 |
Plan Review Details - Permit 17060065
| Plan Review Stops For Permit 17060065 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-12-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-12-20 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-12-19 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2017-12-19 17:31:18 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17060065 | | | ADD: 901 45TH ST. | | | CONT: WESTBROOKE CORP | | | TEL: 561-395-4126 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: TUES. DEC. 19/2017 | | | | | | ACTION: BUILDING PROVISO | | | | | | 1) RESIDENT INSPECTOR FORMS SUBMITTED ON 11/01/2017 | | | UNDER SUBMITTAL: 17110018 AND ROUTED TO KEN CONRAD BY | | | JS. | | | | | | 2) BUILDING PROVISO / DEFERRED SUBMITTALS: SHEET S121 | | | CONSTRUCTION NOTE NUMBER 1 INDICATES THE ARCHITECTURAL | | | ALUMINUM CANOPY DECK, SOFFIT AND FASCIA ARE | | | PRE-ENGINEERED. PLEASE SUBMIT TO THE DESIGNER OF RECORD | | | FOR REVIEW, SHOP DRAWING STAMP OF APPROVAL BEFORE BEING | | | FORWARDED TO THE BUILDING DEPARTMENT. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 3) BUILDING PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B | | | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 | | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 | | | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR | | | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS, ROOF TOP INTAKE AND EXHAUST FANS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | | | | SUBMITTED PRODUCT APPROVALS: | | | FL 12400.3 FLUSH OUTSWING DOOR | | | FL20701-R1 SWINGING EXTERIOR DOOR | | | FL 16392-R2 1006 SERIES ELECTRIC STRIKE | | | FL 14313-R5 CURTAIN WALL | | | NOA 15-0226.03 STO THERM CI LM 180 CMU EFIS SYSTEM | | | | | | 4) BUILDING PROVISO / DEFERRED SUBMITTAL: FBC 107.3.4.1 | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED | | | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 5) BUILDING PROVISO / DEFERRED SUBMITTAL: ROOFING: FOR | | | ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING | | | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF | | | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF | | | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. | | | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH | | | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE | | | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION | | | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. | | | 1609.6.4.4.1 COMPONENTS & CLADDING. | | | | | | 6) BUILDING PROVISO / DEFERRED SUBMITTAL / DELEGATE | | | SESIGN ) SHEET M301 ROOF TOP CURB AND EQUIPMENT TIE | | | DOWN NOTE: | | | ALL SUPPORTS SHALL BE IN COMPLIANCE WITH FBC/FMC 2014 | | | AND THE HURRICANE CODES TO WITHSTAND WIND AND IMPACT | | | LOADS AND DESIGNED BY A FLORIDA REGISTERED STRUCTURAL | | | ENGINEER. SUBMIT CALCULATIONS FOR REVIEW. SEE | | | STRUCTURAL DRAWINGS FOR THE WIND DESIGN CRITERIA, | | | PLEASE PROVIDE. 107.2.1.3 ADDITIONAL INFORMATION | | | REQUIRED. LATERAL FORCE-RESISTING SYSTEM | | | FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, | | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | | 2014 FBC-B 1604.4 ANALYSIS. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-10-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-10-26 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-10-25 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2017-10-26 08:56:51 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17060065 | | | ADD: 901 45TH ST. | | | CONT: WESTBROOKE CORP | | | TEL: 561-395-4126 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: THURS. OCT. 26/2017 | | | ACTION: DENIED | | | | | | | | | PLANS APPEAR TO BE CODE COMPLIANT, STAMPED NEED | | | RESIDENT INSPECTOR FORMS TO PASS INTHE COMPUTER | | | PROGRAM> | | | 10/26/2017 | | | | | | | | | 1) COMPLIED. | | | | | | 2) BUILDING PROVISO / DEFERRED SUBMITTALS: SHEET S121 | | | CONSTRUCTION NOTE NUMBER 1 INDICATES THE ARCHITECTURAL | | | ALUMINUM CANOPY DECK, SOFFIT AND FASCIA ARE | | | PRE-ENGINEERED. PLEASE SUBMIT TO THE DESIGNER OF RECORD | | | FOR REVIEW, SHOP DRAWING STAMP OF APPROVAL BEFORE BEING | | | FORWARDED TO THE BUILDING DEPARTMENT. