Plan Review Details - Permit 17051039
Plan Review Stops For Permit 17051039
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-07-12 Cont ID  
Sent By rmcdouga Date 2017-07-12 Time 11:13 Rev Time 0.00
Received By rmcdouga Date 2017-07-12 Time 11:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-07-12 Cont ID  
Sent By rmcdouga Date 2017-07-12 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2017-07-12 Time 07:51 Sent To  
Notes
2017-07-12 07:51:09PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TESTS THAT WERE SUBMITTED DO NOT MATCH THE SITE
 CONDITIONS. THE SITE HAS A 7" THICK SLAB AND THE TESTS
 WERE DONE ON AN 8" THICK SLAB. THERE ARE AREAS THAT DO
 NOT NOT HAVE A SUSPENDED CEILING AND THE TESTS WERE
 DONE WITH A SUSPENDED CEILING. FBC 107.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-30 Cont ID  
Sent By rmcdouga Date 2017-06-30 Time 17:16 Rev Time 0.00
Received By rmcdouga Date 2017-06-30 Time 16:34 Sent To  
Notes
2017-06-30 17:16:19PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF THE TEST REPORTS OF THE FLAME
 SPREAD FOR THE SOUND UNDERLAYMENT. FBC 603.1 FLAME
 SPREAD - ASTM E 84-09
  
 2) PROVIDE A DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 THE TEST REPORTS FOR THE SAM 90 SOUND UNDERLAYMENT WERE
 DONE ON AN 8 INCH CONCRETE FLOOR ASSEMBLY WITH A
 SUSPENDED GYPSUM BOARD CEILING GRID SYSTEM AND 3.5 INCH
 UNFACED BATT INSULATION LAID OVER THE GRID SYSTEM. THIS
 IS NOT THE SITE CONDITION FOR YOUR PROJECT. THE KITCHEN
 AND BATH AREAS HAVE SUSPENDED CEILINGS WITHOUT THE BATT
 INSULATION AND THE OTHER AREAS HAVE THE EXPOSED FLOOR
 SLAB. FBC 107.2.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-22 Cont ID  
Sent By rmcdouga Date 2017-06-22 Time 17:27 Rev Time 0.00
Received By rmcdouga Date 2017-06-22 Time 17:27 Sent To  
Notes
2017-06-22 18:24:00REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-06-08 Cont ID  
Sent By jleahy Date 2017-06-08 Time 16:14 Rev Time 0.00
Received By jleahy Date 2017-06-08 Time 16:14 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-07-12 Cont ID  
Sent By rmcdouga Date 2017-07-12 Time 11:14 Rev Time 0.00
Received By rmcdouga Date 2017-07-12 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-12 Cont ID  
Sent By rmcdouga Date 2017-07-12 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2017-07-07 Time 10:16 Sent To  
Notes
2017-07-10 10:17:03MCDOUGAL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-30 Cont ID  
Sent By rmcdouga Date 2017-06-30 Time 17:16 Rev Time 0.00
Received By rmcdouga Date 2017-06-27 Time 09:58 Sent To  
Notes
2017-06-28 09:58:19RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-22 Cont ID  
Sent By rmcdouga Date 2017-06-22 Time 18:38 Rev Time 0.00
Received By rmcdouga Date 2017-06-06 Time 13:30 Sent To  
Notes
2017-06-07 13:30:23ROUTED TO ELECTRICAL INBOX