Plan Review Details - Permit 17050939
Plan Review Stops For Permit 17050939
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-06-29 Cont ID  
Sent By shill Date 2017-06-29 Time 12:45 Rev Time 0.00
Received By shill Date 2017-06-29 Time 12:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-29 Cont ID  
Sent By shill Date 2017-06-29 Time 08:06 Rev Time 0.00
Received By shill Date 2017-06-29 Time 07:56 Sent To  
Notes
2017-06-29 08:12:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVIDE A REASONABLE VALUE FOR THIS PROJECT, FBC 109.
  
 THE VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD AND
 PROFIT, INCLUDING ITEMS PROVIDED BY OTHERS.
  
 THE PLANS HAVE BEEN STAMPED; THIS ITEM MAY BE ADDRESSED
 VIA EMAIL.
  
 PLEASE ADDRESS IMMEDIATELY TO AVOID PERMIT ISSUANCE
 DELAYS.
  
 AN EMAIL WAS SENT TO THE CONTRACTOR'S EMAIL IN OUR
 RECORDS AND WAS RETURNED AS UNDELIVERABLE; CALLED JOHN
 954-665-0682
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-30 Cont ID  
Sent By shill Date 2017-05-30 Time 17:22 Rev Time 0.00
Received By shill Date 2017-05-30 Time 17:22 Sent To  
Notes
2017-05-30 17:24:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. APPLICATION WORK DESCRIPTION STATES THAT WOOD FLOORS
 WILL BE INSTALLED, PLANS SPECIFY TILE, CORRELATE FBC
 107.
  
 2. PROVIDE TEST REPORTS FOR THE FLOORING UNDERLAYMENT.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 3. A1 DECLARES BUILDING TYPE AS IIIA, ISN'T THIS A HIGH
 RISE, CANNOT BE COMBUSTILE? REVISE, FBC CHAPTER 6.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-06-02 Cont ID  
Sent By jpearson Date 2017-06-02 Time 12:29 Rev Time 0.00
Received By jpearson Date 2017-06-02 Time 12:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-30 Cont ID  
Sent By pleduc Date 2017-06-30 Time   Rev Time 0.00
Received By pleduc Date 2017-06-30 Time 12:14 Sent To P
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-24 Cont ID  
Sent By pleduc Date 2017-05-24 Time   Rev Time 0.00
Received By pleduc Date 2017-05-24 Time 14:23 Sent To  
Notes
2017-05-24 15:39:44THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY WORK ON THE FIRE ALARM SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-03 Cont ID  
Sent By gjohnson Date 2017-07-03 Time 16:42 Rev Time 0.00
Received By gjohnson Date 2017-06-27 Time 10:03 Sent To  
Notes
2017-06-28 10:03:10B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-06 Cont ID  
Sent By gjohnson Date 2017-06-06 Time 16:49 Rev Time 0.00
Received By gjohnson Date 2017-05-22 Time 11:08 Sent To  
Notes
2017-05-23 11:08:33B05

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-03 Cont ID  
Sent By gjohnson Date 2017-07-03 Time 16:41 Rev Time 0.00
Received By gjohnson Date 2017-07-03 Time 16:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-06-06 Cont ID  
Sent By gjohnson Date 2017-06-06 Time 16:44 Rev Time 0.00
Received By gjohnson Date 2017-06-06 Time 16:44 Sent To  
Notes
***NONE***