Plan Review Details - Permit 17050881
Plan Review Stops For Permit 17050881
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-08-10 Cont ID  
Sent By jwitmer Date 2017-08-10 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2017-08-10 Time 11:11 Sent To  
Notes
2017-08-10 11:53:562014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050881
 ADD: 805 19TH ST.
 CONT: M. J. EBERSBACH CONSTRUCTION
 TEL: 561-271-0136
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: THURS. AUGUST 10/ 2017
 ACTION: PROVISO
  
 1) BUILDING PROVISO: CHANGE OUT OF ALL WINDOWS FOR 1ST
 & 2ND FLOOR. EXCEPTION TO SECTION 704.1 OF THE 2014
 EXISTING BUILDING CODE AN ALLOWABLE 5 PERCENT REDUCTION
 IN THE CLEAR OPENING DIMENSIONS OF THE REPLACEMENT
 WINDOW. THE CONTRACTOR HAS SUBMITTED PICTURES OF
 EXISTING SINGLE HUNG WINDOWS IN THE EXISTING OPENING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-07-20 Cont ID  
Sent By jwitmer Date 2017-07-20 Time 11:17 Rev Time 0.00
Received By jwitmer Date 2017-07-20 Time 11:16 Sent To  
Notes
2017-07-20 11:17:182014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050881
 ADD: 805 19TH ST.
 CONT: M. J. EBERSBACH CONSTRUCTION
 TEL: 561-271-0136
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. JULY 20/ 2017
 ACTION: DENIED
  
 1) BUILDING PROVISO: CHANGE OUT OF ALL WINDOWS FOR 1ST
 & 2ND FLOOR. EXCEPTION TO SECTION 704.1 OF THE 2014
 EXISTING BUILDING CODE AN ALLOWABLE 5 PERCENT REDUCTION
 IN THE CLEAR OPENING DIMENSIONS OF THE REPLACEMENT
 WINDOW. THE CONTRACTOR HAS SUBMITTED PICTURES OF
 EXISTING SINGLE HUNG WINDOWS IN THE EXISTING OPENING.
  
 2) 2ND REQUEST. 107.2.4 EXTERIOR WALL ENVELOPE. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
 THE CONSTRUCTION DOCUMENTS SHALL INCLUDE MANUFACTURERS
 INSTALLATION INSTRUCTIONS THAT PROVIDE SUPPORTING
 DOCUMENTATION THAT THE PROPOSED PENETRATION AND OPENING
 DETAILS DESCRIBED IN THE CONSTRUCTION DOCUMENTS
 MAINTAIN THE WEATHER RESISTANCE OF THE EXTERIOR WALL
 ENVELOPE.
  
 3-4) COMPLIED.
  
 5) NEW COMMENT. SHEET # 2 SHOWS NEW AIR CONDENSERS ON
 CONCRETE PADS PLEASE PROVIDE ENGINEERING HOW THESE
 UNITS WILL BE ANCHORED TO THE CONCRETE PAD. PROVIDE
 LATERAL FORCE RESISTING SYSTEM. 2014 FBC-B 1604.4
 ANALYSIS. SEE MECH. PLAN REVIEW AS WELL.
  
 6) NEW COMMENT. SUBMITTED DOOR AND MULLION PRODUCT
 APPROVAL WITH THE DESIGNER OF RECORD REVIEW. THIS
 REVIEW I COULD FIND NO WINDOW PRODUCT APPROVAL FOR ANY
 TYPE OF WINDOW. THE WINDOW SCHEDULE ON SHEET A.2 DOES
 INDICATE ALL OF THE NEW WINDOWS ARE TO BE SINGLE HUNG
 WINDOWS. PLEASE COMPLY WITH 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(B) WINDOWS.
  
 E-MAIL SENT 07/20/17 11:34 THERE MAYBE OTHER ISSUES
 THAT DEAL WITH THE REQUIRED FLOOR UNDELAYMENT SOUND
 REQUIREMENTS FOR THE 2ND FLOOR.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-11 Cont ID  
Sent By jwitmer Date 2017-07-11 Time 06:32 Rev Time 0.00
Received By jwitmer Date 2017-07-10 Time 15:56 Sent To  
Notes
2017-07-11 06:33:162014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050881
 ADD: 805 19TH ST.
 CONT: M. J. EBERSBACH CONSTRUCTION
 TEL: 561-271-0136
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JULY11/ 2017
 ACTION: DENIED
  
 1) THE RESPONSE COMMENT INDICATES THAT THE DESIGNER OF
 RECORD IS TRYING TO TAKE THE EXCEPTION TO SECTION 704.1
 OF THE 2014 EXISTING BUILDING CODE AN ALLOWABLE 5
 PERCENT REDUCTION IN THE CLEAR OPENING DIMENSIONS OF
 THE REPLACEMENT WINDOW. I?VE SPOKEN WITH THE BUILDING
 OFFICIAL ROBERT BROWN ABOUT THIS REQUEST TO USE THE
 EXCEPTION. THIS REVIEW, NEITHER THE DESIGNER OF RECORD
 NOR THE CONTRACTOR SUBMITTED PROOF OF THE EXISTING
 WINDOWS CLEAR OPENING. MR. BROWN SAID PROOF CAN BE
 PICTURES TAKEN OF THE RESIDENCE SHOWING THE TYPE OF
 WINDOWS (BEDROOM EGRESS WINDOWS), THEN A CLOSE UP OF
 THE WINDOW WITH THE WINDOW IN THE OPEN POSITION AND
 PROVIDE THE VERTICAL DIMENSION FROM THE TOP OF THE
 WINDOW SILL SASH TO THE CLOSEST FRAMING MEMBER OF THE
 WINDOW FRAME VERTICALLY ABOVE. PLEASE PROVIDE A PICTURE
 OF BOTH CASES SO THE CLEAR OPENING DIMENSION ( MEASURE
 OPENING WITH TAPE DOCUMENTED IN THE PHOTOGRAPH) SO IT
 CAN BE DOCUMENTED AND BECOME PART OF THE PERMIT RECORD.
 ALSO PROVIDE FROM THE MANUFACTURER THE VERTICAL CLEAR
 OPENING DIMENSION FOR THIS WINDOW.
 YOU CAN EITHER SUBMIT THE PHOTOGRAPHS BY E-MAIL TO MAKE
 SURE WE CAN USE THIS INFORMATION AS PART OF THE
 DOCUMENTATION OR SUBMIT THE PHOTOGRAPHS WHEN
 RESUBMITTING WITH THE PERMIT PACKAGE.
  
 1ST ROUND COMMENT. SHEET 2.0 INDICATES THE WINDOW TYPE
 FOR THE BEDROOMS TO BE IDENTIFIED AS TYPE 1 WINDOWS.
 THE SIZE TO BE 53 INCHES WIDE AND 38 INCHES TALL. THE
 WINDOW TYPE AS SHOWN IN THE COUNTY PICTOMETRY PROGRAM
 AND IN GOOGLE STREET VIEW APPEARS TO BE AWNING TYPE
 WINDOWS THAT WAS WIDELY USED DURING THAT TIME PERIOD.
 WITH THE REPLACEMENT OF THESE WINDOWS THE PLANS
 INDICATE THE NEW WINDOWS ARE TO BE SINGLE HUNG WINDOW
 TYPE OF WINDOW. THIS REDUCES THE AMOUNT OF REQUIRED
 CLEAR OPENING REQUIRED.
  
 2014 EXISTING BUILDING CODE 701.2 CONFORMANCE. AN
 EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE
 ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE THAN
 ITS EXISTING CONDITION.
 EXCEPTION: WHERE THE CURRENT LEVEL OF SAFETY IS
 PROPOSED TO BE REDUCED, THE PORTION ALTERED SHALL
 CONFORM TO THE REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 IN THE 2014 FBC-B THE REQUIREMENT FOR EMERGENCY ESCAPE
 AND RESCUE OPENINGS (WINDOWS) IS REQUIRED. SEE FBC-B
 SECTIONS:
 1A) FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (2ND FLOOR).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADE
 FLOOR EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5
 SQUARE FEET.
  
