Plan Review Details - Permit 17050988
Plan Review Stops For Permit 17050988
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-08 Cont ID  
Sent By cthroop Date 2017-08-08 Time 12:26 Rev Time 0.00
Received By cthroop Date 2017-08-04 Time 14:07 Sent To  
Notes
2017-08-08 12:27:00NO NOTES

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By cthroop Date 2017-06-21 Time 08:46 Rev Time 0.00
Received By cthroop Date 2017-06-20 Time 10:58 Sent To  
Notes
2017-06-21 08:51:25BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SEPERATE PERMITS ARE REQUIRED FOR EACH STRUCTURE.
  
 A COMPLETE AND THOROUGH REVIEW CANNOT BE PERFORMED AT
 THIS TIME. YOU MAY INCLUDE BOTH STRUCTURES ON ONE SET
 OF PLANS.
 CLEARLY SEPERATE AND IDENTIFY WHICH DETAILS/PLAN PAGES
 PERTAIN TO EACH STRUCTURE.
  
 THE FOLLOWING COMMENTS ARE SEPERATED BETWEEN EACH
 STRUCTURE.
  
 NEW CABANA
  
 1. PROVIDE PRODUCT APPROVALS FOR DOOR #4 AND DOOR #6.
 2. DOOR TYPE ON DOOR SCHEDULE INDICATES SLIDING GLASS
 DOORS. PLEASE CLARIFY.
 3. PROVIDE FOUNDATION DETAIL (FOOTING).
 4. CORRECT PLAN PAGE HEADINGS TO SPECIFY WHICH
 STRUCTURE DETAILS PERTAIN TO.
 5. ROOFING PERMIT REQUIRED.
  
 CLOSET/BALCONY ADDITION
  
 1. SEPERATE ENERGY SUBMITTAL REQUIRED.
 2. ROOFING PERMIT REQUIRED.
 3. PROVIDE PRODUCT APPROVALS FOR NEW GLASS DOOR.
 4. PROVIDE DETAIL FOR BALCONY RAILINGS/GUARDS.
 5. CHIMNEY CLEARANCES SHALL COMPLY WITH FBC R1001.1
 6. IMPACT FEES MAY APPLY.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-08-15 Cont ID  
Sent By jpearson Date 2017-08-15 Time 07:09 Rev Time 0.00
Received By jpearson Date 2017-08-15 Time 07:09 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-07-28 Cont ID  
Sent By jpearson Date 2017-07-28 Time 14:12 Rev Time 0.00
Received By jpearson Date 2017-07-28 Time 14:12 Sent To  
Notes
2017-07-28 14:12:19CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW (2ND REVIEW) COMMENTS:
  
