| 2017-06-06 15:29:01 | 1) THE ENTIRE GAS SYSTEM IS UNDERSIZED BASED ON THE |
| | INFORMATION PROVIDED ON THE PLANS. SUBMIT A REVISED GAS |
| | DRAWING SHOWING A GAS PIPING RISER THAT IS SIZED IN |
| | ACCORDANCE WITH THE SIZING TABLES FOUND IN 2014 |
| | FBC-FUEL GAS SEC.402.4. |
| | 2) THE NOTES FOR THE GAS SYSTEM FOR TABLE #1 REFERS TO |
| | TABLE 402.4 (2) WITH A DEVELOPED LENGTH DISTANCE OF 100 |
| | FEET AND A LOAD OF 1,600 MBH. THE MAXIMUM BTU LOAD |
| | ALLOWED ON A 1 INCH SCH. 40 LINE AT 100 FEET PER TABLE |
| | 402.4 (2) IS 195,000 BTU'S. I HAVE NO IDEA WHAT THE |
| | INTENT OF THE DESIGNER OF THIS SYSTEM IS, AS THIS |
| | SYSTEM DOESN'T COME CLOSE TO BEING COMPLIANT WITH THE |
| | FUEL GAS CODE. CLARIFY. A THOROUGH REVIEW COULD NOT BE |
| | ACCOMPLISHED DUE TO THE DEFICIENCIES IN THE DESIGN. |
| | 3) THE NOTES FOR THE GAS SYSTEM FOR TABLE #2 REFERS TO |
| | TABLE 402.4 (15) WITH A DEVELOPED LENGTH DISTANCE OF |
| | 100 FEET AND A LOAD OF 800 MBH. THE MAXIMUM BTU LOAD |
| | ALLOWED ON A 3/4 INCH CSST LINE AT 100 FEET PER TABLE |
| | 402.4 (15) IS 62,000 BTU'S. AGAIN, THIS IS NOT IN |
| | COMPLIANCE WITH THE REFERENCED SIZING TABLE ON THE |
| | PLANS. CLARIFY. |
| | 4) SHOW THE CORRESPONDING EHD OF THE CSST FOR THE PIPE |
| | SIZE SHOWN ON THE GAS RISER. 2014 FBC-FUEL GAS |
| | SECS.404.2 & THE APPROPRIATE SIZING TABLES IN SEC. |
| | 402.4. |
| | 5) SUBMIT A CLEAR DETAIL AS TO HOW THE VENT PIPING IS |
| | BEING TIED TOGETHER. THE PLAN IS SOMEWHAT |
| | CONFUSING.WILL THE TRAC PIPE PS-II BE ENCASED IN AN |
| | ADDITIONAL SLEEVE AND THEN VENTED OR WILL THE SLEEVE ON |
| | THE PIPING BE FITTED WITH THE VENT FITTING? IS THE VENT |
| | FITTING MANUFACTURED BY TRAC PIPE? IF SO, SUBMIT |
| | SPECIFICATIONS/LITERATURE ON THE FITTING.IF ENCASED IN |
| | AN ADDITIONAL SLEEVE, SUBMIT INFORMATION AS TO TYPE OF |
| | MATERIAL, SIZE, ETC. CLARIFY.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 6) CLARIFY THE TOTAL DEVELOPED LENGTH DISTANCE. IS THE |
| | OVERALL DEVELOPED LENGTH OF 100 FEET FOR BOTH TABLES OR |
| | IS IT 100 FOR EACH TABLE, WHICH WOULD BE AN OVERALL |
| | LENGTH OF 200 FEET? CLARIFY. |
| | 7) ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2014 |
| | FBC-FUEL GAS SEC. 301.3. SUBMIT MANUF. SPECIFICATIONS |
| | SHOWING THE LISTING OF THE APPLIANCES. |
| | 8) THE MAIN PLANS (PERMIT #16090688) SHOW NUMEROUS GAS |
| | APPLIANCES IN ADDITION TO THIS LIVE KITCHEN.WILL ANY |
| | GAS PIPING BE RUN TO THESE OTHER APPLIANCES? CLARIFY ON |
| | THE PLANS.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 9) INDICATE THE TYPE OF PIPING TO BE USED FOR THE VENT |
| | FOR THE PIPING.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) WHAT TYPE OF OPERATIONS WILL BE DONE AT THE "LIVE |
| | KITCHENS?" WILL THERE BE ANY COOKING? CLARIFY. |
| | 11) EMERGENCY SHUT OFF VALVE (SOLENOID VALVE) SHALL BE |
| | BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| | UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. |
| | SECS. 10.4, 10.5 OF NFPA 96-08. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |