| Plan Review Stops For Permit 17050988 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-08-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-08-08 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-08-04 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2017-08-08 12:27:00 | NO NOTES |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-06-21 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-06-21 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-06-20 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2017-06-21 08:51:25 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | SEPERATE PERMITS ARE REQUIRED FOR EACH STRUCTURE. | | | | | | A COMPLETE AND THOROUGH REVIEW CANNOT BE PERFORMED AT | | | THIS TIME. YOU MAY INCLUDE BOTH STRUCTURES ON ONE SET | | | OF PLANS. | | | CLEARLY SEPERATE AND IDENTIFY WHICH DETAILS/PLAN PAGES | | | PERTAIN TO EACH STRUCTURE. | | | | | | THE FOLLOWING COMMENTS ARE SEPERATED BETWEEN EACH | | | STRUCTURE. | | | | | | NEW CABANA | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR DOOR #4 AND DOOR #6. | | | 2. DOOR TYPE ON DOOR SCHEDULE INDICATES SLIDING GLASS | | | DOORS. PLEASE CLARIFY. | | | 3. PROVIDE FOUNDATION DETAIL (FOOTING). | | | 4. CORRECT PLAN PAGE HEADINGS TO SPECIFY WHICH | | | STRUCTURE DETAILS PERTAIN TO. | | | 5. ROOFING PERMIT REQUIRED. | | | | | | CLOSET/BALCONY ADDITION | | | | | | 1. SEPERATE ENERGY SUBMITTAL REQUIRED. | | | 2. ROOFING PERMIT REQUIRED. | | | 3. PROVIDE PRODUCT APPROVALS FOR NEW GLASS DOOR. | | | 4. PROVIDE DETAIL FOR BALCONY RAILINGS/GUARDS. | | | 5. CHIMNEY CLEARANCES SHALL COMPLY WITH FBC R1001.1 | | | 6. IMPACT FEES MAY APPLY. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-08-15 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-08-15 |
Time |
07:09 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-08-15 |
Time |
07:09 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-07-28 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-07-28 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-07-28 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2017-07-28 14:12:19 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW (2ND REVIEW) COMMENTS: | | | | | | 1. PREVIOUS COMMENT #1 NOT ADDRESSED SATISFACTORILY. | | | RISER DIAGRAM IS NOT COMPLETE, DOES NOT SHOW NEW PANEL | | | FOR GUEST HOUSE (WHERE IS THIS FED FROM?), DOES NOT | | | PROVIDE WIRE SIZES AS REQUESTED. PROVIDE AS PREVIOUSLY | | | REQUESTED: "PROVIDE RISER DIAGRAM SHOWING EXISTING | | | SERVICE AND ANY NEW WIRING. PROVIDE DETAILS OF WIRE AND | | | CONDUIT SIZE". NEC 215.5, FBC 107.3.5 | | | 2. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY. | | | LOAD FOR SERVICE WAS NOT SUPPLIED ON PREVIOUS PERMIT | | | 17050712. PROVIDE AS PREVIOUSLY REQUESTED: "PROVIDE | | | LOAD CALCULATION FOR MAIN SERVICE INCLUDING NEW LOADS | | | TO BE ADDED TO DETERMINE CURRENT SERVICE IS | | | SUFFICIENT". NEC 220, FBC RE3602.2 | | | 3. PREVIOUS COMMENT #3 NOT ADDRESSED SATISFACTORILY. | | | RESPONSE TO COMMENT STATES THAT THE SERVICE WILL BE | | | MOUNTED ON GUEST HOUSE WHEN BUILT. SHOW LOCATION OF | | | SERVICE ON PLAN. SHOW LOCATION OF NEW 100 AMP PANEL. BE | | | ADVISED THAT ANY SEPARATE STRUCTURE IS REQUIRED TO HAVE | | | A MAIN BREAKER OR DISCONNECT FOR THAT STRUCTURE. THE | | | RISER DIAGRAM PROVIDED SHOWS THE OTHER PANELS AS MAIN | | | LUG ONLY PANELS, WHICH WILL NEED TO BE CORRECTED. | | | PROVIDE AS PREVIOUSLY REQUESTED: "PROVIDE DISCONNECT | | | FOR ELECTRICAL SERVICE TO NEW BUILDING PER SECTION II | | | OF THE NEC". NEC 225.30, 225.31, 225.33 | | | 4. PREVIOUS COMMENT #4 NOT ADDRESSED SATISFACTORILY. | | | EACH SEPARATE BUILDING OR STRUCTURE MUST HAVE A | | | GROUNDING ELECTRODE SYSTEM ESTABLISHED AND BONDED | | | TOGETHER PER NEC 250.32. PROVIDE AS PREVIOUSLY | | | REQUESTED: "PROVIDE GROUNDING ELECTRODE CONDUCTOR AND | | | GROUNDING ELECTRODE AT SEPARATE BUILDING WITH | | | INTERSYSTEM BONDING TERMINATION POINT". NEC 250.32, | | | 250.64, 250.94, FBC RE3609.3.5 | | | 5.PREVIOUS COMMENT #5 ADDRESSED, BUT NEEDS CORRECTION. | | | WATER HEATER IS SHOWN WITH A 30 AMP BREAKER, THIS | | | SHOULD BE A 25 AMP PER CODE(BASED ON 4500 WATTS). | | | BATHROOM OUTLETS REQUIRES A DEDICATED 20 AMP CIRCUIT | | | WITH GFCI PROTECTION(THE RECEPTACLES DO NOT CURRENTLY | | | SHOW GFCI PROTECTION). THE OUTLETS IN THE STORAGE AREA | | | REQUIRE GFCI PROTECTION(THE RECEPTACLES DO NOT | | | CURRENTLY SHOW GFCI PROTECTION).PROVIDE CORRECTION. NEC | | | 210.8, 210.11, 408.4, 422.13; FBC RE3703.4, RE 3902.1, | | | RE3902.2 | | | 6. RISER PROVIDED SHOW 3 LEADS