING ENGINEERED LIFE SAFETY
 EQUIPMENT/FEATURES OF THE OCCUPANCY.
  
 IS THERE SMOKE CONTROL, SMOKE BARRIERS,
 PRESSURIZATIONS, EVACUATION SYSTEMS THAT MAY OR WILL BE
 COMPROMISED BY THIE PROPOSED CONSTRUCTION?
  
 PLEASE PROVIDE A DETAILED REVIEW OF ALL PHASES AND/OR
 PROVIDE FOR THE CORRECTION OR MAINTENANCE OF THESE
 SYSTEMS.
  
  
  
  
 4) F 111.A - THE FFP PAGE TITLE SHOWS ONLY PHASE 1 - A;
 HOWEVER, ALL PHASES APPEAR TO BE DRAWN.
  
 EACH PHASE SHOULD BE DETAILED ON HOW IT WILL BE
 ISOLATED OR CONTROLLED TO MAINTAIN FUNCTION THROUGHOUT
 CONTRUCTION.
  
 PLEASE REVIEW, CLARIFY OR CORRECT.
  
  
  
  
 5) SHEET E 001 - UNDER DEMOLITION GENERAL NOTES AND
 GENERAL NOTES, THERE IS/ARE NO INDICATIONS OF FIRE
 ALARM WORK. THE FIRE ALARM SHALL BE MAINTAINED
 THROUGHOUT CONTRUCTION. ALL WORK SHALL BE DONE BY
 CERTIFIED LIFE SAFETY CONTRACTORS UNDER SEPARATE SHOP
 DRAWINGS. BASED ON THE SEPARATION OF AREAS AND PHASES,
 ADDITIONAL DEVICES MAY BE REQUIRED FOR CODE COVERAGE
 PURPOSES.
  
 PLEASE REVIEW AND PROVIDE AND APPLICABLE NOTE.
  
  
  
 6) SHEET E 109 - THERE ARE TWO NOTE TAGE; 0.99.1 &
 0.98.1, THAT DO NOT APPEAR TO HAVE AN OBVIOUS
 EXPLANATION DETAIL OF DEFINITION. WHAT DOES THESE
 INDICATE.
  
 PLEASE CLARIFY.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-08 Cont ID  
Sent By cpuell Date 2018-01-08 Time 17:02 Rev Time 0.00
Received By cpuell Date 2017-12-13 Time 13:34 Sent To  
Notes
2017-12-14 13:34:55C27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-13 Cont ID  
Sent By gjohnson Date 2017-11-13 Time 09:45 Rev Time 0.00
Received By gjohnson Date 2017-10-13 Time 13:11 Sent To  
Notes
2017-10-16 13:11:43C33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-28 Time   Rev Time 0.00
Received By cpuell Date 2017-06-01 Time 08:44 Sent To  
Notes
2017-06-02 08:44:21C27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-12-19 Cont ID  
Sent By jwitmer Date 2017-12-19 Time 17:12 Rev Time 0.00
Received By jwitmer Date 2017-12-19 Time 17:10 Sent To  
Notes
2017-12-19 17:12:44PALM BEACH COUNTY IMPACT FEE OFFICE
 RECEIPT NUMBER: 2017-1122-230
 MU-2017-032098-0000
 FEES PAID: $21,352.16
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-10-26 Cont ID  
Sent By jwitmer Date 2017-10-26 Time 08:50 Rev Time 0.00
Received By jwitmer Date 2017-10-26 Time 08:50 Sent To  
Notes
2017-10-26 08:51:041) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-06-27 Cont ID  
Sent By jwitmer Date 2017-06-27 Time 16:32 Rev Time 0.00
Received By jwitmer Date 2017-06-27 Time 16:31 Sent To  
Notes
2017-06-27 16:32:14BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-01-05 Cont ID  
Sent By ccole Date 2018-01-05 Time 12:21 Rev Time 0.00
Received By ccole Date 2018-01-05 Time 10:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-02 Cont ID  
Sent By ccole Date 2017-11-02 Time 11:45 Rev Time 0.00
Received By ccole Date 2017-11-02 Time 11:45 Sent To  
Notes
2017-11-02 12:19:192ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17060065
 11/2/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 IT APPEARS THAT ONLY ONE UPDATED SET OF MECHANICAL
 PLANS WAS SUBMITTED IN THE CORRECTED PLAN SETS. THAT
 REVISED SET HAS THE ENGINEER'S SEAL DATED 10/6/17
 AFFIXED. I HAVE REVIEWED THAT SET ALONG WITH THE
 SUBMITTED NARRATIVE RESPONSE TO 1ST REVIEW COMMENTS
 FROM HUNTONBRADY AND HAVE FOUND DEFIICENCIES. PLEASE
 REFER TO 1ST REVIEW COMMENTS WHICH I HAVE ITEMIZED
 BELOW.
  
