Plan Review Details - Permit 17050993
Plan Review Stops For Permit 17050993
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-06-06 Cont ID  
Sent By tklarge Date 2017-06-06 Time 10:00 Rev Time 0.00
Received By tklarge Date 2017-06-06 Time 09:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-05-31 Cont ID  
Sent By tklarge Date 2017-05-31 Time 08:50 Rev Time 0.00
Received By tklarge Date 2017-05-31 Time 06:06 Sent To  
Notes
2017-05-31 06:24:301) THE SUBMITTED FLOOR PLAN SHOWS PE PIPE BEING RUN
 UNDER A COVERED PATIO AND THE BUILDING. THIS IS NOT
 PERMITTED PER THE 2014 FBC-FUEL GAS SECTION 404.17.1.
 PE PIPE SHALL ONLY BE INSTALLED OUTSIDE UNDERGROUND
 2014 FBC-FUEL GAS SEC.404.17.1,
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE DRYER
 THAT IS LOCATED IN THE LAUNDRY ROOM PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1, 614.5 OR 2014 FBC-RES.
 SEC. G 2407.1, G2439.4. 2ND REQUEST.
 3) THE GAS RISER SHOWS THE GALVANIZED DROP TO THE NEW
 DRYER LOCATION AS 3/4 INCH AND ALSO AS 1/2 INCH.
 CLARIFY.
 4) WHAT IS THE LENGTH OF PIPING OF THE 1 INCH RISER AND
 3/4 INCH GALVANIZED PIPE FROM THE METER TO THE
 CONNECTION WITH THE 3/4 INCH PE PIPE? THIS DISTANCE
 SHALL BE INCLUDED IN THE TOTAL DEVELOPED LENGTHAND
 SHALL BE NOTED ON THE PLAN.
 5) THE 1 INCH RISER FROM THE METER IS UNDERSIZED FOR
 THE TOTAL BTU LOAD ON SCHEDULE 40 METALLIC PIPE PER THE
 SUBMITTED TABLE 402.4 (2). THE TOTAL DEVELOPED LENGTH
 TO BE USED FOR SIZING THIS LINE IS 90 FEET SINCE THERE
 IS NO 85 FEET ROW IN THE TABLE. THE MINIMUM SIZE FROM
 THE METER SHALL BE 1 1/4 INCH ON A SYSTEM THAT IS LESS
 THAN 2 PSI WITH A TOTAL BTU LOAD OF 254,000.
 6) SUBMIT TWO COPIES OF THE FLOOR PLAN. WPB AMEND. TO
 FBC SEC. 107.1.
 7) SUBMIT TWO COPIES OF SPECS FOR ALL GAS EQUIPMENT.WPB
 AMEND. TO FBC SEC. 107.1.
  
 I SUGGEST CALLING TO SET UP AN APPOINTMENT TO REVIEW
 THE PLAN REVIEW COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-05-25 Cont ID  
Sent By tklarge Date 2017-05-25 Time 11:28 Rev Time 0.00
Received By tklarge Date 2017-05-25 Time 11:12 Sent To  
Notes
2017-05-25 11:28:461) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE GAS
 APPLIANCES AND THE LOCATION OF THE PE PIPE. PE PIPE
 SHALL ONLY BE INSTALLED OUTSIDE UNDERGROUND 2014
 FBC-FUEL GAS SEC.404.17.1, WPB AMEND. TO FBC SEC.
 107.2.1.
 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD OF THE SYSTEM ON THE PLANS. REFER TO THE 2014
 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413.
 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3. THIS IS THE DEVELOPED LENGTH INCLUDING ALL
 SECTIONS OF PIPE.
 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407. IF THE DRYER IS LOCATED IN A CLOSET OR ROOM WITH
 A DOOR, COMPLY WITH 2014 FBC-FUEL GAS SEC. 614.5.
 6) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. THE
 SUBMITTED MANUFACTURER'S SPEC SHEETS DO NOT SHOW THE
 APPLIANCES ARE LISTED & LABELED.
 7) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-06 Cont ID  
Sent By tklarge Date 2017-06-06 Time 10:00 Rev Time 0.00
Received By tklarge Date 2017-06-02 Time 10:55 Sent To G
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-31 Cont ID  
Sent By tklarge Date 2017-05-31 Time 08:50 Rev Time 0.00
Received By tklarge Date 2017-05-26 Time 09:38 Sent To  
Notes
2017-05-30 09:38:16RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-25 Cont ID  
Sent By tklarge Date 2017-05-25 Time 11:28 Rev Time 0.00
Received By tklarge Date 2017-05-23 Time 16:22 Sent To  
Notes
2017-05-24 16:22:49PLUMB <5K