 1. PREVIOUS COMMENT #1 NOT ADDRESSED SATISFACTORILY.
 RISER DIAGRAM IS NOT COMPLETE, DOES NOT SHOW NEW PANEL
 FOR GUEST HOUSE (WHERE IS THIS FED FROM?), DOES NOT
 PROVIDE WIRE SIZES AS REQUESTED. PROVIDE AS PREVIOUSLY
 REQUESTED: "PROVIDE RISER DIAGRAM SHOWING EXISTING
 SERVICE AND ANY NEW WIRING. PROVIDE DETAILS OF WIRE AND
 CONDUIT SIZE". NEC 215.5, FBC 107.3.5
 2. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY.
 LOAD FOR SERVICE WAS NOT SUPPLIED ON PREVIOUS PERMIT
 17050712. PROVIDE AS PREVIOUSLY REQUESTED: "PROVIDE
 LOAD CALCULATION FOR MAIN SERVICE INCLUDING NEW LOADS
 TO BE ADDED TO DETERMINE CURRENT SERVICE IS
 SUFFICIENT". NEC 220, FBC RE3602.2
 3. PREVIOUS COMMENT #3 NOT ADDRESSED SATISFACTORILY.
 RESPONSE TO COMMENT STATES THAT THE SERVICE WILL BE
 MOUNTED ON GUEST HOUSE WHEN BUILT. SHOW LOCATION OF
 SERVICE ON PLAN. SHOW LOCATION OF NEW 100 AMP PANEL. BE
 ADVISED THAT ANY SEPARATE STRUCTURE IS REQUIRED TO HAVE
 A MAIN BREAKER OR DISCONNECT FOR THAT STRUCTURE. THE
 RISER DIAGRAM PROVIDED SHOWS THE OTHER PANELS AS MAIN
 LUG ONLY PANELS, WHICH WILL NEED TO BE CORRECTED.
 PROVIDE AS PREVIOUSLY REQUESTED: "PROVIDE DISCONNECT
 FOR ELECTRICAL SERVICE TO NEW BUILDING PER SECTION II
 OF THE NEC". NEC 225.30, 225.31, 225.33
 4. PREVIOUS COMMENT #4 NOT ADDRESSED SATISFACTORILY.
 EACH SEPARATE BUILDING OR STRUCTURE MUST HAVE A
 GROUNDING ELECTRODE SYSTEM ESTABLISHED AND BONDED
 TOGETHER PER NEC 250.32. PROVIDE AS PREVIOUSLY
 REQUESTED: "PROVIDE GROUNDING ELECTRODE CONDUCTOR AND
 GROUNDING ELECTRODE AT SEPARATE BUILDING WITH
 INTERSYSTEM BONDING TERMINATION POINT". NEC 250.32,
 250.64, 250.94, FBC RE3609.3.5
 5.PREVIOUS COMMENT #5 ADDRESSED, BUT NEEDS CORRECTION.
 WATER HEATER IS SHOWN WITH A 30 AMP BREAKER, THIS
 SHOULD BE A 25 AMP PER CODE(BASED ON 4500 WATTS).
 BATHROOM OUTLETS REQUIRES A DEDICATED 20 AMP CIRCUIT
 WITH GFCI PROTECTION(THE RECEPTACLES DO NOT CURRENTLY
 SHOW GFCI PROTECTION). THE OUTLETS IN THE STORAGE AREA
 REQUIRE GFCI PROTECTION(THE RECEPTACLES DO NOT
 CURRENTLY SHOW GFCI PROTECTION).PROVIDE CORRECTION. NEC
 210.8, 210.11, 408.4, 422.13; FBC RE3703.4, RE 3902.1,
 RE3902.2
 6. RISER PROVIDED SHOW 3 LEADS OF 2/0 TO 200 AMP PANEL.
 2/0 IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(16); FBC RE3602.2
 7. PREVIOUS COMMENT #7 NOT ADDRESSED SATISFACTORILY.
 RESPONSE STATED THE LIGHT AND FAN LOCATIONS WERE MOVED,
 HOWEVER, THEY ARE IS THE SAME LOCATION. PROVIDE AS
 PREVIOUSLY REQUESTED: "IT APPEARS FROM SCALING THE
 PRINT THAT THERE ARE LIGHT FIXTURES AND CEILING FANS
 LOCATED WITHIN THE 5 FEET HORIZONTAL AND 12 FEET HEIGHT
 ZONE DESCRIBED IN NEC 680.22. PROVIDE CORRECTION". NEC
 680.22(B), FBC RE4203.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-06 Cont ID  
Sent By jpearson Date 2017-06-06 Time 09:43 Rev Time 0.00
Received By jpearson Date 2017-06-06 Time 09:43 Sent To  
Notes
2017-06-06 10:15:27CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE RISER DIAGRAM SHOWING EXISTING SERVICE AND
 ANY NEW WIRING. PROVIDE DETAILS OF WIRE AND CONDUIT
 SIZE. NEC 215.5, FBC 107.3.5
 2. PROVIDE LOAD CALCULATION FOR MAIN SERVICE INCLUDING
 NEW LOADS TO BE ADDED TO DETERMINE CURRENT SERVICE IS
 SUFFICIENT. NEC 220, FBC RE3602.2
 3. PROVIDE DISCONNECT FOR ELECTRICAL SERVICE TO NEW
 BUILDING PER SECTION II OF THE NEC. NEC 225.30, 225.31,
 225.33
 4. PROVIDE GROUNDING ELECTRODE CONDUCTOR AND GROUNDING
 ELECTRODE AT SEPARATE BUILDING WITH INTERSYSTEM BONDING
 TERMINATION POINT. NEC 250.64, 250.94, FBC RE3609.3.5
 5. PROVIDE PANEL SCHEDULE, INDICATE WIRE AND BREAKER
 SIZE FOR EACH CIRCUIT. INDICATE CIRCUITS THAT ARE TO BE
 AFCI OR GFCI PROTECTED PER CODE. NEC 210.8, 210.12,
 408.4, 680.22, FBC RE3706.2
 6. PROVIDE ELECTRICAL PLAN FOR ADDITION TO MAIN HOUSE
 FOR REVIEW. FBC 107.2.1