 COMMENT #1: COMMISSIONING PLAN NOT PROVIDED.
  
 #2) SMOKE DETECTORS NOT SHOWN ON SHEET M111 AS
 INDICATED IN THE NARRATIVE.
  
 #3) MATERIALS TO BE STORED IN DIS-PREP STORAGE ROOM NOT
 IDENTIFIED, AND STORAGE EXHAUST NOT PROVIDED AS
 INDICATED IN THE NARRATIVE.
  
 #4) THE ROOFTOP MECHANICAL EQUIPMENT CURB AND BASE
 ATTACHMENTS TO THE ROOF STRUCTURE HAVE NOT BEEN
 PROVIDED FOR THE ROOF UPBLAST FAN, AND THE ISOLATION
 ROOM FAN. PLEASE CLARIFY IF THE ISOLATION ROOM AND THE
 DECON ROOM ARE ONE IN THE SAME, OR IF THERE IS A ROOM
 DESIGNATED AS ISOLATION ROOM SOMEWHERE ELSE ON THE
 PLAN- I CANNOT LOCATE IT.
  
 #5) PLEASE ADD OUTDOOR AHU SOUND LEVEL NOTE TO THE
 PLANS.
  
 #6) NOTE #20 ON THE REVISED SHEET M121 IS NOT ON THE
 PLAN AS INDICATED IN THE NARRATIVE.
  
 #8) THE DESIGN PARAMETER TABLE SHOWING THE ROOM-TO-ROOM
 PRESSURE RELATIONSHIPS ON SHEET M111 HAS NOT BEEN
 PROVIDED AS INDICATED IN THE NARRATIVE.
  
 #9) THE REVISED ENERGY COMPLIANCE FORM SHOWING THE
 WATER HEATER AND PIPING SYSTEM COMPLIANCE DATA HAS NOT
 BEEN PROVIDED.
  
 1) NEW COMMENT: REFER TO SECTION 449.3.6.5 FBC-14
 BUILDING AS IT APPLIES TIO THE NEW TRAUMA CENTER. IT
 APPEARS THAT VARIABLE-AIR VOLUME SYSTEMS MAY NOT BE
 PERMITTED FOR USE IN THE DECON ROOM AND POSSIBLY THE
 TRAUMA ROOMS- PLEASE CLARIFY THE USE OF THESE ROOMS
 WHAT PROCEDURES ARE PERFOMED IN EACH.
  
 2) NEW COMMENT: PROVIDE PRODUCT DATA FOR THE DUCTWORK
 IN THE TRAUMA ROOM ON THE PLANS, AND PROVIDE A
 SUBMITTAL REVIEWED BY THE DESIGN PROFESSIONALS OF
 RECORD.
  
 3) NEW COMMENT: PLEASE REVIEW SECTION 2.1-8.2.4.3(2) IN
 THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH
 CARE FACILITIES. IT APPEARS THAT ANESTHESIA SCAVENGING
 SYSTEMS NEED TO BE INSTALLED IN THE TRAUMA ROOMS.
 PLEASE COMPLY.
  
 4) NEW COMMENT: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE EXHAUST DUCT WRAP. PLEASE CLARIFY WHAT FUMES OR
 GASES ARE BEING EXHAUSTED FROM THE ROOM AND WHY THE
 EXHAUST DUCT NEEDS TO BE WRAPPED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-28 Cont ID  
Sent By ccole Date 2017-06-28 Time 16:22 Rev Time 0.00
Received By ccole Date 2017-06-28 Time 14:32 Sent To  
Notes
2017-06-28 17:26:151ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #17060065
 6/28/17
  
 PLAN REVIEW RESULT: DENIED
  
 1) PROVIDE A COMMISSIONING PLAN- SECTION C408.2.1
 FBC-14 ENERGY CONSERVATION.
  
 2) SHOW THE LOCATIONS OF THE REQUIRED SMOKE DETECTORS
 IN THE RETURN AIR SYSTEMS OF AHU-G-1 & G-2- SECTION
 606.2.1.
  
 3) INDICATE WHAT MATERIALS ARE BEING STORED IN THE DIS
 PREP STOR ROOM TG322. WILL MEDICAL GAS BE STORED IN THE
 ROOM OR ANY OTHER NEW ROOMS OR SPACES? PLEASE NOTE A
 LOCAL EXHAUST SYSTEM MAY BE REQUIRED.
  
