Plan Review Details - Permit 17051018
Plan Review Stops For Permit 17051018
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-06 Cont ID  
Sent By jwitmer Date 2017-07-06 Time 14:00 Rev Time 0.00
Received By jwitmer Date 2017-07-06 Time 12:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-12 Cont ID  
Sent By shill Date 2017-06-12 Time 10:31 Rev Time 0.00
Received By shill Date 2017-06-12 Time 09:43 Sent To  
Notes
2017-06-12 09:51:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1. REVISE PLAN TO INCLUDE ALL INFORMATION REQUIRED TO
 BE ON THE TITLE BLOCK FOR THE ARCHITECT, FLORIDA
 STATUTE 481, FLORIDA ADMINISTRATIVE CODE 61G1-16.004.
  
 2. COMMENT FROM FIRST REVIEW, NOT ADDRESSED:
  
 PLEASE IDENTIFY THE SCOPE OF WORK. THE PERMIT
 APPLICATION INDICATES REPAIRS, THIS APPEARS TO BE A
 LEVEL II ALTERATION UNDER THE WORK AREA METHOD OF THE
 2014 EXISTING BUILDING CODE. PLEASE DECLARE LEVEL OF
 ALTERATION:
  
 REPAIRS. REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE THE
 PATCHING OR RESTORATION OR REPLACEMENT OF DAMAGED
 MATERIALS, ELEMENTS, EQUIPMENT OR FIXTURES FOR THE
 PURPOSE OF MAINTAINING SUCH COMPONENTS IN GOOD OR SOUND
 CONDITION WITH RESPECT TO EXISTING LOADS OR PERFORMANCE
 REQUIREMENTS.
  
 LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT
 OR THE COVERING OF EXISTING MATERIALS, ELEMENTS,
 EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS,
 EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE.
  
 LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF
 SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
  
 2ND REVIEW, PROJECT DESCRIPTION IS "REPAIRS." IT IS NOT
 CLEAR WHAT IS BEING REPAIRED.
 SOME WORK WAS ALREADY DONE WITHOUT PERMIT. THE FIRST
 PLAN SUBMITTED SHOWS DEMO OF THE ACOUSTIC CEILING; NEW
 PLAN DOES NOT SHOW THIS WORK.
  
 CONFIRM THAT ALL WORK PROPOSED, INCLUDING WORK DONE
 WITHOUT PERMITS, IS INCLUDED ON THE PLAN.
  
 REVISE PLAN TO SHOW NATURE OF "REPAIRS" OR DECLARE
 LEVEL OF ALTERATION. BASED ON THE PLAN SUBMITTED, THIS
 APPEARS TO BE A LEVEL 2 ALTERATION; REVISE PLAN
 ACCORDINGLY.
  
 3. COMMENT FROM FIRST REVIEW, NOT ADDRESSED:
  
 PLEASE INSPECT BEFORE REMOVAL OF WALL, NOTE ON THE
 PLANS WHERE THE DOOR, SIDELIGHTS, DOOR FRAME, AND WALL
 SECTION ARE BEING REMOVED THIS IS A NON-BEARING WALL.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4. PLAN REFERENCES EXISTING MARBLE, SHOWS REMOVAL OF
 CARPET IN SOME AREAS AS WELL AS INSTALLATION OF TILE.
  
 SEE FBC A 404.3; REVISE PLAN TO SHOW PROPOSED ELEVATION
 CHANGES BETWEEN THE NEW TILE AREAS AND EXISTING AREAS
 WHICH WILL NOT BE ALTERED.
  
 5. FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB. A COST BREAKDOWN (LABOR, MATERIALS, ETC.) MAY ALSO
 BE REQUIRED. VALUE ON APPLICATION IS UNREASONABLY LOW.
  
 6. WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-26 Cont ID  
Sent By jwitmer Date 2017-05-26 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2017-05-26 Time 09:21 Sent To  
Notes
2017-05-26 09:35:422014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17051018
 ADD: 801 SPENCER DR.
 CONT: RJS CONSTRUCTION
 TEL: 561-795-4712
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY26/2017
 ACTION: DENIED
  
 1) THE PLANS DOES NOT HAVE THE WHO THE AUTHOR OF THE
 PLANS IS? PLEASE PRINT THE NAME, SIGN NAME AND LICENSE
 NUMBER OF THE QUALIFIER OF LICENSED IN THE TRADE THE
 PLANS ARE FOR. EXAMPLE, THE CGC CAN ONLY DRAW PLANS FOR
 THE BUILDING UNLESS ADDITIONAL LICENSES ARE HELD.
 107.3.4.3 CERTIFICATIONS BY CONTRACTORS.
  
 2) PLEASE IDENTIFY THE SCOPE OF WORK. THE PERMIT
 APPLICATION INDICATES REPAIRS, THIS APPEARS TO BE A
 LEVEL II ALTERATION UNDER THE WORK AREA METHOD OF THE
 2014 EXISTING BUILDING CODE. PLEASE DECLARE LEVEL OF
 ALTERATION:
 REPAIRS. REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE THE
 PATCHING OR RESTORATION OR REPLACEMENT OF DAMAGED
 MATERIALS, ELEMENTS, EQUIPMENT OR FIXTURES FOR THE
 PURPOSE OF MAINTAINING SUCH COMPONENTS IN GOOD OR SOUND
 CONDITION WITH RESPECT TO EXISTING LOADS OR PERFORMANCE
 REQUIREMENTS.
  
 LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT
 OR THE COVERING OF EXISTING MATERIALS, ELEMENTS,
 EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS,
 EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE.
  
 LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF
 SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
  
 3) PLEASE INSPECT BEFORE REMOVAL OF WALL, NOTE ON THE
 PLANS WHERE THE DOOR, SIDELIGHTS, DOOR FRAME, AND WALL
 SECTION ARE BEING REMOVED THIS IS A NON-BEARING WALL.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-10 Cont ID  
Sent By jpearson Date 2017-07-10 Time 08:07 Rev Time 0.00
Received By jpearson Date 2017-07-10 Time 08:07 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-13 Cont ID  
Sent By jleahy Date 2017-06-13 Time 12:30 Rev Time 0.00
Received By jleahy Date 2017-06-13 Time 12:30 Sent To  
Notes
2017-06-13 08:27:25FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 C405.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND
 C405.2.4.
  
 C405.2.2.2 OCCUPANCY SENSORS.
 OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS,
 PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND
 JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET
 (28 M2) OR LESS ENCLOSED
 BY FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC
 CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY
 TURN OFF LIGHTS WITHIN
 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND
 SHALL EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO
 AUTOMATICALLY TURN THE
 LIGHTING ON TO NOT MORE THAN 50 PERCENT POWER.
  
 EXCEPTION: FULL AUTOMATIC-ON CONTROLS SHALL BE
 PERMITTED TO CONTROL LIGHTING IN PUBLIC CORRIDORS,
 STAIRWAYS, RESTROOMS,
 PRIMARY BUILDING ENTRANCE AREAS AND LOBBIES, AND AREAS
 WHERE MANUAL-ON OPERATION WOULD ENDANGER THE SAFETY OR
 SECURITY
 OF THE ROOM OR BUILDING OCCUPANTS.
  
 E3706.2 PANELBOARD CIRCUIT IDENTIFICATION.
 ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY
 IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE.
 THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO
 ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS.
 SPARE POSITIONS
 THAT CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES
 SHALL BE DESCRIBED ACCORDINGLY. THE IDENTIFICATION
 SHALL BE INCLUDED
 IN A CIRCUIT DIRECTORY LOCATED ON THE FACE OF THE
 PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR. CIRCUITS
 SHALL NOT BE DESCRIBED
 IN A MANNER THAT DEPENDS ON TRANSIENT CONDITIONS OF
 OCCUPANCY.
  