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 3) 2ND REVIEW. THE CONTRACTOR ELECTS TO USE A RESIDENT | | | INSPECTOR FORMS WILL BE E-MAILED TO: | | | [email protected] SENT 10/25/2017 04:28 PM. | | | | | | 3A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL | | | PARTIES NOTARIZED AND RETURNED TO THE BUILDING | | | DEPARTMENT. | | | | | | 3B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW MAY BE SCHEDULED. | | | | | | 3C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 3D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE | | | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND | | | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO | | | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR | | | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP | | | INSPECTORS. | | | | | | 3E) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 AND | | | GUIDELINES AND POLICIES FOR PROJECTS CONCERNING | | | RESIDENT INSPECTORS. COMMENT # 14. 3 COPIES OF ALL SHOP | | | DRAWINGS (HANDRAILS, PRECAST JOINT AND SLABS, PRODUCT | | | APPROVALS, TRUSSES, BAR JOIST, ETC.) MUST BE SUBMITTED | | | TO THE BUILDING DEPARTMENT. TWO REVIEWED SETS OF | | | DOCUMENTS WILL BE RETURNED TO THE JOB SITE BEFORE ANY | | | OF THE ABOVE ARE INSTALLED ON THE JOB. | | | | | | 3F) INFORMATION ONLY. PLEASE CALL THE CITY OF WEST PALM | | | BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS. | | | | | | 4)BUILDING PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B | | | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 | | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 | | | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR | | | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS, ROOF TOP INTAKE AND EXHAUST FANS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | SUBMITTED PRODUCT APPROVALS: | | | FL 12400.3 FLUSH OUTSWING DOOR | | | FL20701-R1 SWINGING EXTERIOR DOOR | | | FL 16392-R2 1006 SERIES ELECTRIC STRIKE | | | FL 14313-R5 CURTAIN WALL | | | NOA 15-0226.03 STO THERM CI LM 180 CMU EFIS SYSTEM | | | | | | 5) BUILDING PROVISO / DEFERRED SUBMITTAL: FBC 107.3.4.1 | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED | | | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 6) BUILDING PROVISO / DEFERRED SUBMITTAL: ROOFING: FOR | | | ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING | | | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF | | | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF | | | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. | | | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH | | | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE | | | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION | | | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. | | | 1609.6.4.4.1 COMPONENTS & CLADDING. | | | | | | 7) BUILDING PROVISO / DEFERRED SUBMITTAL / DELEGATE | | | SESIGN ) SHEET M301 ROOF TOP CURB AND EQUIPMENT TIE | | | DOWN NOTE: | | | ALL SUPPORTS SHALL BE IN COMPLIANCE WITH FBC/FMC 2014 | | | AND THE HURRICANE CODES TO WITHSTAND WIND AND IMPACT | | | LOADS AND DESIGNED BY A FLORIDA REGISTERED STRUCTURAL | | | ENGINEER. SUBMIT CALCULATIONS FOR REVIEW. SEE | | | STRUCTURAL DRAWINGS FOR THE WIND DESIGN CRITERIA, | | | PLEASE PROVIDE. 107.2.1.3 ADDITIONAL INFORMATION | | | REQUIRED. LATERAL FORCE-RESISTING SYSTEM | | | FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, | | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | | 2014 FBC-B 1604.4 ANALYSIS. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-06-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-06-27 |
Time |
16:31 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2017-06-24 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2017-06-27 16:31:26 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17060065 | | | ADD: 901 45TH ST. | | | CONT: WESTBROOKE CORP | | | TEL: 561-395-4126 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUES. JUNE 27/2017 | | | ACTION: DENIED | | | | | | 1) THE PLANS INDICATE NEW ADDITIONS TO THE HOSPITAL BUT | | | THERE WAS NO SOILS REPORT SUBMITTED THIS REVIEW. 2014 | | | FBC-B 803.5.2 QUESTIONABLE SOIL. | | | | | | 2) SHEET S121 CONSTRUCTION NOTE NUMBER 1 INDICATES THE | | | ARCHITECTURAL ALUMINUM CANOPY DECK, SOFFIT AND FASCIA | | | ARE PRE-ENGINEERED. PLEASE SUBMIT TO THE DESIGNER OF | | | RECORD FOR REVIEW, SHOP DRAWING STAMP OF APPROVAL | | | BEFORE BEING FORWARDED TO THE BUILDING DEPARTMENT. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 3) THE CANOPY, NEW X-RAY, RADIATION ROOMS, OFFICES AND | | | TRAUMA UNIT ADDITIONS SHOW STEEL BEAMS & BOLTED | | | CONNECTIONS OR WELDED CONNECTIONS. THE CONTRACTOR IS | | | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & | | | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN | | | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF | | | INSPECTION. | | | 2014 FBC-B 2204.1 WELDING | | | 2014 FBC-B 2204.2 BOLTING. | | | | | | IF THE CONTRACTOR PREFERS THE USE OF A RESIDENT | | | INSPECTOR FOR THE EFFICIENCY OF THE JOB, PLEASE PROVIDE | | | DOCUMENTATION IN THE COMMENT RESPONSE NARRATIVE. THIS | | | WILL REQUIRE RESIDENT INSPECTORS FORMS, AND ALSO 3 SETS | | | OF PLANS. | | | | | | 4) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS, ROOF TOP INTAKE AND EXHAUST FANS | | | (G) PRE-ENGINEERED A/C STANDS | | | IF THE CONTRACTOR WISHES TO DEFER THE PRODUCT APPROVALS | | | UNTIL AFTER PERMIT ISSUANCE PLEASE INFORM THROUGH THE | | | COMMENT RESPONSE. | | | | | | 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE | | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND | | | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B | | | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE | | | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S | | | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE | | | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED | | | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. | | | | | | 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY | | | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES | | | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL | | | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF | | | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR | | | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN | | | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. | | | CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA | | | REGISTERED PROFESSIONAL ENGINEER OR REGISTERED | | | ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING. | | | | | | 8) SHEET A201, A231, A241 & A242 ALL SHOW THE | | | INSTALLATION OF EFIS SYSTEMS. : PLEASE PROVIDE THE | | | PRODUCT APPROVAL FOR THE SYSTEM TO BE INSTALLED. PLEASE | | | ALSO PROVIDE THE MANUFACTURERS INSTALLATION BROCHURE | | | PROVIDING COMPLIANCE WITH 2014 FBC-B SECTIONS; | | | 1408.2 PERFORMANCE CHARACTERISTICS. | | | 1408.2 PERFORMANCE CHARACTERISTICS. | | | 1408.3 STRUCTURAL DESIGN. | | | 1408.4 WEATHER RESISTANCE. | | | 1408.4.1 EIFS WITH DRAINAGE. | | | 408.4.1.1 WATER-RESISTIVE BARRIER. | | | 1408.5 INSTALLATION. | | | | | | 9) SHEET M301 ROOF TOP CURB AND EQUIPMENT TIE DOWN | | | NOTE: | | | ALL SUPPORTS SHALL BE IN COMPLIANCE WITH FBC/FMC 2014 | | | AND THE HURRICANE CODES TO WITHSTAND WIND AND IMPACT | | | LOADS AND DESIGNED BY A FLORIDA REGISTERED STRUCTURAL | | | ENGINEER. SUBMIT CALCULATIONS FOR REVIEW. SEE | | | STRUCTURAL DRAWINGS FOR THE WIND DESIGN CRITERIA, | | | PLEASE PROVIDE. 107.2.1.3 ADDITIONAL INFORMATION | | | REQUIRED. LATERAL FORCE-RESISTING SYSTEM | | | FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, | | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | | 2014 FBC-B 1604.4 ANALYSIS. | | | | | | | | | 10) SHEET A811 DETAIL A10 DETAILS TO X-RAY ROOMS AND | | | CONTROL ROOM AS WELL AS IN THE 4 TRAUMA UNITS. | | | . FBC-B 465.5.1 SHIELDING. EACH X-RAY FACILITY SHALL | | | HAVE PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS | | | NEEDED TO ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A | | | RADIATION DOSE IN EXCESS OF THE LIMITS SPECIFIED IN | | | PART III OF CHAPTER 64E-5, FLORIDA ADMINISTRATIVE CODE. | | | PLEASE SHOW COMPLIANCE WITH: | | | 10A) FBC-B 465.5.1.1 STRUCTURAL SHIELDING IN WALLS AND | | | OTHER VERTICAL BARRIERS REQUIRED FOR PERSONNEL | | | PROTECTION SHALL EXTEND WITHOUT BREACH FROM THE FLOOR | | | TO A HEIGHT OF AT LEAST 7 FEET (2.1 M). | | | | | | 10B) FBC-B 465.5.1.2 DOORS, DOOR FRAMES, WINDOWS AND | | | WINDOW FRAMES SHALL HAVE THE SAME LEAD EQUIVALENT | | | SHIELDING AS THAT REQUIRED IN THE WALL OR OTHER BARRIER | | | IN WHICH THEY ARE INSTALLED. | | | | | | 10C) FBC-B 465.5.1.3 PRIOR TO CONSTRUCTION, THE FLOOR | | | PLANS AND EQUIPMENT ARRANGEMENT OF ALL NEW | | | INSTALLATIONS, OR MODIFICATIONS OF EXISTING | | | INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND | | | ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE | | | SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND | | | APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER | | | REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE | | | FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR | | | RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN | | | INTO CONSIDERATION. | | | | | | 10D) 465.5.1.3.1 THE PLANS SHALL SHOW, AS A MINIMUM, | | | THE FOLLOWING. | | | | | | 465.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM'S | | | RADIATION PORT; THE PORT'S TRAVEL AND TRAVERSE LIMITS; | | | GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY | | | WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR'S | | | BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL. | | | | | | 465.