Plan Review Details - Permit 17051018
| Plan Review Stops For Permit 17051018 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-07-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-07-06 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-07-06 |
Time |
12:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-06-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-12 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-12 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2017-06-12 09:51:54 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1. REVISE PLAN TO INCLUDE ALL INFORMATION REQUIRED TO | | | BE ON THE TITLE BLOCK FOR THE ARCHITECT, FLORIDA | | | STATUTE 481, FLORIDA ADMINISTRATIVE CODE 61G1-16.004. | | | | | | 2. COMMENT FROM FIRST REVIEW, NOT ADDRESSED: | | | | | | PLEASE IDENTIFY THE SCOPE OF WORK. THE PERMIT | | | APPLICATION INDICATES REPAIRS, THIS APPEARS TO BE A | | | LEVEL II ALTERATION UNDER THE WORK AREA METHOD OF THE | | | 2014 EXISTING BUILDING CODE. PLEASE DECLARE LEVEL OF | | | ALTERATION: | | | | | | REPAIRS. REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE THE | | | PATCHING OR RESTORATION OR REPLACEMENT OF DAMAGED | | | MATERIALS, ELEMENTS, EQUIPMENT OR FIXTURES FOR THE | | | PURPOSE OF MAINTAINING SUCH COMPONENTS IN GOOD OR SOUND | | | CONDITION WITH RESPECT TO EXISTING LOADS OR PERFORMANCE | | | REQUIREMENTS. | | | | | | LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT | | | OR THE COVERING OF EXISTING MATERIALS, ELEMENTS, | | | EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS, | | | EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE. | | | | | | LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF | | | SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR | | | WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, | | | OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. | | | | | | 2ND REVIEW, PROJECT DESCRIPTION IS "REPAIRS." IT IS NOT | | | CLEAR WHAT IS BEING REPAIRED. | | | SOME WORK WAS ALREADY DONE WITHOUT PERMIT. THE FIRST | | | PLAN SUBMITTED SHOWS DEMO OF THE ACOUSTIC CEILING; NEW | | | PLAN DOES NOT SHOW THIS WORK. | | | | | | CONFIRM THAT ALL WORK PROPOSED, INCLUDING WORK DONE | | | WITHOUT PERMITS, IS INCLUDED ON THE PLAN. | | | | | | REVISE PLAN TO SHOW NATURE OF "REPAIRS" OR DECLARE | | | LEVEL OF ALTERATION. BASED ON THE PLAN SUBMITTED, THIS | | | APPEARS TO BE A LEVEL 2 ALTERATION; REVISE PLAN | | | ACCORDINGLY. | | | | | | 3. COMMENT FROM FIRST REVIEW, NOT ADDRESSED: | | | | | | PLEASE INSPECT BEFORE REMOVAL OF WALL, NOTE ON THE | | | PLANS WHERE THE DOOR, SIDELIGHTS, DOOR FRAME, AND WALL | | | SECTION ARE BEING REMOVED THIS IS A NON-BEARING WALL. | | | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 4. PLAN REFERENCES EXISTING MARBLE, SHOWS REMOVAL OF | | | CARPET IN SOME AREAS AS WELL AS INSTALLATION OF TILE. | | | | | | SEE FBC A 404.3; REVISE PLAN TO SHOW PROPOSED ELEVATION | | | CHANGES BETWEEN THE NEW TILE AREAS AND EXISTING AREAS | | | WHICH WILL NOT BE ALTERED. | | | | | | 5. FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS | | | JOB. A COST BREAKDOWN (LABOR, MATERIALS, ETC.) MAY ALSO | | | BE REQUIRED. VALUE ON APPLICATION IS UNREASONABLY LOW. | | | | | | 6. WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-05-26 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-05-26 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2017-05-26 09:35:42 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17051018 | | | ADD: 801 SPENCER DR. | | | CONT: RJS CONSTRUCTION | | | TEL: 561-795-4712 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: FRI. MAY26/2017 | | | ACTION: DENIED | | | | | | 1) THE PLANS DOES NOT HAVE THE WHO THE AUTHOR OF THE | | | PLANS IS? PLEASE PRINT THE NAME, SIGN NAME AND LICENSE | | | NUMBER OF THE QUALIFIER OF LICENSED IN THE TRADE THE | | | PLANS ARE FOR. EXAMPLE, THE CGC CAN ONLY DRAW PLANS FOR | | | THE BUILDING UNLESS ADDITIONAL LICENSES ARE HELD. | | | 107.3.4.3 CERTIFICATIONS BY CONTRACTORS. | | | | | | 