Plan Review Details - Permit 17050979
Plan Review Stops For Permit 17050979
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2017-05-31 Cont ID  
Sent By jleahy Date 2017-05-31 Time 08:01 Rev Time 0.00
Received By jleahy Date 2017-05-31 Time 08:01 Sent To  
Notes
2017-05-31 13:04:32BUILDING REVIEW NOT REQUIRED INDOOR ANTENNA SYSTEM JL

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-31 Cont ID  
Sent By jleahy Date 2017-05-31 Time 08:01 Rev Time 0.00
Received By jleahy Date 2017-05-31 Time 08:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-31 Cont ID  
Sent By wjolin Date 2017-05-31 Time 14:08 Rev Time 0.00
Received By wjolin Date 2017-05-31 Time 13:53 Sent To E
Notes
2017-05-31 14:08:30PER NFPA 72 SECTION 24.5.2.2.1 CRITICAL AREAS. CRITICAL
 AREAS, SUCH AS THE FIRE COMMAND CENTER(S), THE FIRE
 PUMP ROOM(S), EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR
 LOBBIES, STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE
 LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT FLOOR AREA RADIO COVERAGE. GENERAL BUILDING
 AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA
 RADIO COVERAGE. A MINIMUM INBOUND/OUTBOUND SIGNAL
 STRENGTH OF -95 DBM SHALL BE PROVIDED THROUGHOUT THE
 COVERAGE AREA.
  
 NEED A #301 AND #302 FIRE INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-31 Cont ID  
Sent By jleahy Date 2017-05-31 Time 15:55 Rev Time 0.00
Received By jleahy Date 2017-05-22 Time 14:46 Sent To  
Notes
2017-05-23 14:48:48B11