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS | | | OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS, | | | FLOOR AND CEILING OF THE ROOM CONCERNED. | | | | | | 465.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED. | | | | | | 465.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT | | | AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM | | | CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE | | | TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS | | | MAY BE PRESENT. | | | | | | 465.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT | | | AND THE MAXIMUM TECHNIQUE FACTORS. | | | | | | 465.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS | | | WHICH WILL BE PERFORMED WITH THE EQUIPMENT. | | | | | | 10E) 465.6 DOORS, INTERLOCKS, AND WARNING SYSTEMS. | | | | | | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 12 ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-01-05 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-01-05 |
Time |
08:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-11-12 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-12 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-12 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2017-11-12 13:32:12 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS: 2ND REVIEW. ITEMS CORRECTED | | | ARE NOTED. REMAINING ITEMS HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. | | | | | | 1. CORRECTED. | | | 2.CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. CORRECTED. | | | 8. CORRECTED. | | | 9. CORRECTED. | | | 10. CORRECTED. | | | 11. WITH THE CURRENT LOAD CALCULATION PROVIDED, IT | | | APPEARS GENERATOR #1 IS OVERLOADED. PANEL TESB SHOWS A | | | DEMAND OF 1027.3 KVA AND THE GENERATOR IS RATED FOR | | | 1000. IF ANY CORRECTIONS TO LOAD CALCULATIONS FROM | | | ABOVE COMMENTS RESULT IN ADDITIONAL LOAD, THEN THIS | | | WILL INCREASE THE OVERLOAD. PROVIDE CLARIFICATION | | | AND/OR CORRECTION. FBC 107.2.1, NEC 517.30(D) (RESPONSE | | | PROVIDED STATED: "WILL COMPLY. EXISTING LOADS HAVE TO | | | BE DEMANDED PROPERLY." GENERATOR MUST HAVE SUFFICIENT | | | CAPACITY AND PROPER RATING TO MEET THE DEMAND PRODUCED | | | BY THE LOAD OF THE ESSENTIAL SYSTEM AT ANY GIVEN TIME. | | | PROVIDE ADDITIONAL DETAILS TO SHOW GENERATOR IS SIZED | | | SUFFICIENTLY TO HANDLE THE LOAD, INCLUDE STARTING | | | CURRENT REQUIRED OF FIRE PUMP.) NEC 517.30(D), | | | 695.3(D)(1) | | | 12. CORRECTED. | | | 13. CORRECTED. | | | 14. CORRECTED. | | | 15. CORRECTED. | | | 16. INDICATE PANEL BOARD BONDING REQUIRED. NEC 517.14 | | | (NO RESPONSE PROVIDED.) | | | 17. CORRECTED. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-06-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-06-27 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-26 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2017-06-27 10:45:53 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS: | | | | | | 1. THE DEMAND AMPS/KVA FOR PANEL EGLB1 EXCEED THE | | | CAPACITY OF TRANSFORMER T-EGLB1. PROVIDE CORRECTION. | | | NEC 517.30(D); 230.79 | | | 2. PROVIDE PANEL SCHEDULE FOR PANEL QDP-B. NEC 408.4; | | | 215.5; FBC 107.2.1 | | | 3. SHEET E802, PANEL TDP1, LOAD CALCULATION PROVIDED | | | SHOWS X-RAY LOAD WITH A 19.17% DEMAND FACTOR, AND | | | RECEPTACLE LOAD WITH A 78.41% DEMAND FACTOR. PROVIDE | | | CODE SECTION FROM THE NEC WHERE THESE DEMAND FACTORS | | | ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS. NEC 220; | | | FBC 107.2.1 | | | 4. SHEET E805, PANEL XRH, LOAD CALCULATION PROVIDED | | | SHOWS X-RAY LOAD WITH A 37.5% DEMAND FACTOR. PROVIDE | | | CODE SECTION FROM THE NEC WHERE THESE DEMAND FACTORS | | | ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS. NEC 220; | | | FBC 107.2.1 | | | 5. SEVERAL PANEL SCHEDULES SHOW THE LIGHTING DEMAND | | | FACTOR AT 40% (EXAMPLE PANEL CGHC2 AND GHC2). THE NOTE | | | AT THE BOTTOM OF TABLE 220.42 STATES THAT THIS DEMAND | | | FACTOR SHOULD NOT BE USED WHERE IT IS LIKELY THE | | | LIGHTING WILL BE ON AT THE SAME TIME, SUCH AS THE | | | TRAUMA ROOMS. PROVIDE CLARIFICATION FOR THIS DEMAND | | | FACTOR, INDICATING ANY AREAS WHERE LIGHTING WILL BE | | | USED AT THE SAME TIME. FBC 107.2.1; NEC TABLE 220.42 | | | 6. SHEET E801 AND E802, ISOLATION PANELS T1A, T1B, T2A, | | | T2B, T3A, T3B, T4A, T4B: NOTE STATES THAT THE BRANCH | | | CIRCUITS WILL BE ON A 2 POLE BREAKER, BUT THIS IS NOT | | | REFLECTED IN THE PANEL SCHEDULE. PROVIDE CORRECTION TO | | | ACCURATELY REFLECT THE PANEL LAYOUT. FBC 107.2.1; NEC | | | 408.4 | | | 7. SHEET E803, PANEL