 408.6 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION.
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE
 IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF
 DETAIL THAT ALLOWS
 EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE
 POSITIONS THAT CONTAIN UNUSED OVERCURRENT DEVICES OR
 SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE
 FACE OR INSIDE OF THE
 PANEL DOOR IN THE CASE OF A PANELBOARD AND AT EACH
 SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD OR
 SWITCHGEAR. NO CIRCUIT SHALL
 BE DESCRIBED IN A MANNER THAT DEPENDS ON TRANSIENT
 CONDITIONS OF OCCUPANCY NEC 2011

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-30 Cont ID  
Sent By jleahy Date 2017-05-30 Time 18:32 Rev Time 0.00
Received By jleahy Date 2017-05-30 Time 18:32 Sent To  
Notes
2017-05-30 18:32:55JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 SEE MECHANICAL REVIEWERS COMMENTS

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-07-05 Cont ID  
Sent By pleduc Date 2017-07-05 Time   Rev Time 0.00
Received By pleduc Date 2017-07-03 Time 16:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-06-12 Cont ID  
Sent By pleduc Date 2017-06-12 Time   Rev Time 0.00
Received By pleduc Date 2017-06-12 Time 12:37 Sent To  
Notes
2017-06-12 13:11:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) SHEET A 1.1 - THERE IS A NOTE THAT WAS NOT SUBMITTED
 WITH THE ORIGINAL, INDICATING A NEW WOOD FINISH APPLIED
 TO THE CEILING.
  
 PER NFPA 101, CHAPTER 39, EXISTING BUSINESS
 OCCUPANCIES,
  
  
 39.3.3.2 INTERIOR WALL AND CEILING FINISH.
 39.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIALS
 COMPLYING WITH SECTION 10.2 SHALL BE CLASS A OR CLASS B
 IN EXITS AND IN EXIT ACCESS CORRIDORS.
 39.3.3.2.2 INTERIOR WALL AND CEILING FINISHES SHALL BE
 CLASS A, CLASS B, OR CLASS C IN AREAS OTHER THAN THOSE
 SPECIFIED IN 39.3.3.2.1.
  
  
 10.2* INTERIOR FINISH.
 10.2.1* GENERAL.
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN ACCORDANCE WITH TESTS MADE UNDER CONDITIONS
 SIMULATING ACTUAL INSTALLATIONS, PROVIDED THAT THE
 AUTHORITY HAVING JURISDICTION IS PERMITTED TO ESTABLISH
 THE CLASSIFICATION OF ANY MATERIAL ON WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE PROVIDED IN 10.2.1.2 OR 10.2.1.3.
 10.2.1.2 MATERIALS APPLIED DIRECTLY TO THE SURFACE OF
 WALLS AND CEILINGS IN A TOTAL THICKNESS OF LESS THAN
 1?28 IN. (0.9 MM) SHALL NOT BE CONSIDERED INTERIOR
 FINISH AND SHALL BE EXEMPT FROM TESTS SIMULATING ACTUAL
 INSTALLATION IF THEY MEET THE REQUIREMENTS OF CLASS A
 INTERIOR WALL OR CEILING FINISH WHEN TESTED IN
 ACCORDANCE WITH 10.2.3 USING FIBER CEMENT BOARD AS THE
 SUBSTRATE MATERIAL.
 10.2.1.3 APPROVED EXISTING INSTALLATIONS OF MATERIALS
 APPLIED DIRECTLY TO THE SURFACE OF WALLS AND CEILINGS
 IN A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM)
 SHALL BE PERMITTED TO REMAIN IN USE, AND THE PROVISIONS
 OF 10.2.2 THROUGH 10.2.3.7.2 SHALL NOT APPLY.
  
  
 PLEASE PROVIDE THE APPLICABLE MANUFACTURES SPEC SHEETS
 AND AN APPLICABLE NOTE OF COMPLIANCE WITH THE
 REQUIREMENT ON THE PLAN SHEET.
  
