Plan Review Details - Permit 17051202
Plan Review Stops For Permit 17051202
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-11 Cont ID  
Sent By jwitmer Date 2017-07-11 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2017-07-11 Time 16:52 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-06 Cont ID  
Sent By jwitmer Date 2017-07-06 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2017-07-06 Time 07:45 Sent To  
Notes
2017-07-06 08:51:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17051202
 ADD: 410 EVERNIA ST. SUITE: MANAGEMENT OFFICE
 CONT: HARTZELL
 TEL: 954-957-9711
 E-MAIL: [email protected]
 [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 2ND REVIEW
 DATE: THURS. JULY 06/2017
 ACTION: DENIED
 1)COMPLIED. VALUE OF THE PROJECT.
  
 2) 2ND REQUEST. THE SUBMITTED PLANS DOES NOT INCLUDE A
 TITLE STRIP OF WHO THE AUTHOR IS OF THE PLANS. THE
 QUALIFIER FOR THE COMPANY NEEDS TO PRINT THEIR NAME,
 SIGN THEIR NAME AND PRINT THEIR LICENSE NUMBER ON THE
 PLANS AND IDENTIFY THE PROJECT BY ADDRESS. 107.2.1.
 INFORMATION ON THE CONSTRUCTION DOCUMENTS.
  
 3) 2ND REQUEST. THE PLANS ARE MISSING INFORMATION: 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 3A)2ND REQUEST. MINIMUM TYPE OF CONSTRUCTION SHALL BE
 DETERMINED BY FBC-B TABLE 503
  
 3B)2ND REQUEST. GROUP OCCUPANCY GROUP
  
 3C) 2ND REQUEST. PLANS DRAWN TO SCALE
  
 3D)2ND REQUEST. NEW WALL CONSTRUCTION DETAIL/ CUT
 SECTION/ MATERIALS/ ANCHORAGE OF WALL/ HIGHRISE
  
 3E) 2ND REQUEST, SEMI-COMPLIED. THE NEW PLAN INDICATES
 THE INSTALLATION OF A 32 INCH X 80 INCH NEW DOOR. THE
 2014 FBC-B 1008.1.1 MINIMUM DOOR SIZE IS A 32 INCH
 CLEAR WIDTH, A 2 FT. 10 INCH DOOR WILL NOT MAKE A 32
 INCH CLEAR OPENING FOR EGRESS DOORS.
 2014 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM WIDTH OF
 EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT
 LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32
 INCHES. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 4)COMPLIED. 2014 FBC-ACCESS. CODE 404.2.6 DOORS IN
 SERIES AND GATES IN SERIES.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-02 Cont ID  
Sent By jwitmer Date 2017-06-02 Time 07:33 Rev Time 0.00
Received By jwitmer Date 2017-06-02 Time 07:02 Sent To  
Notes
2017-06-02 07:33:212014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17051202
 ADD: 410 EVERNIA ST. SUITE: MANAGEMENT OFFICE
 CONT: HARTZELL
 TEL: 954-957-9711
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 02/2017
 ACTION: DENIED
  
 1) VALUE OF THE PROJECT IS LOW, PLEASE PROVIDE AN
 ACCURATE VALUE FOR THIS PROJECT. PERMIT FEES/ PLAN
 REVIEW:
 W P B ADMINISTRATIVE CODE 108.3* BUILDING PERMIT
 VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR PLUMBING
 SYSTEMS APPEARS TO BE UNDER ESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE SUBMITTED PLANS DOES NOT INCLUDE A TITLE STRIP
 OF WHO THE AUTHOR IS OF THE PLANS. THE QUALIFIER FOR
 THE COMPANY NEEDS TO PRINT THEIR NAME, SIGN THEIR NAME
 AND PRINT THEIR LICENSE NUMBER ON THE PLANS AND
 IDENTIFY THE PROJECT BY ADDRESS. 107.2.1. INFORMATION
 ON THE CONSTRUCTION DOCUMENTS.
  
 3) THE PLANS ARE MISSING INFORMATION: 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 3A) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED BY
 FBC-B TABLE 503
 3B) OCCUPANCY GROUP
 3C) PLANS DRAWN TO SCALE
 3D) NEW WALL CONSTRUCTION DETAIL/ CUT SECTION/
 MATERIALS/ ANCHORAGE OF WALL/ HIGHRISE
 3E) NEW DOOR SIZE, NOT NOTED. 2014 FBC-B 1008.1.1
 MINIMUM DOOR SIZE IS A 32 INCH CLEAR WIDTH OR A 2 FT.
 10 INCH DOOR.
  
