Plan Review Details - Permit 17050921
Plan Review Stops For Permit 17050921
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-06 Cont ID  
Sent By shill Date 2017-06-06 Time 11:46 Rev Time 0.00
Received By shill Date 2017-06-06 Time 11:20 Sent To  
Notes
2017-06-06 11:47:35PROVISO
 SEPARATE PERMIT REQUIRED FOR ACCESS CONTROL, LOW
 VOLTAGE.
 AFTER ACCESS CONTROL PERMIT IS ISSUED, BEFORE FINAL
 INSPECTION, SEND A REQUEST TO [email protected] TO REVOKE
 07020017.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-23 Cont ID  
Sent By shill Date 2017-05-23 Time 09:05 Rev Time 0.00
Received By shill Date 2017-05-23 Time 07:38 Sent To  
Notes
2017-05-23 09:05:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 REVIEW #1 (INITIAL SUBMITTAL, PERMIT APPLICATION)
  
 1. FBC 107, FBC B 1604, FBC B 2406, REVISE PLAN TO
 PROVIDE A FRAMING DETAIL FOR THE NEW WINDOW OPENINGS.
 INCLUDE THE DISTANCE FROM FINISHED FLOOR TO THE BOTTOM
 OF THE PROPOSED WINDOWS.
  
 2. FBC 107, REVISE PLAN TO CLARIFY USE OF SPACE
 "COLLATERAL ROOM".
  
 3. THERE IS AN ABANDONED ACCESS APPLICATION ON RECORD
 FOR THIS FLOOR (07020017). PROVIDE INFORMATION; WAS
 THIS INSTALLED? IF IT WAS INSTALLED, SUBMIT APPLICATION
 FOR THE WORK INSTALLED WITHOUT PERMIT. IF IT WAS NOT
 INSTALLED, PLEASE ADVISE.
  
 4. IT APPEARS THAT AN ELEVATOR LOBBY IS REQUIRED BY FBC
 B 713.14.1. REVISE PLAN TO PROVIDE INFORMATION
 REGARDING THE ELEVATOR LOBBY OR APPLICABLE EXCEPTION.
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS.
  
 NOTE THAT THE FLOOR PLAN SUBMITTED DOES NOT APPEAR TO
 BE CONSISTENT WITH THE MOST RECENT RENOVATION PERMIT
 FOR THIS FLOOR.
  
 5. THE DBPR WEBSITE DOES NOT REFLECT THAT THE ENGINEER
 (HERBERT F KAHLERT, PE) HAS TAKEN THE ADVANCED FLORIDA
 BUILDING CODE COURSE REQUIRED BY FLORIDA STATUTE
 471.0195. THIS WAS REQUIRED BY JUNE 30,2016. IF
 ENGINEER HAS TAKEN THE COURSE, PLEASE EMAIL EVIDENCE TO
 FBPE AND REQUEST THAT THE WEBSITE BE UPDATED.
  
 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 107, FBC 109.
  
 7. THE CONTRACTOR HAS SIGNED AS OWNER. PLEASE EXPLIAN
 RELATIONSHIP; THE CONTRACT IS REQUIRED IF THE
 CONTRACTOR IS SIGNING ON BEHALF OF THE OWNER.
 ADDITIONAL INFORMATION MAY BE REQUIRED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-05 Cont ID  
Sent By jpearson Date 2017-06-05 Time 13:08 Rev Time 0.00
Received By jpearson Date 2017-06-05 Time 13:08 Sent To  
Notes
2017-06-05 13:09:33REVIEWED PER COMMENTS ONLY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-25 Cont ID  
Sent By jleahy Date 2017-05-25 Time 15:33 Rev Time 0.00
Received By jleahy Date 2017-05-25 Time 15:33 Sent To  
Notes
2017-05-25 15:40:19FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER . COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES .
  
 408.4 FIELD IDENTIFICATION REQUIRED.
 (A) CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS
 TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE
 IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF
 DETAIL THAT
 ALLOWS EACH CIRCUIT TO BE DISTINGUISHED FROM ALL
 OTHERS. SPARE POSITIONS THAT CONTAIN UNUSED OVERCUN'ENT
 DEVICES OR
 SWITCHES SHALL BE DESCRIBED ACCORDINGLY. THE
 IDENTIFICATION SHALL BE INCLUDED IN A CIRCUIT DIRECTORY
 THAT IS LOCATED ON THE
 FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANELBOARD AND AT EACH SWITCH OR CIRCUIT BREAKER IN A
 SWITCHBOARD OR
 SWITCHGEAR. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER
 THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-06 Cont ID  
Sent By pleduc Date 2017-06-06 Time   Rev Time 0.00
Received By pleduc Date 2017-06-05 Time 16:21 Sent To  
Notes
2017-06-06 08:43:512ND REVIEW
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-25 Cont ID  
Sent By pleduc Date 2017-05-25 Time   Rev Time 0.00
Received By pleduc Date 2017-05-24 Time 14:21 Sent To  
Notes
2017-05-25 11:26:29THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-06 Cont ID  
Sent By shill Date 2017-06-06 Time 12:35 Rev Time 0.00
Received By shill Date 2017-06-02 Time 10:36 Sent To  
Notes
2017-06-02 10:36:14B14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-01 Cont ID  
Sent By ccole Date 2017-05-26 Time   Rev Time 0.00
Received By shill Date 2017-05-19 Time 13:44 Sent To  
Notes
2017-05-22 13:44:48B14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-06-06 Cont ID  
Sent By ccole Date 2017-06-06 Time 11:09 Rev Time 0.00
Received By ccole Date 2017-06-06 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-26 Cont ID  
Sent By ccole Date 2017-05-26 Time 11:41 Rev Time 0.00
Received By ccole Date 2017-05-26 Time 11:41 Sent To  
Notes
2017-05-26 11:46:111ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050921
 5/26/17
  
 RESULTS: DENIED.
  
 1) SHEET 4: REFER TO TABLE 403.3 AND ADJUST THE
 VENTILATION CALCULATIONS SO THEY INCLUDE THE OCCUPANT
 DENSITY AND THE CFMS PER OCCUPANT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  