EQH1, LOAD CALCULATION PROVIDED | | | SHOWS THE MOTOR LOAD WITH A 118.49% DEMAND FACTOR, AND | | | THE COOLING LOAD WITH A 85% DEMAND FACTOR. PROVIDE CODE | | | SECTION FROM THE NEC WHERE THESE DEMAND FACTORS ARE | | | LOCATED AND/OR CORRECT THE DEMAND FACTORS. NEC 220; FBC | | | 107.2.1 | | | 8. SHEET E803, PANEL EQL1, LOAD CALCULATION PROVIDED | | | SHOWS THE COOLING LOAD WITH A 85% DEMAND FACTOR. | | | PROVIDE CODE SECTION FROM THE NEC WHERE THESE DEMAND | | | FACTORS ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS. | | | NEC 220; FBC 107.2.1 | | | 9. SHEET E804, PANEL TMSB, LOAD CALCULATION PROVIDED | | | SHOWS THE RECEPTACLE LOAD WITH A 51.04% DEMAND FACTOR, | | | THE MOTOR LOAD WITH A 118.49% DEMAND FACTOR, THE | | | COOLING LOAD WITH A 85% DEMAND FACTOR, AND THE X-RAY | | | LOAD WITH A 19.17% DEMAND FACTOR. PROVIDE CODE SECTION | | | FROM THE NEC WHERE THESE DEMAND FACTORS ARE LOCATED | | | AND/OR CORRECT THE DEMAND FACTORS. NEC 220; FBC 107.2.1 | | | 10. SHEET E804, PANEL TESB, LOAD CALCULATION PROVIDED | | | SHOWS RECEPTACLE LOAD WITH A 51.06% DEMAND FACTOR, THE | | | MOTOR LOAD WITH A 118.49% DEMAND FACTOR, THE COOLING | | | LOAD WITH A 85% DEMAND FACTOR, AND THE X-RAY LOAD WITH | | | A 19.17% DEMAND FACTOR. PROVIDE CODE SECTION FROM THE | | | NEC WHERE THESE DEMAND FACTORS ARE LOCATED AND/OR | | | CORRECT THE DEMAND FACTORS. NEC 220; FBC 107.2.1 | | | 11. WITH THE CURRENT LOAD CALCULATION PROVIDED, IT | | | APPEARS GENERATOR #1 IS OVERLOADED. PANEL TESB SHOWS A | | | DEMAND OF 1027.3 KVA AND THE GENERATOR IS RATED FOR | | | 1000. IF ANY CORRECTIONS TO LOAD CALCULATIONS FROM | | | ABOVE COMMENTS RESULT IN ADDITIONAL LOAD, THEN THIS | | | WILL INCREASE THE OVERLOAD. PROVIDE CLARIFICATION | | | AND/OR CORRECTION. FBC 107.2.1, NEC 517.30(D) | | | 12. SHEET E804, PANEL QDP, LOAD CALCULATION PROVIDED | | | SHOWS THE MOTOR LOAD WITH A 118.49% DEMAND FACTOR. | | | PROVIDE CODE SECTION FROM THE NEC WHERE THESE DEMAND | | | FACTORS ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS. | | | NEC 220; FBC 107.2.1 | | | 13. PROVIDE AUTOMATIC LIGHTING CONTROLS FOR INTERIOR | | | LIGHTING PER THE FLORIDA BUILDING CODE ENERGY | | | CONSERVATION. FBC C401.2.1, C405 | | | 14. SHEET E901, LIGHTING CONTACTOR DETAIL SHOWS A | | | PHOTOCELL CONTROLLING THE CONTACTOR. ENERGY CODE | | | STATES: "EXTERIOR LIGHTING CONTROLS. LIGHTING NOT | | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND | | | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS". PROVIDE | | | CORRECTION. FBC C405.2.4 | | | 15. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY | | | FBC C401.2 AND ASHREA 90.1: 8.4.2 | | | 16. INDICATE PANEL BOARD BONDING REQUIRED. NEC 517.14 | | | 17. SHEETS V106, V206, V306, V406, V506, V606: INDICATE | | | WHICH MODEL IS USED TO DETERMINE PROPER WIRING | | | REQUIREMENTS. FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-12-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-12-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-12-18 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-10-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-10-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-10-17 |
Time |
10:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-06-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-06-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-06-06 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2017-06-08 10:11:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET G 109 - THE LIFE SAFETY PLAN DOES NOT APPEAR | | | TO INDICATED EXIT CONDITIONS DURING CONSTRUCTION. THE | | | LIFE SAFETY PLAN MUST INDICATE HOW THE CONSTRUCTION | | | AREA WILL BE PROTECTED/SEPARATED FROM REGULAR BUSINESS | | | ACTIVITIES. | | | | | | WHAT EXITS WILL BE BLOCKED, HOW WILL THEY REROUTE | | | PEOPLE, WHAT IS/ARE THE PROPOSED OCCUPANCY LOADS | | | CHANGING BASED ON THE REROUTING, WILL FIRE ALARM | | | DEVICES/NOTIFICATIONS BE AFFECTED BY THE CONSTRUCTION | | | SEPARATIONS , NEW EXIT SIGNS, NEW EMERGENCY LIGHTING, | | | ETC. | | | | | | PLEASE PROVIDE DETAILED INDICATIONS AND NARRATIVES | | | RELATING TO THE ABOVE. | | | | | | | | | | | | 2) SHEET G 109 - THERE IS A NOTE INDICATING EXISTING DE | | | DOORS WILL BE REMOVED AT THE END OF PHASE 1A. HAVE | | | THESE DOORS BEEN ELVALUATED FOR THEIR FUNCTION RELATING | | | TO SMOKE CONTROL/BARRIERS? | | | | | | PLEASE REVIEW THE EXISTING LIFE SAFETY ENGINEERING | | | SYSTEMS AND ENSURE THAT THESE DOORS CAN BE REMOVED AND | | | PROVIDE AND APPLICATION NOTE OR LETTE FROM THE EOR. | | | | | | | | | | | | | | | 3) LIFE SAFETY SHEETS - IN ADDITION TO THE