Plan Review Details - Permit 17051249
Plan Review Stops For Permit 17051249
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-18 Cont ID  
Sent By rmcdouga Date 2017-07-18 Time 19:25 Rev Time 0.00
Received By rmcdouga Date 2017-07-18 Time 19:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-09 Cont ID  
Sent By rmcdouga Date 2017-06-09 Time 09:51 Rev Time 0.00
Received By rmcdouga Date 2017-06-09 Time 06:54 Sent To  
Notes
2017-06-09 08:27:36PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LWC-34 SYSTEM FOR THE LIGHTWEIGHT CONCRETE DECK
 HAS A MAXIMUM DESIGN PRESSURE OF -60.0 PSF. THIS IS NOT
 ADEQUATE FOR THE PERIMETER AND CORNER AREAS. SUBMIT
 ENHANCED FASTENING CALCULATIONS THAT HAVE BEEN SIGNED
 AND SEALED BY A FLORIDA LICENSED DESIGN PROFESSIONAL.
 SEE LIMITATION NUMBER 5.7 ON PAGE 5 OF PRODUCT APPROVAL
 FL2533.
  
 2) SUBMIT TWO SETS OF A MOISTURE SURVEY OF THE
 LIGHTWEIGHT CONCRETE DECK. FBC 1510 & FBC 1917
  
 3) SUBMIT TWO SETS OF A FASTENER WITHDRAWAL TESTING FOR
 THE LIGHTWEIGHT CONCRETE DECK. SEE LIMITATION NUMBER
 5.9 ON PAGE 5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-31 Cont ID  
Sent By rmcdouga Date 2017-05-31 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2017-05-31 Time 07:12 Sent To  
Notes
2017-05-31 07:51:38PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE DECK TYPE, THE SYSTEM NUMBER AND THE
 MAXIMUM DESIGN PRESSURE OF THE ROOFING SYSTEM THAT WILL
 BE INSTALLED FROM THE ONES LISTED IN THE PRODUCT
 APPROVAL. FBC 107.2.1
  
 2) IF THIS IS A MECHANICALLY ATTACHED SYSTEM AND
 ENHANCED FASTENING IS REQUIRED IN ORDER TO MEET THE
 INCREASED UPLIFT PRESSURES FOR ROOF ZONES 2 AND 3, THEN
 SUBMIT TWO SETS OF SIGNED AND SEALED RAS117
 CALCULATIONS. FBC-R905.11.3

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-18 Cont ID  
Sent By rmcdouga Date 2017-07-18 Time 19:25 Rev Time 0.00
Received By rmcdouga Date 2017-07-17 Time 14:30 Sent To  
Notes
2017-07-18 14:30:21RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-09 Cont ID  
Sent By rmcdouga Date 2017-06-09 Time 09:51 Rev Time 0.00
Received By rmcdouga Date 2017-06-07 Time 15:43 Sent To  
Notes
2017-06-08 15:43:26RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-31 Cont ID  
Sent By rmcdouga Date 2017-05-31 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2017-05-30 Time 16:51 Sent To  
Notes
2017-05-30 16:51:41RMCDOUGAL