2) PLEASE IDENTIFY THE SCOPE OF WORK. THE PERMIT | | | APPLICATION INDICATES REPAIRS, THIS APPEARS TO BE A | | | LEVEL II ALTERATION UNDER THE WORK AREA METHOD OF THE | | | 2014 EXISTING BUILDING CODE. PLEASE DECLARE LEVEL OF | | | ALTERATION: | | | REPAIRS. REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE THE | | | PATCHING OR RESTORATION OR REPLACEMENT OF DAMAGED | | | MATERIALS, ELEMENTS, EQUIPMENT OR FIXTURES FOR THE | | | PURPOSE OF MAINTAINING SUCH COMPONENTS IN GOOD OR SOUND | | | CONDITION WITH RESPECT TO EXISTING LOADS OR PERFORMANCE | | | REQUIREMENTS. | | | | | | LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT | | | OR THE COVERING OF EXISTING MATERIALS, ELEMENTS, | | | EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS, | | | EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE. | | | | | | LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF | | | SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR | | | WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, | | | OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. | | | | | | 3) PLEASE INSPECT BEFORE REMOVAL OF WALL, NOTE ON THE | | | PLANS WHERE THE DOOR, SIDELIGHTS, DOOR FRAME, AND WALL | | | SECTION ARE BEING REMOVED THIS IS A NON-BEARING WALL. | | | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-07-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-07-10 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-07-10 |
Time |
08:07 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-06-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-06-13 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-06-13 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2017-06-13 08:27:25 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | C405.2 LIGHTING CONTROLS (MANDATORY). | | | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS | | | SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND | | | C405.2.4. | | | | | | C405.2.2.2 OCCUPANCY SENSORS. | | | OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS, | | | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK | | | ROOMS, | | | PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND | | | JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET | | | (28 M2) OR LESS ENCLOSED | | | BY FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC | | | CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY | | | TURN OFF LIGHTS WITHIN | | | 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND | | | SHALL EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO | | | AUTOMATICALLY TURN THE | | | LIGHTING ON TO NOT MORE THAN 50 PERCENT POWER. | | | | | | EXCEPTION: FULL AUTOMATIC-ON CONTROLS SHALL BE | | | PERMITTED TO CONTROL LIGHTING IN PUBLIC CORRIDORS, | | | STAIRWAYS, RESTROOMS, | | | PRIMARY BUILDING ENTRANCE AREAS AND LOBBIES, AND AREAS | | | WHERE MANUAL-ON OPERATION WOULD ENDANGER THE SAFETY OR | | | SECURITY | | | OF THE ROOM OR BUILDING OCCUPANTS. | | | | | | E3706.2 PANELBOARD CIRCUIT IDENTIFICATION. | | | ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY | | | IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC | | | PURPOSE OR USE. | | | THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO | | | ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. | | | SPARE POSITIONS | | | THAT CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES | | | SHALL BE DESCRIBED ACCORDINGLY. THE IDENTIFICATION | | | SHALL BE INCLUDED | | | IN A CIRCUIT DIRECTORY LOCATED ON THE FACE OF THE | | | PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR. CIRCUITS | | | SHALL NOT BE DESCRIBED | | | IN A MANNER THAT DEPENDS ON TRANSIENT CONDITIONS OF | | | OCCUPANCY. | | | | | | 408.6 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. | | | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY | | | IDENTIFIED AS TO | | | ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE | | | IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF | | | DETAIL THAT ALLOWS | | | EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE | | | POSITIONS THAT CONTAIN UNUSED OVERCURRENT DEVICES OR | | | SWITCHES SHALL BE | | | DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE | | | INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE | | | FACE OR INSIDE OF THE | | | PANEL DOOR IN THE CASE OF A PANELBOARD AND AT EACH | | | SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD OR | | | SWITCHGEAR. NO CIRCUIT SHALL | | | BE DESCRIBED IN A MANNER THAT DEPENDS ON TRANSIENT | | | CONDITIONS OF OCCUPANCY NEC 2011 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-05-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-30 |
Time |
18:32 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-30 |
Time |
18:32 |
Sent To |
|
|
| Notes |
| 2017-05-30 18:32:55 | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | SEE MECHANICAL REVIEWERS COMMENTS |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-07-05 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-07-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-07-03 |
Time |
16:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2017-06-12 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-06-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-06-12 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2017-06-12 13:11:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | | | | 1) SHEET A 1.1 - THERE IS A NOTE THAT WAS NOT SUBMITTED | | | WITH THE ORIGINAL, INDICATING A NEW WOOD FINISH APPLIED | | | TO THE CEILING. | | | | | | PER NFPA 101, CHAPTER 39, EXISTING BUSINESS | | | OCCUPANCIES, | | | | | | | | | 39.3.3.2 INTERIOR WALL AND CEILING FINISH. | | | 39.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIALS | | | COMPLYING WITH SECTION 10.2 SHALL BE CLASS A OR CLASS B | | | IN EXITS AND IN EXIT ACCESS CORRIDORS. | | | 39.3.3.2.2 INTERIOR WALL AND CEILING FINISHES SHALL BE | | | CLASS A, CLASS B, OR CLASS C IN AREAS OTHER THAN THOSE | | | SPECIFIED IN 39.3.3.2.1. | | | | | | | | | 10.2* INTERIOR FINISH. | | | 10.2.1* GENERAL. | | | 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS | | | SHALL BE IN ACCORDANCE WITH TESTS MADE UNDER CONDITIONS | | | SIMULATING ACTUAL INSTALLATIONS, PROVIDED THAT THE | | | AUTHORITY HAVING JURISDICTION IS PERMITTED TO ESTABLISH | | | THE CLASSIFICATION OF ANY MATERIAL ON WHICH | | | CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE, | | | UNLESS OTHERWISE PROVIDED IN 10.2.1.2 OR 10.2.1.3. | | | 10.2.1.2 MATERIALS APPLIED DIRECTLY TO THE SURFACE OF | | | WALLS AND CEILINGS IN A TOTAL THICKNESS OF LESS THAN | | | 1?28 IN. (0.9 MM) SHALL NOT BE CONSIDERED INTERIOR | | | FINISH AND SHALL BE EXEMPT FROM TESTS SIMULATING ACTUAL | | | INSTALLATION IF THEY MEET THE REQUIREMENTS OF CLASS A | | | INTERIOR WALL OR CEILING FINISH WHEN TESTED IN | | | ACCORDANCE WITH 10.2.3 USING FIBER CEMENT BOARD AS THE | | | SUBSTRATE MATERIAL. | | | 10.2.1.3 APPROVED EXISTING INSTALLATIONS OF MATERIALS | | | APPLIED DIRECTLY TO THE SURFACE OF WALLS AND CEILINGS | | | IN A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) | | | SHALL BE PERMITTED TO REMAIN IN USE, AND THE PROVISIONS | | | OF 10.2.2 THROUGH 10.2.3.7.2 SHALL NOT APPLY. | | | | | | | | | PLEASE PROVIDE THE APPLICABLE MANUFACTURES SPEC SHEETS | | | AND AN APPLICABLE NOTE OF COMPLIANCE WITH THE | | | REQUIREMENT ON THE PLAN SHEET. | | | | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-05-30 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-05-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-05-30 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2017-05-30 14:12:38 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS NO INDICATIONS OF AN EXIT SIGN AT THE | | | RECEPTION AREA LEADING TO THE FRONT LOBBY EXIT. | | | | | | PER NFPA 101, CHAPTER 39, EXISTING BUSINESS | | | OCCUPANCIES. | | | | | | 39.2.7 DISCHARGE FROM EXITS. EXIT DISCHARGE SHALL | | | COMPLY WITH SECTION 7.7. | | | | | | 39.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. | | | | | | 39.