Plan Review Details - Permit 17060024
Plan Review Stops For Permit 17060024
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-18 Cont ID  
Sent By jwitmer Date 2017-07-18 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2017-07-18 Time 09:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-05 Cont ID  
Sent By jwitmer Date 2017-06-05 Time 08:57 Rev Time 0.00
Received By jwitmer Date 2017-06-05 Time 08:01 Sent To  
Notes
2017-06-05 08:57:452014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060024
 ADD: 930 OMAR RD.
 CONT: STATEWIDE WINDOWS & DOORS
 TEL: 561-202-1412
 E-MAIL: SCOTT.STATEWIDEWINDOWS @GMAIL.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 05/2017
 ACTION: DENIED
  
 1) THE SUBMITTED FLOOR PLAN DOES NOT HAVE WHO THE
 AUTHOR OF THE FLOOR PLAN IS. THE QUALIFIER FOR THE
 COMPANY SHOULD PRINT THEIR NAME, SIGN THEIR NAME AND
 CONTRACTOR LICENSE NUMBER ON THE PLANS TAKING OWNERSHIP
 OF THE PLANS. 105.3.1.2. / 107.3.4.3 CERTIFICATIONS BY
 CONTRACTORS.
  
 2A) THE SUBMITTED FLOOR PLAN INDICATES (2) BEDROOMS
 WITH WINDOWS (5-8) BEING LOCATED IN THE (2) BEDROOMS.
 STATEWIDE ORDER FORM DATED 3/1/17 HAS ALL FOUR OF THESE
 WINDOWS LABELED SH (SINGLE HUNG) WINDOWS. PLEASE NOTE
 WINDOW # 5 IS 36(W)X(50(H) IN DIMENSIONS OR APPROX.
 (CLEAR OPENING)32 INCHES WIDE X 19 INCHES IN HEIGHT AND
 A NET CLEAR OPENING OF 4.25 SQ. FT. DOES NOT MEET THE
 EGRESS REQUIREMENTS.
  
 WINDOWS 6-8 STILL THE BEDROOM WINDOWS ALL SHOW 36 IN.
 (W)X 38 IN. (H)WITH AN APPROX.. CLEAR OPENING OF 3.18
 SQ. FT. DOES NOT MEET THE EGRESS REQUIREMENTS.
  
  
 2014 FBC-R SECTION R310 EMERGENCY ESCAPE AND RESCUE
 OPENINGS R310.1. EMERGENCY ESCAPE AND RESCUE REQUIRED.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND
 RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE
 SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE OPENINGS
 SHALL BE REQUIRED IN EACH SLEEPING ROOM. WHERE
 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY
 SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES
 (1118 MM) MEASURED FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE CLEAR OPENING.
  
 2014 FBC-R310.1.1 MINIMUM OPENING AREA. ALL EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE A MINIMUM NET
 CLEAR OPENING OF 5.7 SQUARE FEET (0.530 M2).
 EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET .
  
 R310.1.2 MINIMUM OPENING HEIGHT. THE MINIMUM NET CLEAR
 OPENING HEIGHT SHALL BE 24 INCHES .
  
 R310.1.3 MINIMUM OPENING WIDTH. THE MINIMUM NET CLEAR
 OPENING WIDTH SHALL BE 20 INCHES.
  
 R310.1.4 OPERATIONAL CONSTRAINTS.
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE
 OPERATIONAL FROM THE INSIDE OF THE ROOM WITHOUT THE USE
 OF KEYS, TOOLS OR SPECIAL KNOWLEDGE.
 2014 FBC-EXISTING BUILDING CODE SECTION 704 MEANS OF
 EGRESS (WINDOWS)
 704.1. MEANS OF EGRESS FOR BUILDINGS UNDERGOING
 ALTERATION SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTION 701.1 AND THE SCOPING PROVISIONS OF CHAPTER 1
 WHERE APPLICABLE.
 EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL
 DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5-PERCENT
 REDUCTION IN THE CLEAR OPENING DIMENSIONS OF
 REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED.
  
 2B) DISCREPANCIES WITH THE STATEWIDE ORDER FORM DATED
 3/1/17 AND THE CUSTOM WINDOW SYSTEMS. THE STATEWIDE
 FORM LIST ALL OF THE WINDOWS AS SINGLE HUNG WHEREAS
 CUSTOM WINDOW FORM HAS 2 LINE ITEMS, NUMBER 4 WITH
 QUANTITY (1) HORIZONTAL SLIDER TIP 74 1/8 IN. X 38 3/8
 IN. AND LINE ITEM NUMBER 5 WITH QUANTITY (2) HORIZONTAL
 SLIDER TIP 74 1/8 IN. X 38 3/8 IN. THE SAME AS LINE
 ITEM NUMBER 4, WHAT IS THE DIFFERENCE? 107. 2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 2C)IN THE CUSTOM WINDOW FORM ITEMS NUMBERED 4 & 5
 HORIZONTAL SLIDER TIP 74 1/8 IN. X 38 3/8 IN THIS IS AN
 OVERALL DIMENSION FOR A SINGLE SLIDER WINDOW IT WOULD
 APPEAR THESE WINDOWS ARE FOR THE WINDOWS 11-14 NOT
 PROVIDED ON THE STATEWIDE FORM DATED 3/1/17. 107. 2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-18 Time   Rev Time 0.00
Received By cpuell Date 2017-07-11 Time 13:58 Sent To  
Notes
2017-07-13 13:58:40JWITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-05 Time   Rev Time 0.00
Received By cpuell Date 2017-06-01 Time 14:26 Sent To  
Notes
2017-06-01 14:26:50BLDG MISC 1