Plan Review Details - Permit 17051281
Plan Review Stops For Permit 17051281
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-28 Cont ID  
Sent By shill Date 2017-06-28 Time 08:05 Rev Time 0.00
Received By shill Date 2017-06-28 Time 07:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-02 Cont ID  
Sent By shill Date 2017-06-02 Time 12:40 Rev Time 0.00
Received By shill Date 2017-06-02 Time 12:37 Sent To  
Notes
2017-06-02 12:44:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. REVISE PLAN TO SHOW COMPLIANCE WITH FBC A FAIR
 HOUSING.
  
 SEE FAIR HOUSING FAQ
 (HTTP://WWW.FAIRHOUSINGFIRST.ORG/FAQ/VIEW_ALL.HTML):
  
 8. DO THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION
 REQUIREMENTS APPLY TO ALTERATION OR RENOVATION OF
 PROPERTIES?
 ALTERATIONS, REHABILITATION OR REPAIR OF COVERED
 MULTIFAMILY DWELLINGS ARE NOT COVERED BECAUSE THE ACT'S
 DESIGN AND CONSTRUCTION REQUIREMENTS ONLY APPLY TO NEW
 CONSTRUCTION OF BUILDINGS BUILT FOR FIRST OCCUPANCY
 AFTER MARCH 13, 1991. HOWEVER, A COVERED MULTIFAMILY
 DWELLING THAT HAS BEEN CONSTRUCTED TO COMPLY WITH THE
 LAW CANNOT LATER BE ALTERED TO MAKE IT NON-COMPLIANT
 WITH THE LAW.
  
 2. ARCHITECT'S TITLE BLOCK LACKS INFORMATION REQUIRED
 BY FS481, FAC61G1-16.004, REVISE TO COMPLY.
  
 3. ID2.3 SHOWS WOOD FLOOR/CEILING JOISTS; ISN'T THIS A
 HIGH RISE NON COMBUSTIBLE BUILDING? FBC 107, FBC B 603.
  
 4. I WAS UNABLE TO FIND ANY INDICATION THAT THE
 FLOORING IS TO BE REPLACED. IF THAT IS THE CASE, REVISE
 PLAN TO NOTE THAT EXISTING FLOORING IS TO REMAIN. IF
 FLOORING IS PROPOSED, REVISE PLAN TO CLARIFY TYPE AND
 PROVIDE THE FOLLOWING TEST REPORTS FOR FLOORING
 UNDERLAYMENT:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-19 Cont ID  
Sent By jpearson Date 2017-07-19 Time 14:28 Rev Time 0.00
Received By jpearson Date 2017-07-19 Time 14:28 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-07-10 Cont ID  
Sent By jpearson Date 2017-07-10 Time 09:35 Rev Time 0.00
Received By jpearson Date 2017-07-10 Time 09:35 Sent To  
Notes
2017-07-10 09:44:51CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (2ND REVIEW):
  
 1. PROVIDE CORRECTION FOR FIRE ALARM SYSTEM. SMOKE
 ALARM SYSTEM IN UNIT SHALL NOT ACTUATE THE BUILDING
 FIRE ALARM SYSTEM. NFPA 101, 9.6.2.10.4
 2. PROVIDE LOCATION ON PLAN OF SMOKE ALARMS, INDICATING
 POWER SOURCE AND INTERCONNECTION AS REQUIRED PER FBC
 907.2.11
 3. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC
 410.16
 4. PROVIDE LIGHT FIXTURE SCHEDULE AND SPEC SHEET FOR
 EACH FIXTURE TO CONFIRM LISTING AND USE. NEC 110.3; FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-07 Cont ID  
Sent By rlecky Date 2017-06-07 Time 13:35 Rev Time 0.00
Received By rlecky Date 2017-06-06 Time 11:53 Sent To  
Notes
2017-06-06 14:54:47 
 17051281
 201 S. NARCISSUS AVE. #804
 INTERIOR REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE THE SIZE, RATING, AND LOCATION OF THE EXISTING
 PANEL BOARD. VERIFY THE REQUIRED WORKING CLEARANCES ARE
 MAINTAINED AT THE ELECTRICAL PANEL. NEC 110.26
  
 VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC
 406.12
  
 VERIFY ALL NEW RECEPTACLE CIRCUITS ARE AFCI PROTECTED.
 NEC 210.12
  
 RECEPTACLES LOCATED AT THE KITCHEN ISLAND COUNTER
 REQUIRE GFCI PROTECTION. NEC 210.8
  
 VERIFY THE EXISTING AC UNITS HAVE THE REQUIRED
 DISCONNECTS. NEC 422.30
  
 VERIFY OR PROVIDE A 20 AMP LAUNDRY CIRCUIT WITH GFCI
 PROTECTION. NEC 210.11 (C) (2)
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED ON EACH
 BALCONY. NEC 210.8, 210.52(E)(3)
  
 PROVIDE A FIRE AND SMOKE ALARM SYSTEM IN ACCORDANCE
 WITH THE REQUIREMENTS FOR AN R2 OCCUPANCY. FBC 907.2.9,
 907.2.11
  
 PROVIDE AN INDIVIDUAL BRANCH CIRCUIT PROTECTED BY A
 READILY ACCESSIBLE GFCI TO THE HYDRO MASSAGE TUB. NEC
 680.71
  
 PROVIDE AN ELECTRICAL BONDING PLAN FOR THE HYDRO
 MASSAGE TUB INSTALLATION. NEC 680.70.74
  
 ALL RECEPTACLES LOCATED WITH SIX FEET OF THE HYDRO
 MASSAGE TUB SHALL BE PROTECTED BY A GFCI. NEC 680.71
  
 PROVIDE A DETAIL ON THE PLAN WHICH SHOWS THE LOCATION
 AND CONSTRUCTION METHOD OF THE PROPOSED ACCESS PANEL
 FOR THE HYDRO MASSAGE TUBE ELECTRICAL PUMP AND GFCI
 RECEPTACLE. NEC 680.73
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-29 Cont ID  
Sent By pleduc Date 2017-06-29 Time   Rev Time 0.00
Received By pleduc Date 2017-06-28 Time 14:49 Sent To  
Notes
2017-06-29 12:58:202ND REVIEW
  
 AN ADDITIONAL NOTE WAS ADDED TO THE ELECTICAL PAGE -
 ALL WORK ON THE FIRE ALARM SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-05 Cont ID  
Sent By pleduc Date 2017-06-05 Time   Rev Time 0.00
Received By pleduc Date 2017-06-05 Time 11:49 Sent To  
Notes
2017-06-05 12:49:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) ID 2.1 - THERE IS NO REFERENCE OF COMPLAINCE WITH
 ANY FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 PLEASE PROVIDE FOR THE REVIEW OF THE CODES AND AN
 APPLICABLE NOTE OF COMPLIANCE.
  
  
  
 2) THERE IS NO INDICATIONS ON ANY SHEET REFERENCING
 WORK ON THE FIRE ALARM AND/OR FIRE SPRINKLER
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE FIRE ALARM EXCEEDS 4 HOURS, A
 FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL
 FULL AND COMPLETE PROTECTION IS RETURNED.
  
  
 PEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 COMPLAINCE.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-07-20 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-18 Time 11:32 Sent To  
Notes
2017-07-19 11:33:13RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-10 Cont ID  
Sent By jpearson Date 2017-07-10 Time 09:45 Rev Time 0.00
Received By jpearson Date 2017-06-23 Time 13:05 Sent To  
Notes
2017-06-26 13:06:08B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-13 Cont ID  
Sent By gjohnson Date 2017-06-13 Time 09:54 Rev Time 0.00
Received By gjohnson Date 2017-05-31 Time 09:45 Sent To  
Notes
2017-06-01 09:46:40B12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-07-20 Cont ID  
Sent By ccole Date 2017-07-20 Time 08:55 Rev Time 0.00
Received By ccole Date 2017-07-20 Time 08:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-07-05 Cont ID  
Sent By ccole Date 2017-07-05 Time 11:50 Rev Time 0.00
Received By ccole Date 2017-07-05 Time 11:50 Sent To  
Notes
2017-07-05 12:01:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17051281
 7/5/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE EXCEPTION UNDER SECTION 504.6.4.1 TO ALLOW
 BOOSTER FANS FOR DRYER EXHAUST DUCTS WAS REMOVED FROM
 THE LATEST 2014 FIFTH EDITION OF THE MECHANICAL CODE.
 MAXIMUM LENGTH OF THE DRYER EXHAUST DUCT SHALL BE 35
 FT. WITH REDUCTIONS FOR FITTINGS- SEE TABLE 504.6.4.1.
 EXHAUST DUCT LENGTH MAY ALSO BE DETERMINED BY
 MANUFACTURER'S SPECIFICATIONS - SECTION 504.6.4.2.
 PLEASE SUBMIT THE SPECS.
  