 7. IT APPEARS FROM SCALING THE PRINT THAT THERE ARE
 LIGHT FIXTURES AND CEILING FANS LOCATED WITHIN THE 5
 FEET HORIZONTAL AND 12 FEET HEIGHT ZONE DESCRIBED IN
 NEC 680.22. PROVIDE CORRECTION. NEC 680.22(B), FBC
 RE4203.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-07-27 Cont ID  
Sent By gjohnson Date 2017-07-27 Time 12:25 Rev Time 0.00
Received By gjohnson Date 2017-07-27 Time 12:25 Sent To  
Notes
2017-07-27 12:27:05GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-08-02 Cont ID  
Sent By destabro Date 2017-08-02 Time 09:11 Rev Time 0.00
Received By destabro Date 2017-08-02 Time 09:11 Sent To B
Notes
2017-08-02 09:11:558/2/2017 - NO CHANGES TO HISTORIC CONCERNS SINCE LAST
 REVIEW. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-05-26 Cont ID  
Sent By fmittner Date 2017-05-26 Time 11:06 Rev Time 0.00
Received By fmittner Date 2017-05-26 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-18 Cont ID  
Sent By hmoser Date 2017-08-18 Time 11:29 Rev Time 0.00
Received By hmoser Date 2017-08-11 Time 16:10 Sent To  
Notes
2017-08-14 16:12:24JPEARSON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-09 Cont ID  
Sent By hmoser Date 2017-08-09 Time 13:38 Rev Time 0.00
Received By hmoser Date 2017-07-14 Time 11:13 Sent To  
Notes
2017-07-18 11:13:40R29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-21 Cont ID  
Sent By cthroop Date 2017-06-21 Time 08:46 Rev Time 0.00
Received By cthroop Date 2017-05-22 Time 11:03 Sent To  
Notes
2017-05-23 11:03:29R27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-08-21 Cont ID  
Sent By cthroop Date 2017-08-21 Time 11:15 Rev Time 0.00
Received By cthroop Date 2017-08-21 Time 11:15 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By cthroop Date 2017-06-21 Time 07:50 Rev Time 0.00
Received By cthroop Date 2017-06-20 Time 10:58 Sent To  
Notes
2017-06-21 07:58:39BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-08-18 Cont ID  
Sent By hmoser Date 2017-08-18 Time 11:29 Rev Time 0.00
Received By hmoser Date 2017-08-18 Time 08:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-09 Cont ID  
Sent By hmoser Date 2017-08-09 Time 13:38 Rev Time 0.00
Received By hmoser Date 2017-08-09 Time 11:30 Sent To  
Notes
2017-08-09 13:09:57PLAN DENIED
 1) PROVIDE EQUIPMENT SCHEDULE ON PLAN.
 PER SECTION 107 FBC
 2) SHOW LOCATION OF CONDENSER ON PLAN
 SECTION 107 FBC
 3) REFER TO SECTION R403.2.4
 AIR HANDLING UNITS 2014 FLORIDA
 ENERGY CODE
 ALL COMMENTS FROM LAST REVIEW.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-15 Cont ID  
Sent By hmoser Date 2017-06-15 Time 14:47 Rev Time 0.00
Received By hmoser Date 2017-06-15 Time 14:07 Sent To  
Notes
2017-06-15 15:05:12PLAN DENIED
 1) PROVIDE EQUIPMENT SCHEDULE ON PLANS.
 PER SECTION 107 FBC.
 2) SHOW LOCATION OF CONDENSER ON PLAN.
 PER SECTION 107 FBC.
 3) SHOW ACCESS TO AIR HANDLER ON THE PLAN.
 PER SECTION R403.2.4 AIR HANDLING UNITS
 FLORIDA ENERGY CODE 2014
 4) PROVIDE A SIGNATURE AND LICENSE NUMBER
 ON THE PLAN ( ON WHO EVER DREW THE PLAN )
 5) REFER TO SECTION R 403.2.1 INSULATION. SUPPLY
 DUCT IN ATTIC SHALL BE INSULATED TO A MINIMUM OF R-8
 FLORIDA ENERGY CODE 2014.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-08-16 Cont ID  
Sent By gjohnson Date 2017-08-16 Time 16:28 Rev Time 0.00
Received By gjohnson Date 2017-08-16 Time 16:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-27 Cont ID  
Sent By gjohnson Date 2017-07-27 Time 12:25 Rev Time 0.00
Received By gjohnson Date 2017-07-27 Time 12:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-12 Cont ID  
Sent By gjohnson Date 2017-06-12 Time 13:49 Rev Time 0.00
Received By gjohnson Date 2017-06-12 Time 12:43 Sent To  
Notes
2017-06-12 13:58:471ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DIMENSIONS FOR THE SHOWERS TO COMPLY
 WITH FBC RES P2708.1
  