OF 2/0 TO 200 AMP PANEL. | | | 2/0 IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC | | | 310.15(B)(16); FBC RE3602.2 | | | 7. PREVIOUS COMMENT #7 NOT ADDRESSED SATISFACTORILY. | | | RESPONSE STATED THE LIGHT AND FAN LOCATIONS WERE MOVED, | | | HOWEVER, THEY ARE IS THE SAME LOCATION. PROVIDE AS | | | PREVIOUSLY REQUESTED: "IT APPEARS FROM SCALING THE | | | PRINT THAT THERE ARE LIGHT FIXTURES AND CEILING FANS | | | LOCATED WITHIN THE 5 FEET HORIZONTAL AND 12 FEET HEIGHT | | | ZONE DESCRIBED IN NEC 680.22. PROVIDE CORRECTION". NEC | | | 680.22(B), FBC RE4203.4 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-06-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-06-06 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-06 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2017-06-06 10:15:27 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS: | | | | | | 1. PROVIDE RISER DIAGRAM SHOWING EXISTING SERVICE AND | | | ANY NEW WIRING. PROVIDE DETAILS OF WIRE AND CONDUIT | | | SIZE. NEC 215.5, FBC 107.3.5 | | | 2. PROVIDE LOAD CALCULATION FOR MAIN SERVICE INCLUDING | | | NEW LOADS TO BE ADDED TO DETERMINE CURRENT SERVICE IS | | | SUFFICIENT. NEC 220, FBC RE3602.2 | | | 3. PROVIDE DISCONNECT FOR ELECTRICAL SERVICE TO NEW | | | BUILDING PER SECTION II OF THE NEC. NEC 225.30, 225.31, | | | 225.33 | | | 4. PROVIDE GROUNDING ELECTRODE CONDUCTOR AND GROUNDING | | | ELECTRODE AT SEPARATE BUILDING WITH INTERSYSTEM BONDING | | | TERMINATION POINT. NEC 250.64, 250.94, FBC RE3609.3.5 | | | 5. PROVIDE PANEL SCHEDULE, INDICATE WIRE AND BREAKER | | | SIZE FOR EACH CIRCUIT. INDICATE CIRCUITS THAT ARE TO BE | | | AFCI OR GFCI PROTECTED PER CODE. NEC 210.8, 210.12, | | | 408.4, 680.22, FBC RE3706.2 | | | 6. PROVIDE ELECTRICAL PLAN FOR ADDITION TO MAIN HOUSE | | | FOR REVIEW. FBC 107.2.1 | | | 7. IT APPEARS FROM SCALING THE PRINT THAT THERE ARE | | | LIGHT FIXTURES AND CEILING FANS LOCATED WITHIN THE 5 | | | FEET HORIZONTAL AND 12 FEET HEIGHT ZONE DESCRIBED IN | | | NEC 680.22. PROVIDE CORRECTION. NEC 680.22(B), FBC | | | RE4203.4 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2017-07-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-07-27 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-07-27 |
Time |
12:25 |
Sent To |
|
|
| Notes |
| 2017-07-27 12:27:05 | GAS PLAN REVIEW | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | | | | GAS PERMIT APPLICATION REQUIREMENTS | | | | | | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL | | | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING | | | IN THE CITY OF WEST PALM BEACH: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | | SEC. 402.4.1. | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP | | | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF | | | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, | | | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY | | | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK | | | PER NFPA 58, TABLE 3-2.2.2. | | | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS | | | ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF | | | THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS | | | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED | | | PER NFPA 58 SECTION 3-2.2.7(H). | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-08-02 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2017-08-02 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2017-08-02 |
Time |
09:11 |
Sent To |
B |
|
| Notes |
| 2017-08-02 09:11:55 | 8/2/2017 - NO CHANGES TO HISTORIC CONCERNS SINCE LAST | | | REVIEW. DLE |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-05-26 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2017-05-26 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2017-05-26 |
Time |
11:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-08-18 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-08-18 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-08-11 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2017-08-14 16:12:24 | JPEARSON'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-08-09 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-07-14 |
Time |
11:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-06-21 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-06-21 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-05-22 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-08-21 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-08-21 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-08-21 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-06-21 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-06-21 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-06-20 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2017-06-21 07:58:39 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | | IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-08-18 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-08-18 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-08-18 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-08-09 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-08-09 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2017-08-09 13:09:57 | PLAN DENIED | | | 1) PROVIDE EQUIPMENT SCHEDULE ON PLAN. | | | PER SECTION 107 FBC | | | 2) SHOW LOCATION OF CONDENSER ON PLAN | | | SECTION 107 FBC | | | 3) REFER TO SECTION R403.2.4 | | | AIR HANDLING UNITS 2014 FLORIDA | | | ENERGY CODE | | | ALL COMMENTS FROM LAST REVIEW. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-06-15 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-06-15 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-06-15 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2017-06-15 15:05:12 | PLAN DENIED | | | 1) PROVIDE EQUIPMENT SCHEDULE ON PLANS. | | | PER SECTION 107 FBC. | | | 2) SHOW LOCATION OF CONDENSER ON PLAN. | | | PER SECTION 107 FBC. | | | 3) SHOW ACCESS TO AIR HANDLER ON THE PLAN. | | | PER SECTION R403.2.4 AIR HANDLING UNITS | | | FLORIDA ENERGY CODE 2014 | | | 4) PROVIDE A SIGNATURE AND LICENSE NUMBER | | | ON THE PLAN ( ON WHO EVER DREW THE PLAN ) | | | 5) REFER TO SECTION R 403.2.1 INSULATION. SUPPLY | | | DUCT IN ATTIC SHALL BE INSULATED TO A MINIMUM OF R-8 | | | FLORIDA ENERGY CODE 2014. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-08-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-08-16 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-08-16 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-07-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-07-27 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-07-27 |
Time |
12:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-06-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-06-12 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-06-12 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2017-06-12 13:58:47 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE DIMENSIONS FOR THE SHOWERS TO COMPLY | | | WITH FBC RES P2708.1 | | | | | | 2. PROVIDE DIMENSIONS FOR BATHROOMS TO SHOW COMPLIANCE | | | WITH FBC RES P2705.1 5. WATER CLOSETS, LAVATORIES AND | | | BIDETS. A WATER CLOSET, LAVATORY OR BIDET SHALL NOT BE | | | SET CLOSER THAN 15 INCHES (381 MM) FROM ITS CENTER TO | | | ANY SIDE WALL, PARTITION OR VANITY OR CLOSER THAN 30 | | | INCHES (762 MM) CENTER-TO-CENTER BETWEEN ADJACENT | | | FIXTURES. THERE SHALL BE A CLEARANCE OF NOT LESS THAN | | | 21 INCHES (533 MM) IN FRONT OF A WATER CLOSET, LAVATORY | | | OR BIDET TO ANY WALL, FIXTURE OR DOOR. | | | | | | 3. PLEASE SHOW LOCATION OF THE WATER HEATER PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. A CLEANOUT IS REQUIRED AT THE BASE OF THE SOIL | | | STACK. FBC RES P3005.2.6 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2017-08-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-08-08 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-08-04 |
Time |
14:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-06-21 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-06-21 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-06-20 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2017-06-21 08:26:48 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | A COMPLETE AND THOROUGH REVIEW CANNOT BE PERFORMED AT | | | THIS TIME | | | | | | 1. SEPERATE PERMITS ARE REQUIRED FOR EACH STRUCTURE. | | | 2. SUBMITTED PRODUCT APPROVALS APPEAR TO BE APPROPRIATE | | | FOR EACH STRUCTURE. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2017-08-02 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2017-08-02 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2017-08-02 |
Time |
09:11 |
Sent To |
HIST |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2017-05-25 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-05-25 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2017-05-25 |
Time |
|
Sent To |
HIST |
|
| Notes |
| 2017-05-25 15:38:27 | *********ZONING COMMENT*************** | | | | | | THE SECOND SET OF PLANS ARE MISSING SHEET A-1. | | | | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | [email protected] | | | 561-822-1449 |
|
|