 4) 2014 FBC-ACCESS. CODE 404.2.6 DOORS IN SERIES AND
 GATES IN SERIES. THE DISTANCE BETWEEN TWO HINGED OR
 PIVOTED DOORS IN SERIES AND GATES IN SERIES SHALL BE 48
 INCHES MINIMUM PLUS THE WIDTH OF DOORS SWINGING INTO
 THE SPACE.
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-07-13 Cont ID  
Sent By pleduc Date 2017-07-13 Time   Rev Time 0.00
Received By pleduc Date 2017-07-13 Time 10:13 Sent To PC
Notes
2017-07-13 10:17:09THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) WITH ANY DEMO OR INSTALLATION OF WALLS, A REVIEW OF
 ANY EXISTING FIRE SPRINKLERS SHALL BE REVIEWED FOR CODE
 COMPLIANT COVERAGE.
  
 ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-06-09 Cont ID  
Sent By pleduc Date 2017-06-09 Time   Rev Time 0.00
Received By pleduc Date 2017-06-08 Time 10:33 Sent To B
Notes
2017-06-09 12:13:012 ND REVIEW
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE COMMENTS MUST BE ADDRESSED SPECIFICALLYAND
 INFORMATION RELATING TO THEM PROVIDED ON THE PLAN
 SHEETS OR AN ATTACHED LETTER.
  
  
  
  
 1) THERE IS INSUFFICIENT DETAIL SUBMITTED TO COMPLETE
 AN ACCURATE REVIEW PER THE FLORIDA FIRE PREVENTION
 CODE.
  
 LACKING INFORMATION NOTED BELOW
  
 FAILED
  
  
 2) CONFIRMED
  
  
 3) THERE IS NO NOTE OF REVIEW AND/OR COMPLIANCE WITH
 THE FLORIDA FIRE PREVENTION CODE, 5TH EDITION.
  
 PLEASE ENSURE A REVIEW AND A NOTE OR COMPLIANCE.
  
 NOT PROVIDED
  
 FAILED
  
  
 4) CONFIRMED
  
  
  
 5) IT APPEARS THAT TWO NEW DOORS ARE BEING INSTALLED.
 THERE IS NO DOOR SCHEDULE AND/OR HARDWARE MEETING THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 PLEASE PROVIDE.
  
 NOT PROVIDED
  
 FAILED
  
  
  
 6) THERE IS NO INDICATIONS OF ANY EXISTING FIRE ALARM
 OR FIRE SPRINKLER SYSTEM.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
 NOT PROVIDED
  
 FAILED
  
  
 7) THERE IS NO INDICATION OF A WALL SCHEDULE.
  
 PLEASE PROVIDE.
  
 NOT PROVIDED
  
 FAILED
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-05-30 Cont ID  
Sent By pleduc Date 2017-05-30 Time   Rev Time 0.00
Received By pleduc Date 2017-05-30 Time 11:48 Sent To B
Notes
2017-05-30 12:33:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS INSUFFICIENT DETAIL SUBMITTED TO COMPLETE
 AN ACCURATE REVIEW PER THE FLORIDA FIRE PREVENTION
 CODE.
  
  
 2) THERE IS NO TITLE BLOCK INDICATING THE ADDRESS,
 SUITE # OR DESIGNER NAME ON THE DRAWING SHEETS.
  
 PLEASE PROVIDE.
  
  
 3) THERE IS NO NOTE OF REVIEW AND/OR COMPLIANCE WITH
 THE FLORIDA FIRE PREVENTION CODE, 5TH EDITION.
  
 PLEASE ENSURE A REVIEW AND A NOTE OR COMPLIANCE.
  
  
 4) THERE IS NO SCOPE OF WORK.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK NOTE OR
 NARRATIVE.
  
  
  
 5) IT APPEARS THAT TWO NEW DOORS ARE BEING INSTALLED.
 THERE IS NO DOOR SCHEDULE AND/OR HARDWARE MEETING THE
 REQUIRMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 PLEASE PROVIDE.
  
  
 6) THERE IS NO INDICATIONS OF ANY EXISTING FIRE ALARM
 OR FIRE SPRINKLER SYSTEM.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
 7) THERE IS NO INDICATION OF A WALL SCHEDULE.
  
 PLEASE PROVIDE.
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-13 Cont ID  
Sent By pleduc Date 2017-07-13 Time   Rev Time 0.00
Received By pleduc Date 2017-07-11 Time 16:50 Sent To  
Notes
2017-07-11 17:12:16SENT TO J. W. DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-06 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-06 Time 09:59 Sent To  
Notes
2017-06-07 09:59:47RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-02 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-26 Time 09:13 Sent To  
Notes
2017-05-30 09:13:31ROUTED TO FIRE INBOX