 4) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 ALL THE ROOFTOP MECHANICAL EQUIPMENT INCLUDING THE
 AHU'S AND CURBS, THE EF'S AND CURBS, THE DUCTWORK AND
 SUPPORT BRACKETS- SECTION 301.15.
  
 5) PROVIDE THE ANTICIPATED DBA LEVEL OF THE NEW ROOFTOP
 AHU'S AND FANS IN ACCORDANCE WITH SECTION
 2.1-8.2.1.1(6)(A) GUIDELINES FOR DESIGN AND
 CONSTRUCTION OF HEALTH CARE FACILITIES.
  
 6) INDICATE THE HEIGHT OF THE AHU AIR INLETS ABOVE THE
 ROOF LEVEL- SEE SECTION 6-3.1 ASHRAE 170.
  
 7) PROVIDE SPECIFICATIONS FOR THE ROOF TOP DUCTWORK AND
 INSULATION, AND THE CHILLED AND STEAM WATER PIPING AND
 INSULATIONS.
  
 8) PLEASE INCLUDE THE PRESSURE RELATIONSHIPS, AND
 EXHAUST AND RECIRCULATION PARAMETERS FOR ALL ROOMS AND
 SPACES IN THE ASHRAE 170, 62.1 CALCULATION SUBMITTAL.
 IT MAY BE HELPFUL TO PLACE THE TABLES ON THE MECHANICAL
 PLANS.
  
 9) PROVIDE THE WATER HEATER AND PIPING SYSTEM
 COMPLIANCE DATA IN THE ENERGYGAUGE SUBMITTAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-11-13 Cont ID  
Sent By gjohnson Date 2017-11-13 Time 09:44 Rev Time 0.00
Received By gjohnson Date 2017-11-09 Time 10:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-28 Cont ID  
Sent By gjohnson Date 2017-06-28 Time 10:53 Rev Time 0.00
Received By gjohnson Date 2017-06-27 Time 15:58 Sent To  
Notes
2017-06-28 13:41:541ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE RELOCATED VENT TERMINAL NEXT TO NEW MECHANICAL
 RM TG326 SHALL COMPLY-WITH FBC PL 903.5 LOCATION OF
 VENT TERMINAL.
 AN OPEN VENT TERMINAL FROM A DRAINAGE SYSTEM SHALL NOT
 BE LOCATED DIRECTLY BENEATH ANY DOOR, OPENABLE WINDOW,
 OR OTHER AIR INTAKE OPENING OF THE BUILDING OR OF AN
 ADJACENT BUILDING, AND ANY SUCH VENT TERMINAL SHALL NOT
 BE WITHIN 10 FEET (3048 MM) HORIZONTALLY OF SUCH AN
 OPENING UNLESS IT IS 3 FEET (914 MM) OR MORE ABOVE THE
 TOP OF SUCH OPENING.
  
 903.6 EXTENSION THROUGH THE WALL.
 VENT TERMINALS EXTENDING THROUGH THE WALL SHALL
 TERMINATE AT A POINT NOT LESS THAN 10 FEET (3048 MM)
 FROM A LOT LINE AND NOT LESS THAN 10 FEET (3048 MM)
 ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS SHALL NOT
 TERMINATE UNDER THE OVERHANG OF A STRUCTURE WITH SOFFIT
 VENTS. SIDE WALL VENT TERMINALS SHALL BE PROTECTED TO
 PREVENT BIRDS OR RODENTS FROM ENTERING OR BLOCKING THE
 VENT OPENING.
  
 2. HOLDING TANK FOR DECON SHOWER.
 A) HOW WILL THIS TANK BE EMPTIED OUT AND WHEN WILL THE
 TANK BE EMPTIED.
 B) PLEASE PROVIDE MANUFACTURE SPECIFICATION ON THE TANK
 AND WATER LEVEL SENSOR.
 C) WHAT TYPE OF CHEMICALS COULD BE INTRODUCED INTO THE
 TANK.
 PER WPB AMEND TP FBC 107.2.1
  
 3. PLEASE PROVIDE TRAP PRIMER FOR THE FLOOR DRAIN IN
 THE DECON SHOWER. PER FBC PL 1002.4
  
 4, PLEASE PROVIDE A MEDICAL GAS RISER. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 TEMPERED WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. PER FBC PL 416.5
  
 6. LABEL FIXTURES ON RISER FOR BATHROOM TG337. PER WPB
 AMEND TP FBC 107.2.1
  
 7. THE BRANCH DRAIN FOR THE BREAKROOM SINK SHALL
 CONNECT TO BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP
 TG337. PER FBC PL 912.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-01-08 Cont ID  
Sent By LL Date 2018-01-08 Time   Rev Time 0.00
Received By llouie Date 2018-01-08 Time   Sent To  
Notes
2018-01-08 15:36:39ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) SEPERATE LANDSCAPE PERMIT AND REVIEW REQUIRED PRIOR
 TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.)
  
