Plan Review Details - Permit 17051075
Plan Review Stops For Permit 17051075
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-08-25 Cont ID  
Sent By jgomez Date 2017-08-25 Time 18:25 Rev Time 0.00
Received By jgomez Date 2017-08-25 Time 17:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-08-18 Cont ID  
Sent By jgomez Date 2017-08-18 Time 09:25 Rev Time 0.00
Received By jgomez Date 2017-08-17 Time 18:22 Sent To  
Notes
2017-08-17 18:23:55RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- THE PROPOSED ROOF WORK FOR THE FLAT ROOF IS TO
 RECOVER THE DECK. GENERAL LIMITATION #5 OF RECOVER DECK
 NOA 13-1022.13 SUBMITTED REQUIRES A FASTENER WITHDRAWAL
 TEST TAS 105. TEST NEEDS TO BE PERFORMED. PROVIDE 2
 COPIES OF THE SIGNED AND SEALED TEST. NOTE: IF THE
 TESTED FASTENER VALUE IS LESS THAN 275 LBF, THEN
 INSULATION ATTACHMENT SHALL NOT BE ACCEPTABLE. SEE
 GENERAL LIMITATION #5 ON LAST PAGE OF NOA.
  
 2- ENGINEER TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED:
 THE FASTENER SPACING FOR THE FIELD AREA DOESN'T MATCH
 THE FASTENER SPACING SHOWN ON THE NOA SUBMITTED. REVISE
 AS REQUIRED BY SEC. 8.1 RAS 117.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-07 Cont ID  
Sent By jgomez Date 2017-08-07 Time 13:10 Rev Time 0.00
Received By jgomez Date 2017-08-07 Time 12:50 Sent To  
Notes
2017-08-07 13:10:17 
 08/07/17 MET WITH CONTRACTOR. HE SAID THE FLAT ROOF IS
 A ROOF OVER. I TOLD HIM HE NEEDS A PRODUCT APPROVAL FOR
 ROOFOVER APPLICATION AND ENGINEERING NEEDS TO BE
 REVISED TO MATCH NEW PRODUCT APPROVAL. TOLD HIM TO
 REVIEW THE LIMITATIONS ON THE ROOF OVER PRODUCT
 APPROVAL. TESTING MAY BE REQUIRED. JG.
  
  
  
 RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED:
 (A) SPECIFIC ROOFING ASSEMBLY TO BE INSTALLED IS NOT
 CLEAR. THE SYSTEM TYPE SPECIFIED BY THE ENGINEER IS: "A
 PAGE 6,7". THIS IS AN INSULATED SYSTEM. IT DOESN'T
 MATCH THE SYSTEM TYPE HIGHLIGHTED BY THE ROOFING
 CONTRACTOR. ROOFING CONTRACTOR HIGHLIGHTED A
 NON-INSULATED SYSTEM TYPE E ON PAGE 14 AND 15 OF 16.
 COORDINATE WITH ROOFING CONTRACTOR EXACT SYSTEM TO BE
 INSTALLED AND REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 (B) SCOPE OF WORK IS NOT CLEAR. THIS IS NOT A "RECOVER"
 ROOF PROJECT. THIS IS A RE-ROOF PROJECT. SEE PRODUCT
 APPROVAL SUBMITTED AND REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-24 Cont ID  
Sent By jgomez Date 2017-05-24 Time 18:29 Rev Time 0.00
Received By jgomez Date 2017-05-24 Time 18:14 Sent To  
Notes
2017-05-24 18:31:49RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED:
 (A) SPECIFIC ROOFING ASSEMBLY TO BE INSTALLED IS NOT
 CLEAR. THE SYSTEM TYPE SPECIFIED BY THE ENGINEER IS: "A
 PAGE 6,7". THIS IS AN INSULATED SYSTEM. IT DOESN'T
 MATCH THE SYSTEM TYPE HIGHLIGHTED BY THE ROOFING
 CONTRACTOR. ROOFING CONTRACTOR HIGHLIGHTED A
 NON-INSULATED SYSTEM TYPE E ON PAGE 14 AND 15 OF 16.
 COORDINATE WITH ROOFING CONTRACTOR EXACT SYSTEM TO BE
 INSTALLED AND REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 (B) SCOPE OF WORK IS NOT CLEAR. THIS IS NOT A "RECOVER"
 ROOF PROJECT. THIS IS A RE-ROOF PROJECT. SEE PRODUCT
 APPROVAL SUBMITTED AND REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-08-25 Cont ID  
Sent By jgomez Date 2017-08-25 Time 18:25 Rev Time 0.00
Received By jgomez Date 2017-08-24 Time 14:25 Sent To  
Notes
2017-08-25 14:25:32RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-18 Cont ID  
Sent By jgomez Date 2017-08-18 Time 09:44 Rev Time 0.00
Received By jgomez Date 2017-08-16 Time 13:51 Sent To  
Notes
2017-08-17 13:51:48RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-07 Cont ID  
Sent By jgomez Date 2017-08-07 Time 13:10 Rev Time 0.00
Received By jgomez Date 2017-08-07 Time 12:49 Sent To  
Notes
2017-08-07 12:50:05MET WITH CONTRACTOR. HE SAID THE FLAT ROOF IS A
 ROOFOVER. TOLD HIM NEED PRODUCT APPROVAL FOR ROOF OVER
 APPLICATION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-24 Cont ID  
Sent By jgomez Date 2017-05-24 Time 18:31 Rev Time 0.00
Received By jgomez Date 2017-05-24 Time 13:43 Sent To  
Notes
2017-05-24 13:43:52JGOMEZ