 2) PLEASE PROVIDE THE MAKE AND MODEL OF THE
 RECIRCULATING KITCHWEN EXHAUST HOOD ON THE PLANS, AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 505.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-06 Cont ID  
Sent By ccole Date 2017-06-06 Time 07:12 Rev Time 0.00
Received By ccole Date 2017-06-05 Time 17:37 Sent To  
Notes
2017-06-06 07:57:011ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17051281
 6/6/17
  
 RESULTS: DENIED.
  
 1) THE PLAN SHOWS 1900 CFMS OF SUPPLY AIR BEING
 PROVIDED BY AN EXISTING 2-TON UNIT WHICH FAR EXCEEDS
 THE UNIT'S CAPACITY- PLEASE CORRECT OR CLARIFY. PLEASE
 NOTE THERE IS A 4" DUCT DROP IN THE POWDER ROOM
 INDICATED AT 200 CFMS WHICH EXCEEDS THE CAPACITY OF A
 4" DUCT- SEE THE DUCT SIZE PREVIEW WHICH INDICATES 10
 CFMS FOR THE POWDER ROOM.
  
 2) MISSING FROM THE DUCT SIZING PREVIEW ARE THE LAUNDRY
 ROOM, THE STORAGE ROOM, AND CAROLYN'S BED AND BATHROOM.
  
 3) PROVIDE A COMPLETE DRYER EXHAUST PLAN THAT INCLUDES
 THE TOTAL LENGTH OF THE DRYER RUN FROM OUTLET TO DRYER
 TERMINATION LOCATION, CLARIFY IF THE NEW EXHAUST DUCT
 IS CONNECTING INTO AN EXISTING CHASE AND SHOW THE
 LOCATION AND HOW CONNECTION IS BEING MADE. PLEASE
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER-
 SECTION 504.
  
 4) PROVIDE COMPLETE KITCHEN EXHAUST PLANS FOR THE NEW
 COOKING APPLIANCES. SHOW THE TYPES AND SIZES OF EXHAUST
 HOODS, EXHAUST DUCTS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE APPLIANCES AND THE HOODS. SHOW
 THE EXHAUST DUCT RUNS FROM THE EXHAUST OUTLETS TO
 TERMINATION LOCATIONS. IF CONNECTING INTO A CHASE,
 INDICATE SHOW CONNECTION IS BEING MADE. PLEASE NOTE
  
 THAT SEPARATE CHASES ARE REQUIRED FOR KITCHEN EXHAUST,
 DRYER EXHAUST AND BATH EXHAUST- SECTION 501.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-07 Cont ID  
Sent By gjohnson Date 2017-07-07 Time 17:28 Rev Time 0.00
Received By gjohnson Date 2017-07-07 Time 17:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-13 Cont ID  
Sent By gjohnson Date 2017-06-13 Time 09:39 Rev Time 0.00
Received By gjohnson Date 2017-06-12 Time 17:34 Sent To  
Notes
2017-06-13 09:54:471ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. ID-2.5 ON THE MASTER BATH RISER IT IS SHOWING
 THE NEW SHOWER ABOVE THE FLOOR LEVEL IS THIS CORRECT
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. BRANCH DRAIN FOR WASHING MACHINE SHALL BE 3". PER
 FBC PL 406.2
  
 3. THE WASHING MACHINE DRAIN SHALL BE SEPARATELY
 VENTED. PER FBC PL 901.2.1
  
 4. IS THE WATER HEATER BEING REPLACED IF SO PLACE NOTE
 ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  