ABOVE | | | COMMENT, DOES ANY OF THE PROPOSED CONSTRUCTION PHASES | | | INTERFERE WITH THE EXISTING ENGINEERED LIFE SAFETY | | | EQUIPMENT/FEATURES OF THE OCCUPANCY. | | | | | | IS THERE SMOKE CONTROL, SMOKE BARRIERS, | | | PRESSURIZATIONS, EVACUATION SYSTEMS THAT MAY OR WILL BE | | | COMPROMISED BY THIE PROPOSED CONSTRUCTION? | | | | | | PLEASE PROVIDE A DETAILED REVIEW OF ALL PHASES AND/OR | | | PROVIDE FOR THE CORRECTION OR MAINTENANCE OF THESE | | | SYSTEMS. | | | | | | | | | | | | | | | 4) F 111.A - THE FFP PAGE TITLE SHOWS ONLY PHASE 1 - A; | | | HOWEVER, ALL PHASES APPEAR TO BE DRAWN. | | | | | | EACH PHASE SHOULD BE DETAILED ON HOW IT WILL BE | | | ISOLATED OR CONTROLLED TO MAINTAIN FUNCTION THROUGHOUT | | | CONTRUCTION. | | | | | | PLEASE REVIEW, CLARIFY OR CORRECT. | | | | | | | | | | | | | | | 5) SHEET E 001 - UNDER DEMOLITION GENERAL NOTES AND | | | GENERAL NOTES, THERE IS/ARE NO INDICATIONS OF FIRE | | | ALARM WORK. THE FIRE ALARM SHALL BE MAINTAINED | | | THROUGHOUT CONTRUCTION. ALL WORK SHALL BE DONE BY | | | CERTIFIED LIFE SAFETY CONTRACTORS UNDER SEPARATE SHOP | | | DRAWINGS. BASED ON THE SEPARATION OF AREAS AND PHASES, | | | ADDITIONAL DEVICES MAY BE REQUIRED FOR CODE COVERAGE | | | PURPOSES. | | | | | | PLEASE REVIEW AND PROVIDE AND APPLICABLE NOTE. | | | | | | | | | | | | 6) SHEET E 109 - THERE ARE TWO NOTE TAGE; 0.99.1 & | | | 0.98.1, THAT DO NOT APPEAR TO HAVE AN OBVIOUS | | | EXPLANATION DETAIL OF DEFINITION. WHAT DOES THESE | | | INDICATE. | | | | | | PLEASE CLARIFY. | | | | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-01-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-01-08 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-12-13 |
Time |
13:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-13 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-13 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-06-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-06-01 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2017-12-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-12-19 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-12-19 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2017-12-19 17:12:44 | PALM BEACH COUNTY IMPACT FEE OFFICE | | | RECEIPT NUMBER: 2017-1122-230 | | | MU-2017-032098-0000 | | | FEES PAID: $21,352.16 | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2017-10-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-10-26 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-10-26 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2017-10-26 08:51:04 | 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-06-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-06-27 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-06-27 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2017-06-27 16:32:14 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-05 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-05 |
Time |
10:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-11-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-02 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-02 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2017-11-02 12:19:19 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060065 | | | 11/2/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | IT APPEARS THAT ONLY ONE UPDATED SET OF MECHANICAL | | | PLANS WAS SUBMITTED IN THE CORRECTED PLAN SETS. THAT | | | REVISED SET HAS THE ENGINEER'S SEAL DATED 10/6/17 | | | AFFIXED. I HAVE REVIEWED THAT SET ALONG WITH THE | | | SUBMITTED NARRATIVE RESPONSE TO 1ST REVIEW COMMENTS | | | FROM HUNTONBRADY AND HAVE FOUND DEFIICENCIES. PLEASE | | | REFER TO 1ST REVIEW COMMENTS WHICH I HAVE ITEMIZED | | | BELOW. | | | | | | COMMENT #1: COMMISSIONING PLAN NOT PROVIDED. | | | | | | #2) SMOKE DETECTORS NOT SHOWN ON SHEET M111 AS | | | INDICATED IN THE NARRATIVE. | | | | | | #3) MATERIALS TO BE STORED IN DIS-PREP STORAGE ROOM NOT | | | IDENTIFIED, AND STORAGE EXHAUST NOT PROVIDED AS | | | INDICATED IN THE NARRATIVE. | | | | | | #4) THE ROOFTOP MECHANICAL EQUIPMENT CURB AND BASE | | | ATTACHMENTS TO THE ROOF STRUCTURE HAVE NOT BEEN | | | PROVIDED FOR THE ROOF UPBLAST FAN, AND THE ISOLATION | | | ROOM FAN. PLEASE CLARIFY IF THE ISOLATION ROOM AND THE | | | DECON ROOM ARE ONE IN THE SAME, OR IF THERE IS A ROOM | | | DESIGNATED AS ISOLATION ROOM SOMEWHERE ELSE ON THE | | | PLAN- I CANNOT LOCATE IT. | | | | | | #5) PLEASE ADD OUTDOOR AHU SOUND LEVEL NOTE TO THE | | | PLANS. | | | | | | #6) NOTE #20 ON THE REVISED SHEET M121 IS NOT ON THE | | | PLAN AS INDICATED IN THE NARRATIVE. | | | | | | #8) THE