| 2017-05-25 11:28:46 | 1) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE GAS |
| | APPLIANCES AND THE LOCATION OF THE PE PIPE. PE PIPE |
| | SHALL ONLY BE INSTALLED OUTSIDE UNDERGROUND 2014 |
| | FBC-FUEL GAS SEC.404.17.1, WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2, |
| | 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2, |
| | G2413.3. |
| | 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD OF THE SYSTEM ON THE PLANS. REFER TO THE 2014 |
| | FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413. |
| | 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014 |
| | FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G |
| | 2413.3. THIS IS THE DEVELOPED LENGTH INCLUDING ALL |
| | SECTIONS OF PIPE. |
| | 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 |
| | FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G |
| | 2407. IF THE DRYER IS LOCATED IN A CLOSET OR ROOM WITH |
| | A DOOR, COMPLY WITH 2014 FBC-FUEL GAS SEC. 614.5. |
| | 6) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. THE |
| | SUBMITTED MANUFACTURER'S SPEC SHEETS DO NOT SHOW THE |
| | APPLIANCES ARE LISTED & LABELED. |
| | 7) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE |
| | DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR |
| | OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3. |
| | |