 1B) FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES. THE
 MINIMUM NET CLEAR OPENING WIDTH DIMENSION SHALL BE 20
 INCHES . THE NET CLEAR OPENING DIMENSIONS SHALL BE THE
 RESULT OF NORMAL OPERATION OF THE OPENING.
  
 1C) FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
 PLEASE NOTE THERE IS AN ALLOWABLE 5 PER-CENT REDUCTION
 FOR THE LARGE MISSILE IMPACT WINDOW BECAUSE OF THE
 HEAVIER FRAMES. 2014 FBC-B EXISTING BUILDING CODE.
 EXCEPTION.
  
 PLEASE PROVIDE A NEW WINDOW SCHEDULE WHERE THE CLEAR
 VENT OR WINDOW OPENING COMPLIES WITH ABOVE
 REQUIREMENTS. A USE OF HORIZONTAL SLIDING WINDOW SIZE
 33 WILL ACCOMPLISH THE REQUIRED 5-0 SQ. FT. WITH THE
 OPENING SIZE OF 5.10 SQ. FT. FOR THE 1ST FLOOR. THE 2ND
 FLOOR REQUIREMENT OF 5.7 SQ. FT. WOULD REQUIRE A
 HORIZONTAL SLIDER THE SIZE OF 34 OR 53 INCHES WIDE AND
 50 5/8 INCHES WIDE TO PROVIDE A CLEAR OPENING OF
 7.00 SQ. FT. PLEASE PROVIDE WINDOW TYPE AND SIZE FOR
 THE NEW EGRESS WINDOWS.
  
 2) 2ND REQUEST. 107.2.4 EXTERIOR WALL ENVELOPE. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
 THE CONSTRUCTION DOCUMENTS SHALL INCLUDE MANUFACTURERS
 INSTALLATION INSTRUCTIONS THAT PROVIDE SUPPORTING
 DOCUMENTATION THAT THE PROPOSED PENETRATION AND OPENING
 DETAILS DESCRIBED IN THE CONSTRUCTION DOCUMENTS
 MAINTAIN THE WEATHER RESISTANCE OF THE EXTERIOR WALL
 ENVELOPE.
  
 3-4) COMPLIED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-30 Cont ID  
Sent By jwitmer Date 2017-05-30 Time 15:39 Rev Time 0.00
Received By jwitmer Date 2017-05-30 Time 17:12 Sent To  
Notes
2017-05-30 15:40:192014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050881
 ADD: 805 19TH ST.
 CONT: M. J. EBERSBACH CONSTRUCTION
 TEL: 561-271-0136
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 30/ 2017
 ACTION: DENIED
  
 1) SHEET 2.0 INDICATES THE WINDOW TYPE FOR THE BEDROOMS
 TO BE IDENTIFIED AS TYPE 1 WINDOWS. THE SIZE TO BE 53
 INCHES WIDE AND 38 INCHES TALL. THE WINDOW TYPE AS
 SHOWN IN THE COUNTY PICTOMETRY PROGRAM AND IN GOOGLE
 STREET VIEW APPEARS TO BE AWNING TYPE WINDOWS THAT WAS
 WIDELY USED DURING THAT TIME PERIOD.
 WITH THE REPLACEMENT OF THESE WINDOWS THE PLANS
 INDICATE THE NEW WINDOWS ARE TO BE SINGLE HUNG WINDOW
 TYPE OF WINDOW. THIS REDUCES THE AMOUNT OF REQUIRED
 CLEAR OPENING REQUIRED.
  
 2014 EXISTING BUILDING CODE 701.2 CONFORMANCE. AN
 EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE
 ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE THAN
 ITS EXISTING CONDITION.
 EXCEPTION: WHERE THE CURRENT LEVEL OF SAFETY IS
 PROPOSED TO BE REDUCED, THE PORTION ALTERED SHALL
 CONFORM TO THE REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 IN THE 2014 FBC-B THE REQUIREMENT FOR EMERGENCY ESCAPE
 AND RESCUE OPENINGS (WINDOWS) IS REQUIRED. SEE FBC-B
 SECTIONS:
 1A) FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (2ND FLOOR).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADE
 FLOOR EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5
 SQUARE FEET.
  
 1B) FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES. THE
 MINIMUM NET CLEAR OPENING WIDTH DIMENSION SHALL BE 20
 INCHES . THE NET CLEAR OPENING DIMENSIONS SHALL BE THE
 RESULT OF NORMAL OPERATION OF THE OPENING.
  
 1C) FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
 PLEASE NOTE THERE IS AN ALLOWABLE 5 PER-CENT REDUCTION
 FOR THE LARGE MISSILE IMPACT WINDOW BECAUSE OF THE
 HEAVIER FRAMES. 2014 FBC-B EXISTING BUILDING CODE.
 EXCEPTION.
  
 PLEASE PROVIDE A NEW WINDOW SCHEDULE WHERE THE CLEAR
 VENT OR WINDOW OPENING COMPLIES WITH ABOVE
 REQUIREMENTS. A USE OF HORIZONTAL SLIDING WINDOW SIZE
 33 WILL ACCOMPLISH THE REQUIRED 5-0 SQ. FT. WITH THE
 OPENING SIZE OF 5.10 SQ. FT. FOR THE 1ST FLOOR. THE 2ND
 FLOOR REQUIREMENT OF 5.7 SQ. FT. WOULD REQUIRE A
 HORIZONTAL SLIDER THE SIZE OF 34 OR 53 INCHES WIDE AND
 50 5/8 INCHES WIDE TO PROVIDE A CLEAR OPENING OF
 7.00 SQ. FT. PLEASE PROVIDE WINDOW TYPE AND SIZE FOR
 THE NEW EGRESS WINDOWS.
  
 2) 107.2.4 EXTERIOR WALL ENVELOPE. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
 THE CONSTRUCTION DOCUMENTS SHALL INCLUDE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS THAT PROVIDE SUPPORTING
 DOCUMENTATION THAT THE PROPOSED PENETRATION AND OPENING
 DETAILS DESCRIBED IN THE CONSTRUCTION DOCUMENTS
 MAINTAIN THE WEATHER RESISTANCE OF THE EXTERIOR WALL
 ENVELOPE.
 3) PLEASE NOTE THE PRODUCT APPROVAL DOES NOT PROVIDE
 THE BUCK ATTACHMENT. WOOD BUCKS BY OTHERS, MUST BE
 ANCHORED PROPERLY TO TRANSFER LOADS TO THE STRUCTURE.
 SHEET 3.0 NOTE 24 DOES NOT PROVIDE THE TYPE OF ANCHOR,
 LENGTH OF ANCHOR NOR THE SPACING OF THE ANCHOR. 107.2.4
 EXTERIOR WALL ENVELOPE. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE.
  
 4) SHEET 2.0 ON THE WIND PRESSURE SCHEDULE INDICATES
 THE VALUES ARE TAKEN AT 50 SQ. FT. PLEASE NOTE MOST OF
 THE OPENINGS AND MULLIONS THAT TRANSFER ? OF THE
 OPENING ARE EITHER 20 SQ. FT OR LESS. PLEASE ALSO NOT
 THE PRESSURES TAKEN FOR ROOFING COMPONENTS AND CLADDING
 WILL NEED TO BE CALCULATED ON 10 SQ. FT. FOR ANCHORS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-14 Cont ID  
Sent By jpearson Date 2017-07-14 Time 10:30 Rev Time 0.00
Received By jpearson Date 2017-07-14 Time 10:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-01 Cont ID  
Sent By jpearson Date 2017-06-01 Time 07:53 Rev Time 0.00
Received By jpearson Date 2017-06-01 Time 07:53 Sent To  
Notes
2017-06-01 08:11:43CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 1ST REVIEW:
 1. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE AND
 VALUE OF WORK. FBC 105.1 , 109.3
 2. SHEET 4.0 STATES THAT THE ELECTRICAL LOAD
 CALCULATION WAS PROVIDED UNDER PERMIT #17030423. IN
 RESEARCHING THIS PERMIT, I FOUND THE LOAD CALCULATIOIN
 TO BE INCOMPLETE, WITH NO LOAD LISTED FOR HOUSE PANEL.
 ADDITIONALLY, THE ADDITION OF TANKLESS WATER HEATERS IN
 EACH UNIT WILL INCREASE THE LOAD. THEREFORE, PROVIDE
 COMPLETE LOAD CALCULATION FOR BUILDING WITH ALL LOADS
 LISTED TO JUSTIFY SIZING OF SERVICE. SPECIFY METHOD
 USED FOR CALCULATION. NEC 220, FBC R E3602.2
 3. THE 2 SMALL APPLIANCE CIRCUITS FOR THE KITCHEN SHALL
 HAVE NO OTHER OUTLETS. THE BATHROOM CAN NOT BE SUPPLIED
 FROM ONE OF THESE CIRCUITS. PROVIDE CORRECTION. NEC
 210.52(B)(2), 210.11(C)(3), FBC R E3703.2, E3901.3.1
 4. THERE IS A CONFLICT WITH THE PANEL SCHEDULE AND WHAT
 IS SHOWN ON PLAN IN REFERENCE TO THE A/C SYSTEM. PANEL
 SCHEDULE SHOWS AN A/C AND AHU, PLAN SHOWS A MINI-SPLIT
 SYSTEM. PROVIDE CORRECTION AND INCLUDE IN ABOVE
 MENTIONED LOAD CALCULATION. FBC 107.2.1, FBC R E3602.2
 5. PROVIDE FLOOR PLAN FOR EACH UNIT. FBC 107.2.1
 6. PENINSUAL IN KITCHEN REQUIRES AN OUTLET, SHOW ON
 PLAN. NEC 210.52(C)(3), FBC R E3901.4.3
 7. PROVIDE PANEL SCHEDULE FOR HOUSE PANEL. NEC 408.4
 8. PROVIDE CLARIFICATION FOR WIRING TO RANGE AND
 TANKLESS WATER HEATER. #8 ROMEX, WHICH IS TYPICAL IN
 HOUSE WIRING, IS NOT RATED FOR THE 50 AMP BREAKER SHOWN
 IN PANEL SCHEDULE. NEC 334.80, FBC R E3705.4.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-07-07 Cont ID  
Sent By pleduc Date 2017-07-07 Time   Rev Time 0.00
Received By pleduc Date 2017-07-07 Time 13:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-22 Cont ID  
Sent By pleduc Date 2017-05-22 Time   Rev Time 0.00
Received By pleduc Date 2017-05-22 Time 10:03 Sent To  
Notes
2017-05-22 13:40:52THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THERE IS NO REFERENCE TO THE FLORIDA FIRE PREVENTION
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS, INCLUDING NFPA 101
 CHAPTER 31, EXISTING APARTMENT BUILDINGS.
  
  
 PLEASE ENSURE COMPLAINCE. THE FIRE INSPECTOR SHALL
 CONFIRM AND VERIFY ON FIRE INSPECTIONS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-08-10 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-07 Time 13:53 Sent To  
Notes
2017-08-09 13:54:16RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-18 Cont ID  
Sent By shill Date 2017-07-17 Time 06:46 Rev Time 0.00
Received By shill Date 2017-07-03 Time 11:35 Sent To  
Notes
2017-07-03 11:35:57B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-01 Cont ID  
Sent By jpearson Date 2017-06-01 Time 08:12 Rev Time 0.00
Received By jpearson Date 2017-05-18 Time 15:50 Sent To  
Notes
2017-05-19 15:50:17B19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-30 Cont ID  
Sent By jwitmer Date 2017-05-30 Time 15:39 Rev Time 0.00
Received By jwitmer Date 2017-05-30 Time 12:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-08-10 Cont ID  
Sent By ccole Date 2017-08-10 Time 08:00 Rev Time 0.00
Received By ccole Date 2017-08-10 Time 08:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-07-14 Cont ID  
Sent By ccole Date 2017-07-14 Time 11:29 Rev Time 0.00
Received By ccole Date 2017-07-14 Time 11:12 Sent To  
Notes
2017-07-14 11:49:112ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17050881
 7/14/17
  
 RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS: 1)
 REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR. IF USING NATURAL
 VENTILATION SEE SECTION 402.1.
  
 2) COMMENT #3 FROM THE 1ST REVIEW STILL PARTIALLY
 EXISTS: SUBMIT AHRI CERTIFICATES FOR THE NEW AC
 SYSTEMS.
  
 3) COMMENT #4 FROM THE 1ST REVIEW STILL PARTIALLY
 EXISTS: PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSERS- SECTION 301.15.
  
 4) NEW COMMENT: CLARIFY HOW AIR IS BEING RETURNED FROM
 EACH BEDROOM #2- SEE SECTION 601.5
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-25 Cont ID  
Sent By ccole Date 2017-05-25 Time 17:07 Rev Time 0.00
Received By ccole Date 2017-05-25 Time 13:54 Sent To  
Notes
2017-05-25 17:07:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050881
 5/25/17
  
 RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW MINI-SPLIT SYSTEMS IN ACCORDANCE WITH SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 3) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLAN, AND
 SUBMIT AHRI CERTIFICATES FOR EACH SYSTEM.
  
 4) SHOW THE LOCATIONS OF THE EXTERIOR CONDENSER UNITS
 AND PROVIDE ENGINEERED INSTALLATION DETAILS- SECTION
 301.15
  
 5) THE PALM BEACH COUNTY APPRAISOR'S REPORT SHOWS NO
 HEATING OR COOLING IN THE APARTMENTS, HOWEVER NOW THAT
 NEW AC SYSTEMS ARE BEING INSTALLED, THE BUILDING SHALL
 BE COMPLIANCE WITH THE CURRENT FBC-14 ENERGY
 CONSERVATION CODE. PLEASE REFER TO SECTION R101.4.5 AND
 SUBMIT DOCUMENTATION OF ENEGY EFFICIENCY COMPLIANCE
 USING EITHER THE PRESCIPTIVE OR PERFORMANCE BASED
  
 METHOD- SEE SECTION R101.5.1 FOR COMPLIANCE MATERIALS
 INFORMATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-08-04 Cont ID  
Sent By gjohnson Date 2017-08-04 Time 11:46 Rev Time 0.00
Received By gjohnson Date 2017-08-04 Time 11:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-07-14 Cont ID  
Sent By gjohnson Date 2017-07-14 Time 18:24 Rev Time 0.00
Received By gjohnson Date 2017-07-14 Time 16:49 Sent To  
Notes
2017-07-14 18:29:022ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: DENIED 5/24/17
  
 NOT COMPLIED 2ND REQUEST1. SANITARY RISER IS NOT CODE
 COMPLIANT EACH FIXTURE BRANCH SHALL CONNECT TO A WET
 VENT OR BE SEPARATELY VENTED THEY CAN NOT CONNECT
 DIRECTLY TO THE BUILDING DRAIN OR SOIL STACK WITHOUT
 BEING VENTED. PER FBC PL 901.2.1
  
  
  
 TO EXPEDITE PLUMBING APPROVAL I SUGGEST A MEETING BE
 SCHEDULED TO GO OVER SANITARY RISER.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-24 Cont ID  
Sent By gjohnson Date 2017-05-24 Time 17:00 Rev Time 0.00
Received By gjohnson Date 2017-05-24 Time 17:00 Sent To  
Notes
2017-05-24 17:12:511ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: DENIED 5/24/17
  
 1. SANITARY RISER IS NOT CODE COMPLIANT EACH FIXTURE
 BRANCH SHALL CONNECT TO A WET VENT OR BE SEPARATELY
 VENTED THEY CAN NOT CONNECT DIRECTLY TO THE BUILDING
 DRAIN OR SOIL STACK WITHOUT BEING VENTED. PER FBC PL
 901.2.1
  
 2. PROVIDE LOCATION OF NEW TANKLESS HEATER. PER WPB
 AMEND TO FBC 107.2.1
  
 3. PROVIDE MANUFACTURE SPECS FOR TANKLESS HEATER. PER
 WPB AMEND TO FBC 107.2.1
  
 TO EXPEDITE PLUMBING APPROVAL I SUGGEST A MEETING BE
 SCHEDULED TO GO OVER SANITARY RISER.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  