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10. | | | | | | PER NFPA 101, CHAPTER 7, MEANS OF EGRESS. | | | | | | 7.7.3 ARRANGEMENT AND MARKING OF EXIT DISCHARGE. | | | | | | 7.7.3.2 THE EXIT DISCHARGE SHALL BE ARRANGED AND MARKED | | | TO MAKE CLEAR THE DIRECTION OF EGRESS TRAVEL FROM THE | | | EXIT DISCHARGE TO A PUBLIC WAY. | | | | | | | | | 7.8 ILLUMINATION OF MEANS OF EGRESS. | | | 7.8.1 GENERAL. | | | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE | | | PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY | | | BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11 | | | THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT | | | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS,AISLES, | | | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING | | | TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT | | | DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, | | | CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT | | | PASSAGEWAYS LEADING TO A PUBLIC WAY. | | | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE | | | CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF | | | OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE | | | FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2. | | | | | | 7.10.1.2 EXITS. | | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | | THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS, | | | SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY | | | VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. | | | 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH | | | WITHIN AN EXIT ENCLOSURE SHALL BE MARKED BY APPROVED | | | EXIT OR DIRECTIONAL EXIT SIGNS WHERE THE CONTINUATION | | | OF THE EGRESS PATH IS NOT OBVIOUS. PLEASE ENSURE ONE IS | | | EXISTING OR PROVIDE. | | | | | | | | | PLEASE NOTE IF ONE IS EXISTING OR PROVIDE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-07-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-06-29 |
Time |
11:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-06-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-06-08 |
Time |
09:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-05-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-30 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-23 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2017-05-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-05-26 |
Time |
09:21 |
Rev Time |
|
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-07-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-07-12 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-07-12 |
Time |
09:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-06-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-06-15 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-06-15 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2017-06-15 15:59:50 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17051018 | | | 6/15/17 | | | | | | 1) THE WORK DESCRIPTION ON THE MECHANICAL SUB-PERMIT | | | INDICATES DUCTS ARE BEING RELOCATED TO NEW DIFFUSER | | | LOCATIONS, HOWEVER THE PLAN IS INDICATING DIFFUSERS AND | | | GRILLS TO BE REPLACED IN THE SAME LOCATIONS- NO DUCT | | | RELOCATIONS ARE SHOWN. PLEASE REVIEW BUILDING COMMENTS | | | AND PROVIDE THE COMPLETE SCOPE OF THE PROPOSED PROJECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-30 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-05-30 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2017-05-30 08:01:33 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17051018 | | | 5/30/17 | | | | | | 1) PROVIDE A REFLECTIVE CEILING PLAN THAT DETAILS THE | | | NEW ASSEMBLY, AND SHOWS THE NEW LOCATIONS OF THE | | | DIFFUSERS AND RETURN GRILLS. | | | | | | 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 | | | WPB AMENDMENTS TO THE FBC. (SEE ALSO SECTION 107.3.5). | | | | | | 3) COMPLY WITH BUILDING REVIEW COMMENTS AND PROVIDE THE | | | CORRECT CODE DATA AND SCOPE OF WORK FOR THE PROPOSED | | | PROJECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
|