Plan Review Details - Permit 17051237
Plan Review Stops For Permit 17051237
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-21 Cont ID  
Sent By rmcdouga Date 2017-07-21 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2017-07-21 Time 08:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-06 Cont ID  
Sent By rmcdouga Date 2017-07-06 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2017-07-06 Time 14:50 Sent To  
Notes
2017-07-06 15:19:27PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SIMPSON H7Z STRAPS THAT ARE SPECIFIED AS THE
 ROOF TO WALL CONNECTORS ONLY PROVIDE RESISTANCE TO
 LATERAL FORCES THAT ARE PARALLEL TO THE WALL. THEY DO
 NOT RESIST LATERAL FORCES THAT ARE PERPENDICULAR TO THE
 WALL. THESE CONNECTORS ARE ALSO REQUIRED TO BE STRAPPED
 TO THE WALL STUDS. THE PLANS SPECIFY THE WALL STUDS TO
 BE 16 INCHES ON CENTER AND THE ROOF TRUSSES ARE TO BE
 24 INCHES ON CENTER. THE H7Z STRAPS WON'T WORK BECAUSE
 THE TRUSSES ARE NOT ALIGNED WITH THE WALL STUDS.
 FBC-R802.1.7.5
  
 2) REVISED ENERGY FORMS SHOWING THE CHANGES WILL NEED
 TO BE SUBMITTED AND REVIEWED. FBC ENERGY CONSERVATION
 R103.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-05 Cont ID  
Sent By rmcdouga Date 2017-06-05 Time 09:49 Rev Time 0.00
Received By rmcdouga Date 2017-06-02 Time 18:48 Sent To  
Notes
2017-06-05 09:49:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SIMPSON TS 18 STRAPS THAT ARE SPECIFIED FOR THE
 ROOF TO WALL CONNECTORS ARE FOR TENSION AND DO NOT
 PROVIDE RESISTANCE TO LATERAL FORCES THAT ARE REQUIRED.
 FBC-R802.1.7.5
  
 2) REVISED ENERGY FORMS SHOWING THE CHANGES WILL NEED
 TO BE SUBMITTED AND REVIEWED. FBC ENERGY CONSERVATION
 R103.2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-06 Cont ID  
Sent By rmcdouga Date 2017-07-06 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2017-06-16 Time 13:13 Sent To  
Notes
2017-06-19 13:13:53RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-05 Cont ID  
Sent By rmcdouga Date 2017-06-05 Time 09:49 Rev Time 0.00
Received By rmcdouga Date 2017-05-30 Time 13:11 Sent To  
Notes
2017-05-31 13:11:11REVISION ROUTED TO RMCDOUGAL