Plan Review Details - Permit 17051294
Plan Review Stops For Permit 17051294
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By tklarge Date 2017-06-16 Time 10:48 Rev Time 0.00
Received By tklarge Date 2017-06-16 Time 10:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-06-07 Cont ID  
Sent By tklarge Date 2017-06-07 Time 05:46 Rev Time 0.00
Received By tklarge Date 2017-06-06 Time 14:57 Sent To  
Notes
2017-06-06 15:29:011) THE ENTIRE GAS SYSTEM IS UNDERSIZED BASED ON THE
 INFORMATION PROVIDED ON THE PLANS. SUBMIT A REVISED GAS
 DRAWING SHOWING A GAS PIPING RISER THAT IS SIZED IN
 ACCORDANCE WITH THE SIZING TABLES FOUND IN 2014
 FBC-FUEL GAS SEC.402.4.
 2) THE NOTES FOR THE GAS SYSTEM FOR TABLE #1 REFERS TO
 TABLE 402.4 (2) WITH A DEVELOPED LENGTH DISTANCE OF 100
 FEET AND A LOAD OF 1,600 MBH. THE MAXIMUM BTU LOAD
 ALLOWED ON A 1 INCH SCH. 40 LINE AT 100 FEET PER TABLE
 402.4 (2) IS 195,000 BTU'S. I HAVE NO IDEA WHAT THE
 INTENT OF THE DESIGNER OF THIS SYSTEM IS, AS THIS
 SYSTEM DOESN'T COME CLOSE TO BEING COMPLIANT WITH THE
 FUEL GAS CODE. CLARIFY. A THOROUGH REVIEW COULD NOT BE
 ACCOMPLISHED DUE TO THE DEFICIENCIES IN THE DESIGN.
 3) THE NOTES FOR THE GAS SYSTEM FOR TABLE #2 REFERS TO
 TABLE 402.4 (15) WITH A DEVELOPED LENGTH DISTANCE OF
 100 FEET AND A LOAD OF 800 MBH. THE MAXIMUM BTU LOAD
 ALLOWED ON A 3/4 INCH CSST LINE AT 100 FEET PER TABLE
 402.4 (15) IS 62,000 BTU'S. AGAIN, THIS IS NOT IN
 COMPLIANCE WITH THE REFERENCED SIZING TABLE ON THE
 PLANS. CLARIFY.
 4) SHOW THE CORRESPONDING EHD OF THE CSST FOR THE PIPE
 SIZE SHOWN ON THE GAS RISER. 2014 FBC-FUEL GAS
 SECS.404.2 & THE APPROPRIATE SIZING TABLES IN SEC.
 402.4.
 5) SUBMIT A CLEAR DETAIL AS TO HOW THE VENT PIPING IS
 BEING TIED TOGETHER. THE PLAN IS SOMEWHAT
 CONFUSING.WILL THE TRAC PIPE PS-II BE ENCASED IN AN
 ADDITIONAL SLEEVE AND THEN VENTED OR WILL THE SLEEVE ON
 THE PIPING BE FITTED WITH THE VENT FITTING? IS THE VENT
 FITTING MANUFACTURED BY TRAC PIPE? IF SO, SUBMIT
 SPECIFICATIONS/LITERATURE ON THE FITTING.IF ENCASED IN
 AN ADDITIONAL SLEEVE, SUBMIT INFORMATION AS TO TYPE OF
 MATERIAL, SIZE, ETC. CLARIFY.WPB AMEND. TO FBC SEC.
 107.2.1.
 6) CLARIFY THE TOTAL DEVELOPED LENGTH DISTANCE. IS THE
 OVERALL DEVELOPED LENGTH OF 100 FEET FOR BOTH TABLES OR
 IS IT 100 FOR EACH TABLE, WHICH WOULD BE AN OVERALL
 LENGTH OF 200 FEET? CLARIFY.
 7) ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2014
 FBC-FUEL GAS SEC. 301.3. SUBMIT MANUF. SPECIFICATIONS
 SHOWING THE LISTING OF THE APPLIANCES.
 8) THE MAIN PLANS (PERMIT #16090688) SHOW NUMEROUS GAS
 APPLIANCES IN ADDITION TO THIS LIVE KITCHEN.WILL ANY
 GAS PIPING BE RUN TO THESE OTHER APPLIANCES? CLARIFY ON
 THE PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 9) INDICATE THE TYPE OF PIPING TO BE USED FOR THE VENT
 FOR THE PIPING.WPB AMEND. TO FBC SEC. 107.2.1.
 10) WHAT TYPE OF OPERATIONS WILL BE DONE AT THE "LIVE
 KITCHENS?" WILL THERE BE ANY COOKING? CLARIFY.
 11) EMERGENCY SHUT OFF VALVE (SOLENOID VALVE) SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE.
 SECS. 10.4, 10.5 OF NFPA 96-08.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-16 Cont ID  
Sent By tklarge Date 2017-06-16 Time 10:48 Rev Time 0.00
Received By tklarge Date 2017-06-16 Time 10:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-07 Cont ID  
Sent By tklarge Date 2017-06-07 Time 05:46 Rev Time 0.00
Received By tklarge Date 2017-05-31 Time 08:09 Sent To P
Notes
***NONE***