 2. PROVIDE DIMENSIONS FOR BATHROOMS TO SHOW COMPLIANCE
 WITH FBC RES P2705.1 5. WATER CLOSETS, LAVATORIES AND
 BIDETS. A WATER CLOSET, LAVATORY OR BIDET SHALL NOT BE
 SET CLOSER THAN 15 INCHES (381 MM) FROM ITS CENTER TO
 ANY SIDE WALL, PARTITION OR VANITY OR CLOSER THAN 30
 INCHES (762 MM) CENTER-TO-CENTER BETWEEN ADJACENT
 FIXTURES. THERE SHALL BE A CLEARANCE OF NOT LESS THAN
 21 INCHES (533 MM) IN FRONT OF A WATER CLOSET, LAVATORY
 OR BIDET TO ANY WALL, FIXTURE OR DOOR.
  
 3. PLEASE SHOW LOCATION OF THE WATER HEATER PER WPB
 AMEND TO FBC 107.2.1
  
 4. A CLEANOUT IS REQUIRED AT THE BASE OF THE SOIL
 STACK. FBC RES P3005.2.6
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-08-08 Cont ID  
Sent By cthroop Date 2017-08-08 Time 12:26 Rev Time 0.00
Received By cthroop Date 2017-08-04 Time 14:07 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By cthroop Date 2017-06-21 Time 08:13 Rev Time 0.00
Received By cthroop Date 2017-06-20 Time 14:40 Sent To  
Notes
2017-06-21 08:26:48BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 A COMPLETE AND THOROUGH REVIEW CANNOT BE PERFORMED AT
 THIS TIME
  
 1. SEPERATE PERMITS ARE REQUIRED FOR EACH STRUCTURE.
 2. SUBMITTED PRODUCT APPROVALS APPEAR TO BE APPROPRIATE
 FOR EACH STRUCTURE.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-02 Cont ID  
Sent By destabro Date 2017-08-02 Time 09:11 Rev Time 0.00
Received By destabro Date 2017-08-02 Time 09:11 Sent To HIST
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-05-25 Cont ID  
Sent By   Date 2017-05-25 Time   Rev Time  
Received By   Date 2017-05-25 Time   Sent To HIST
Notes
2017-05-25 15:38:27*********ZONING COMMENT***************
  
 THE SECOND SET OF PLANS ARE MISSING SHEET A-1.
  
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 [email protected]
 561-822-1449