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-05-30 Cont ID  
Sent By pleduc Date 2017-05-30 Time   Rev Time 0.00
Received By pleduc Date 2017-05-30 Time 11:46 Sent To  
Notes
2017-05-30 14:12:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATIONS OF AN EXIT SIGN AT THE
 RECEPTION AREA LEADING TO THE FRONT LOBBY EXIT.
  
 PER NFPA 101, CHAPTER 39, EXISTING BUSINESS
 OCCUPANCIES.
  
 39.2.7 DISCHARGE FROM EXITS. EXIT DISCHARGE SHALL
 COMPLY WITH SECTION 7.7.
  
 39.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 39.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 7.7.3 ARRANGEMENT AND MARKING OF EXIT DISCHARGE.
  
 7.7.3.2 THE EXIT DISCHARGE SHALL BE ARRANGED AND MARKED
 TO MAKE CLEAR THE DIRECTION OF EGRESS TRAVEL FROM THE
 EXIT DISCHARGE TO A PUBLIC WAY.
  
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS,AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS,
 SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT ENCLOSURE SHALL BE MARKED BY APPROVED
 EXIT OR DIRECTIONAL EXIT SIGNS WHERE THE CONTINUATION
 OF THE EGRESS PATH IS NOT OBVIOUS. PLEASE ENSURE ONE IS
 EXISTING OR PROVIDE.
  
  
 PLEASE NOTE IF ONE IS EXISTING OR PROVIDE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-07-12 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-29 Time 11:45 Sent To  
Notes
2017-06-30 11:46:08B22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-06-15 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-08 Time 09:49 Sent To  
Notes
2017-06-09 09:49:59B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-30 Cont ID  
Sent By jleahy Date 2017-05-30 Time 18:33 Rev Time 0.00
Received By jleahy Date 2017-05-23 Time 10:01 Sent To  
Notes
2017-05-24 10:01:28B03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-26 Cont ID  
Sent By jwitmer Date 2017-05-26 Time 09:21 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-07-12 Cont ID  
Sent By ccole Date 2017-07-12 Time 09:49 Rev Time 0.00
Received By ccole Date 2017-07-12 Time 09:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-15 Cont ID  
Sent By ccole Date 2017-06-15 Time 15:55 Rev Time 0.00
Received By ccole Date 2017-06-15 Time 15:55 Sent To  
Notes
2017-06-15 15:59:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17051018
 6/15/17
  
 1) THE WORK DESCRIPTION ON THE MECHANICAL SUB-PERMIT
 INDICATES DUCTS ARE BEING RELOCATED TO NEW DIFFUSER
 LOCATIONS, HOWEVER THE PLAN IS INDICATING DIFFUSERS AND
 GRILLS TO BE REPLACED IN THE SAME LOCATIONS- NO DUCT
 RELOCATIONS ARE SHOWN. PLEASE REVIEW BUILDING COMMENTS
 AND PROVIDE THE COMPLETE SCOPE OF THE PROPOSED PROJECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-30 Cont ID  
Sent By ccole Date 2017-05-30 Time 07:57 Rev Time 0.00
Received By ccole Date 2017-05-30 Time 07:36 Sent To  
Notes
2017-05-30 08:01:331ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17051018
 5/30/17
  
 1) PROVIDE A REFLECTIVE CEILING PLAN THAT DETAILS THE
 NEW ASSEMBLY, AND SHOWS THE NEW LOCATIONS OF THE
 DIFFUSERS AND RETURN GRILLS.
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1
 WPB AMENDMENTS TO THE FBC. (SEE ALSO SECTION 107.3.5).
  
 3) COMPLY WITH BUILDING REVIEW COMMENTS AND PROVIDE THE
 CORRECT CODE DATA AND SCOPE OF WORK FOR THE PROPOSED
 PROJECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  