 REFERENCE: PB 1753/Z17070020

Review Stop Z ZONING
Rev No 2 Status F Date 2017-10-27 Cont ID  
Sent By llouie Date 2017-10-27 Time   Rev Time 0.00
Received By llouie Date 2017-10-27 Time   Sent To  
Notes
2017-10-27 08:09:02** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SURVEY OF THE PROPERTY IS REQUIRED.
  
 2.) PROVIDE A SITE PLAN SHOWING THE AREA OF WORK. THERE
 ARE MULTIPLE BUILDINGS ON THE PROPERTY WHICH MAKES IT
 VERY DIFFICULT TO DETERMINE WHERE THE SCOPE OF WORK
 WILL OCCUR.
  
 3.) ADDITIONAL INFORMATION IS REQUIRED ON THE TOTAL
 SQUARE FOOTAGE ADDED TO THE EXISTING BUILDING. PLEASE
 NOTE THAT ANY INCREASE IN THE TOTAL BUILDING SQUARE
 FOOTAGE BY MORE THAN 5% SHALL REQUIRE A MAJOR AMENDMENT
 TO THE CSPD. [6/21/17 REPEAT COMMENT]
  
 4.) SITE PLAN CALCULATIONS, INCLUDING:
 EXISTING/PROPOSED LAND USE AND ZONING; TOTAL ACRES OF
 THE PROJECT; EXISTING/PROPOSED BUILDING SQUARE FOOTAGE;
 PERCENT OF OPEN SPACE, LANDSCAPING BUILDING COVERAGE
 AND IMPERMEABLE SURFACE; PARKING COMPUTATIONS (I.E.
 PARKING REQUIRED, PROVIDED, ETC.); FLOOR AREA RATIO
 (FAR). [6/21/17 REPEAT COMMENT]
  
 5.) AN AMENDMENT TO THE ST. MARY'S COMMUNITY SERVICE
 PLANNED DEVELOPMENT (CSPD) IS REQUIRED. THIS PROCESS
 MUST BE COMPLETED WITH THE PLANNING DIVISION PRIOR TO
 BUILDING PERMIT. THE 2017 DEVELOPMENT APPLICATION IS
 AVAILABLE AT: HTTP://WWW.WPB.ORG/DEPARTMENTS/DEVELOPMEN
 T-SERVICES/FORMS/PLANNING-ZONING-FORMS [6/21/17 REPEAT
 COMMENT]
  
 NOTES:
  
 * ZONE: CSPD
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By llouie Date 2017-06-21 Time   Rev Time  
Received By llouie Date 2017-06-21 Time   Sent To  
Notes
2017-06-21 16:59:34** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ADDITIONAL INFORMATION IS REQUIRED ON THE TOTAL
 SQUARE FOOTAGE ADDED TO THE EXISTING BUILDING. PLEASE
 NOTE THAT ANY INCREASE IN THE TOTAL BUILDING SQUARE
 FOOTAGE BY MORE THAN 5% SHALL REQUIRE A MAJOR AMENDMENT
 TO THE CSPD.
  
 2.) SITE PLAN CALCULATIONS, INCLUDING:
 EXISTING/PROPOSED LAND USE AND ZONING; TOTAL ACRES OF
 THE PROJECT; EXISTING/PROPOSED BUILDING SQUARE FOOTAGE;
 PERCENT OF OPEN SPACE, LANDSCAPING BUILDING COVERAGE
 AND IMPERMEABLE SURFACE; PARKING COMPUTATIONS (I.E.
 PARKING REQUIRED, PROVIDED, ETC.); FLOOR AREA RATIO
 (FAR)
  
 3.) AN AMENDMENT TO THE ST. MARY'S COMMUNITY SERVICE
 PLANNED DEVELOPMENT (CSPD) IS REQUIRED. THIS PROCESS
 MUST BE COMPLETED WITH THE PLANNING DIVISION PRIOR TO
 BUILDING PERMIT. THE 2017 DEVELOPMENT APPLICATION IS
 AVAILABLE AT: HTTP://WWW.WPB.ORG/DEPARTMENTS/DEVELOPMEN
 T-SERVICES/FORMS/PLANNING-ZONING-FORMS
  
 NOTES:
  
 * ZONE: CSPD
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved