| Plan Review Stops For Permit 17050921 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-06-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-06 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-06 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2017-06-06 11:47:35 | PROVISO | | | SEPARATE PERMIT REQUIRED FOR ACCESS CONTROL, LOW | | | VOLTAGE. | | | AFTER ACCESS CONTROL PERMIT IS ISSUED, BEFORE FINAL | | | INSPECTION, SEND A REQUEST TO [email protected] TO REVOKE | | | 07020017. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-23 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-23 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2017-05-23 09:05:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | REVIEW #1 (INITIAL SUBMITTAL, PERMIT APPLICATION) | | | | | | 1. FBC 107, FBC B 1604, FBC B 2406, REVISE PLAN TO | | | PROVIDE A FRAMING DETAIL FOR THE NEW WINDOW OPENINGS. | | | INCLUDE THE DISTANCE FROM FINISHED FLOOR TO THE BOTTOM | | | OF THE PROPOSED WINDOWS. | | | | | | 2. FBC 107, REVISE PLAN TO CLARIFY USE OF SPACE | | | "COLLATERAL ROOM". | | | | | | 3. THERE IS AN ABANDONED ACCESS APPLICATION ON RECORD | | | FOR THIS FLOOR (07020017). PROVIDE INFORMATION; WAS | | | THIS INSTALLED? IF IT WAS INSTALLED, SUBMIT APPLICATION | | | FOR THE WORK INSTALLED WITHOUT PERMIT. IF IT WAS NOT | | | INSTALLED, PLEASE ADVISE. | | | | | | 4. IT APPEARS THAT AN ELEVATOR LOBBY IS REQUIRED BY FBC | | | B 713.14.1. REVISE PLAN TO PROVIDE INFORMATION | | | REGARDING THE ELEVATOR LOBBY OR APPLICABLE EXCEPTION. | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS. | | | | | | NOTE THAT THE FLOOR PLAN SUBMITTED DOES NOT APPEAR TO | | | BE CONSISTENT WITH THE MOST RECENT RENOVATION PERMIT | | | FOR THIS FLOOR. | | | | | | 5. THE DBPR WEBSITE DOES NOT REFLECT THAT THE ENGINEER | | | (HERBERT F KAHLERT, PE) HAS TAKEN THE ADVANCED FLORIDA | | | BUILDING CODE COURSE REQUIRED BY FLORIDA STATUTE | | | 471.0195. THIS WAS REQUIRED BY JUNE 30,2016. IF | | | ENGINEER HAS TAKEN THE COURSE, PLEASE EMAIL EVIDENCE TO | | | FBPE AND REQUEST THAT THE WEBSITE BE UPDATED. | | | | | | 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | | 107, FBC 109. | | | | | | 7. THE CONTRACTOR HAS SIGNED AS OWNER. PLEASE EXPLIAN | | | RELATIONSHIP; THE CONTRACT IS REQUIRED IF THE | | | CONTRACTOR IS SIGNING ON BEHALF OF THE OWNER. | | | ADDITIONAL INFORMATION MAY BE REQUIRED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-06-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-06-05 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-05 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2017-06-05 13:09:33 | REVIEWED PER COMMENTS ONLY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-05-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-25 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-25 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2017-05-25 15:40:19 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER . COMPLETE LOAD | | | CALCULATIONS, PANEL SCHEDULES . | | | | | | 408.4 FIELD IDENTIFICATION REQUIRED. | | | (A) CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY | | | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY | | | IDENTIFIED AS | | | TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE | | | IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF | | | DETAIL THAT | | | ALLOWS EACH CIRCUIT TO BE DISTINGUISHED FROM ALL | | | OTHERS. SPARE POSITIONS THAT CONTAIN UNUSED OVERCUN'ENT | | | DEVICES OR | | | SWITCHES SHALL BE DESCRIBED ACCORDINGLY. THE | | | IDENTIFICATION SHALL BE INCLUDED IN A CIRCUIT DIRECTORY | | | THAT IS LOCATED ON THE | | | FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A | | | PANELBOARD AND AT EACH SWITCH OR CIRCUIT BREAKER IN A | | | SWITCHBOARD OR | | | SWITCHGEAR. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER | | | THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-06-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-06-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-06-05 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2017-06-06 08:43:51 | 2ND REVIEW | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-05-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-05-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-05-24 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2017-05-25 11:26:29 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-06-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-06 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-02 |
Time |
10:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-06-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-19 |
Time |
13:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-06-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-06-06 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-06-06 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-26 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-05-26 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2017-05-26 11:46:11 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050921 | | | 5/26/17 | | | | | | RESULTS: DENIED. | | | | | | 1) SHEET 4: REFER TO TABLE 403.3 AND ADJUST THE | | | VENTILATION CALCULATIONS SO THEY INCLUDE THE OCCUPANT | | | DENSITY AND THE CFMS PER OCCUPANT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|