DESIGN PARAMETER TABLE SHOWING THE ROOM-TO-ROOM | | | PRESSURE RELATIONSHIPS ON SHEET M111 HAS NOT BEEN | | | PROVIDED AS INDICATED IN THE NARRATIVE. | | | | | | #9) THE REVISED ENERGY COMPLIANCE FORM SHOWING THE | | | WATER HEATER AND PIPING SYSTEM COMPLIANCE DATA HAS NOT | | | BEEN PROVIDED. | | | | | | 1) NEW COMMENT: REFER TO SECTION 449.3.6.5 FBC-14 | | | BUILDING AS IT APPLIES TIO THE NEW TRAUMA CENTER. IT | | | APPEARS THAT VARIABLE-AIR VOLUME SYSTEMS MAY NOT BE | | | PERMITTED FOR USE IN THE DECON ROOM AND POSSIBLY THE | | | TRAUMA ROOMS- PLEASE CLARIFY THE USE OF THESE ROOMS | | | WHAT PROCEDURES ARE PERFOMED IN EACH. | | | | | | 2) NEW COMMENT: PROVIDE PRODUCT DATA FOR THE DUCTWORK | | | IN THE TRAUMA ROOM ON THE PLANS, AND PROVIDE A | | | SUBMITTAL REVIEWED BY THE DESIGN PROFESSIONALS OF | | | RECORD. | | | | | | 3) NEW COMMENT: PLEASE REVIEW SECTION 2.1-8.2.4.3(2) IN | | | THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH | | | CARE FACILITIES. IT APPEARS THAT ANESTHESIA SCAVENGING | | | SYSTEMS NEED TO BE INSTALLED IN THE TRAUMA ROOMS. | | | PLEASE COMPLY. | | | | | | 4) NEW COMMENT: SUBMIT MANUFACTURER'S SPECIFICATIONS | | | FOR THE EXHAUST DUCT WRAP. PLEASE CLARIFY WHAT FUMES OR | | | GASES ARE BEING EXHAUSTED FROM THE ROOM AND WHY THE | | | EXHAUST DUCT NEEDS TO BE WRAPPED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-06-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-06-28 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-06-28 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2017-06-28 17:26:15 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, | | | ENERGY CONSERVATION CODES | | | PERMIT #17060065 | | | 6/28/17 | | | | | | PLAN REVIEW RESULT: DENIED | | | | | | 1) PROVIDE A COMMISSIONING PLAN- SECTION C408.2.1 | | | FBC-14 ENERGY CONSERVATION. | | | | | | 2) SHOW THE LOCATIONS OF THE REQUIRED SMOKE DETECTORS | | | IN THE RETURN AIR SYSTEMS OF AHU-G-1 & G-2- SECTION | | | 606.2.1. | | | | | | 3) INDICATE WHAT MATERIALS ARE BEING STORED IN THE DIS | | | PREP STOR ROOM TG322. WILL MEDICAL GAS BE STORED IN THE | | | ROOM OR ANY OTHER NEW ROOMS OR SPACES? PLEASE NOTE A | | | LOCAL EXHAUST SYSTEM MAY BE REQUIRED. | | | | | | 4) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | | ALL THE ROOFTOP MECHANICAL EQUIPMENT INCLUDING THE | | | AHU'S AND CURBS, THE EF'S AND CURBS, THE DUCTWORK AND | | | SUPPORT BRACKETS- SECTION 301.15. | | | | | | 5) PROVIDE THE ANTICIPATED DBA LEVEL OF THE NEW ROOFTOP | | | AHU'S AND FANS IN ACCORDANCE WITH SECTION | | | 2.1-8.2.1.1(6)(A) GUIDELINES FOR DESIGN AND | | | CONSTRUCTION OF HEALTH CARE FACILITIES. | | | | | | 6) INDICATE THE HEIGHT OF THE AHU AIR INLETS ABOVE THE | | | ROOF LEVEL- SEE SECTION 6-3.1 ASHRAE 170. | | | | | | 7) PROVIDE SPECIFICATIONS FOR THE ROOF TOP DUCTWORK AND | | | INSULATION, AND THE CHILLED AND STEAM WATER PIPING AND | | | INSULATIONS. | | | | | | 8) PLEASE INCLUDE THE PRESSURE RELATIONSHIPS, AND | | | EXHAUST AND RECIRCULATION PARAMETERS FOR ALL ROOMS AND | | | SPACES IN THE ASHRAE 170, 62.1 CALCULATION SUBMITTAL. | | | IT MAY BE HELPFUL TO PLACE THE TABLES ON THE MECHANICAL | | | PLANS. | | | | | | 9) PROVIDE THE WATER HEATER AND PIPING SYSTEM | | | COMPLIANCE DATA IN THE ENERGYGAUGE SUBMITTAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-11-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-13 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-09 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-06-28 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-06-28 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-06-27 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2017-06-28 13:41:54 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE RELOCATED VENT TERMINAL NEXT TO NEW MECHANICAL | | | RM TG326 SHALL COMPLY-WITH FBC PL 903.5 LOCATION OF | | | VENT TERMINAL. | | | AN OPEN VENT TERMINAL FROM A DRAINAGE SYSTEM SHALL NOT | | | BE LOCATED DIRECTLY BENEATH ANY DOOR, OPENABLE WINDOW, | | | OR OTHER AIR INTAKE OPENING OF THE BUILDING OR OF AN | | | ADJACENT BUILDING, AND ANY SUCH VENT TERMINAL SHALL NOT | | | BE WITHIN 10 FEET (3048 MM) HORIZONTALLY OF SUCH AN | | | OPENING UNLESS IT IS 3 FEET (914 MM) OR MORE ABOVE THE | | | TOP OF SUCH OPENING. | | | | | | 903.6 EXTENSION THROUGH THE WALL. | | | VENT TERMINALS EXTENDING THROUGH THE WALL SHALL | | | TERMINATE AT A POINT NOT LESS THAN 10 FEET (3048 MM) | | | FROM A LOT LINE AND NOT LESS THAN 10 FEET (3048 MM) | | | ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS SHALL NOT | | | TERMINATE UNDER THE OVERHANG OF A STRUCTURE WITH SOFFIT | | | VENTS. SIDE WALL VENT TERMINALS SHALL BE PROTECTED TO | | | PREVENT BIRDS OR RODENTS FROM ENTERING OR BLOCKING THE | | | VENT OPENING. | | | | | | 2. HOLDING TANK FOR DECON SHOWER. | | | A) HOW WILL THIS TANK BE EMPTIED OUT AND WHEN WILL THE | | | TANK BE EMPTIED. | | | B) PLEASE PROVIDE MANUFACTURE SPECIFICATION ON THE TANK | | | AND WATER LEVEL SENSOR. | | | C) WHAT TYPE OF CHEMICALS COULD BE INTRODUCED INTO THE | | | TANK. | | | PER WPB AMEND TP FBC 107.2.1 | | | | | | 3. PLEASE PROVIDE TRAP PRIMER FOR THE FLOOR DRAIN IN | | | THE DECON SHOWER. PER FBC PL 1002.4 | | | | | | 4, PLEASE PROVIDE A MEDICAL GAS RISER. PER WPB AMEND TO | | | FBC 107.3.5.1.3(13) | | | | | | 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | TEMPERED WATER SHALL BE DELIVERED THROUGH AN APPROVED | | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | | 1070 OR CSA B125.3. PER FBC PL 416.5 | | | | | | 6. LABEL FIXTURES ON RISER FOR BATHROOM TG337. PER WPB | | | AMEND TP FBC 107.2.1 | | | | | | 7. THE BRANCH DRAIN FOR THE BREAKROOM SINK SHALL | | | CONNECT TO BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP | | | TG337. PER FBC PL 912.1 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-01-08 |
|
|
Cont ID |
|
| Sent By |
LL |
Date |
2018-01-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-01-08 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-01-08 15:36:39 | ZONING APPROVED WITH THE FOLLOWING PROVISO: | | | | | | 1.) SEPERATE LANDSCAPE PERMIT AND REVIEW REQUIRED PRIOR | | | TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.) | | | | | | REFERENCE: PB 1753/Z17070020 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2017-10-27 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-10-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2017-10-27 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-10-27 08:09:02 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) SURVEY OF THE PROPERTY IS REQUIRED. | | | | | | 2.) PROVIDE A SITE PLAN SHOWING THE AREA OF WORK. THERE | | | ARE MULTIPLE BUILDINGS ON THE PROPERTY WHICH MAKES IT | | | VERY DIFFICULT TO DETERMINE WHERE THE SCOPE OF WORK | | | WILL OCCUR. | | | | | | 3.) ADDITIONAL INFORMATION IS REQUIRED ON THE TOTAL | | | SQUARE FOOTAGE ADDED TO THE EXISTING BUILDING. PLEASE | | | NOTE THAT ANY INCREASE IN THE TOTAL BUILDING SQUARE | | | FOOTAGE BY MORE THAN 5% SHALL REQUIRE A MAJOR AMENDMENT | | | TO THE CSPD. [6/21/17 REPEAT COMMENT] | | | | | | 4.) SITE PLAN CALCULATIONS, INCLUDING: | | | EXISTING/PROPOSED LAND USE AND ZONING; TOTAL ACRES OF | | | THE PROJECT; EXISTING/PROPOSED BUILDING SQUARE FOOTAGE; | | | PERCENT OF OPEN SPACE, LANDSCAPING BUILDING COVERAGE | | | AND IMPERMEABLE SURFACE; PARKING COMPUTATIONS (I.E. | | | PARKING REQUIRED, PROVIDED, ETC.); FLOOR AREA RATIO | | | (FAR). [6/21/17 REPEAT COMMENT] | | | | | | 5.) AN AMENDMENT TO THE ST. MARY'S COMMUNITY SERVICE | | | PLANNED DEVELOPMENT (CSPD) IS REQUIRED. THIS PROCESS | | | MUST BE COMPLETED WITH THE PLANNING DIVISION PRIOR TO | | | BUILDING PERMIT. THE 2017 DEVELOPMENT APPLICATION IS | | | AVAILABLE AT: HTTP://WWW.WPB.ORG/DEPARTMENTS/DEVELOPMEN | | | T-SERVICES/FORMS/PLANNING-ZONING-FORMS [6/21/17 REPEAT | | | COMMENT] | | | | | | NOTES: | | | | | | * ZONE: CSPD | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2017-06-21 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-06-21 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2017-06-21 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-06-21 16:59:34 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) ADDITIONAL INFORMATION IS REQUIRED ON THE TOTAL | | | SQUARE FOOTAGE ADDED TO THE EXISTING BUILDING. PLEASE | | | NOTE THAT ANY INCREASE IN THE TOTAL BUILDING SQUARE | | | FOOTAGE BY MORE THAN 5% SHALL REQUIRE A MAJOR AMENDMENT | | | TO THE CSPD. | | | | | | 2.) SITE PLAN CALCULATIONS, INCLUDING: | | | EXISTING/PROPOSED LAND USE AND ZONING; TOTAL ACRES OF | | | THE PROJECT; EXISTING/PROPOSED BUILDING SQUARE FOOTAGE; | | | PERCENT OF OPEN SPACE, LANDSCAPING BUILDING COVERAGE | | | AND IMPERMEABLE SURFACE; PARKING COMPUTATIONS (I.E. | | | PARKING REQUIRED, PROVIDED, ETC.); FLOOR AREA RATIO | | | (FAR) | | | | | | 3.) AN AMENDMENT TO THE ST. MARY'S COMMUNITY SERVICE | | | PLANNED DEVELOPMENT (CSPD) IS REQUIRED. THIS PROCESS | | | MUST BE COMPLETED WITH THE PLANNING DIVISION PRIOR TO | | | BUILDING PERMIT. THE 2017 DEVELOPMENT APPLICATION IS | | | AVAILABLE AT: HTTP://WWW.WPB.ORG/DEPARTMENTS/DEVELOPMEN | | | T-SERVICES/FORMS/PLANNING-ZONING-FORMS | | | | | | NOTES: | | | | | | * ZONE: CSPD | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |