Plan Review Details - Permit 17050813
Plan Review Stops For Permit 17050813
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-10-12 Cont ID  
Sent By cthroop Date 2017-10-12 Time 14:07 Rev Time 0.00
Received By cthroop Date 2017-10-12 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-09-19 Cont ID  
Sent By cthroop Date 2017-09-19 Time 07:29 Rev Time 0.00
Received By cthroop Date 2017-09-18 Time 11:19 Sent To  
Notes
2017-09-19 07:31:19BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DUPLICATE PLAN SHEETS SUBMITTED.
 2. CONSOLIDATE PLANS INTO ONE SET.
 3. DESIGNER TO SIGN PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-09 Cont ID  
Sent By cthroop Date 2017-08-09 Time 16:43 Rev Time 0.00
Received By cthroop Date 2017-08-09 Time 09:19 Sent To  
Notes
2017-08-09 16:44:02BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ADDRESS 1ST REVIEW COMMENTS AND RE-SUBMIT.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-08 Cont ID  
Sent By cthroop Date 2017-06-08 Time 11:28 Rev Time 0.00
Received By cthroop Date 2017-06-08 Time 10:33 Sent To  
Notes
2017-06-08 11:37:21BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 REVISION
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR REPLACEMENT WINDOWS.
 DESIGNER TO REVIEW AND APPROVE.
 2. DESIGNER OF RECORD TO SIGN AND SEAL PLANS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW SUBMITTALS.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
 WHERE SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL
 IS AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION
 DOCUMENTS TO BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN REQUIRED BY THE BUILDING OFFICIAL, AND
 MAY REQUIRE ONLY ONE SET OF SUBMITTALS.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-09-14 Cont ID  
Sent By jpearson Date 2017-09-14 Time 09:31 Rev Time 0.00
Received By jpearson Date 2017-09-14 Time 09:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-08-01 Cont ID  
Sent By jpearson Date 2017-08-01 Time 13:51 Rev Time 0.00
Received By jpearson Date 2017-08-01 Time 13:51 Sent To  
Notes
2017-08-01 13:51:40CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW (2ND REVIEW) STATUS: DENIED, SEE
 COMMENTS BELOW.
  
 1. PREVIOUS COMMENT NOT ADDRESSED: PLAN IS REQUIRED TO
 BE SIGNED AND SEALED BY THE DESIGN PROFESSIONAL OF
 RECORD. FS 471.003(2)(H); 471.025; FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-30 Cont ID  
Sent By jleahy Date 2017-05-30 Time 15:26 Rev Time 0.00
Received By jpearson Date 2017-05-30 Time 15:25 Sent To  
Notes
2017-05-30 15:28:331. PLAN REQUIRED TO BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL OR ELECTRICAL QUALIFIER. FS 471.003(2)(H),
 FS 471.025

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2017-10-11 Cont ID  
Sent By gjohnson Date 2017-10-11 Time 08:22 Rev Time 0.00
Received By gjohnson Date 2017-10-11 Time 08:22 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-09-22 Cont ID  
Sent By gjohnson Date 2017-09-22 Time 15:34 Rev Time 0.00
Received By gjohnson Date 2017-09-22 Time 15:34 Sent To  
Notes
2017-09-22 15:44:571ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. GAS PLAN SHOWS TWO LOCATIONS OF TANKLESS WATER
 HEATER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE INDICATE LENGTH OF VENT AND INTAKE OF
 TANKLESS HEATER. FBC FG 502-505
  
 3. PROVIDE GAS RISER THAT CLEARLY SHOWS WERE THE BRANCH
 PIPE CONNECT AND WHAT ARE HORIZONTAL RUNS OR VERTICAL.
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-08-11 Cont ID  
Sent By gjohnson Date 2017-08-11 Time 14:03 Rev Time 0.00
Received By gjohnson Date 2017-08-11 Time 14:03 Sent To  
Notes
2017-08-11 14:07:012ND REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS: HAS NOT COMPLIED 2ND REQUEST
  
 1. PLEASE PROVIDE REVISED GAS PLAN AND RISER SHOWING
 RELOCATION OF TANKLESS HEATER. FBC-2014 FUEL GAS, SECS.
 402.4.1, 402.4.2.
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-06-05 Cont ID  
Sent By gjohnson Date 2017-06-05 Time 10:13 Rev Time 0.00
Received By gjohnson Date 2017-06-05 Time 10:13 Sent To  
Notes
2017-06-05 10:17:191ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 1. PLEASE PROVIDE REVISED GAS PLAN AND RISER SHOWING
 RELOCATION OF TANKLESS HEATER. FBC-2014 FUEL GAS, SECS.
 402.4.1, 402.4.2.
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-09-20 Cont ID  
Sent By destabro Date 2017-09-20 Time 16:57 Rev Time 0.00
Received By destabro Date 2017-09-20 Time 16:57 Sent To B
Notes
2017-09-20 16:58:209/20/2017 - NO CHANGES SINCE LAST SUBMITTAL. DLE

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By destabro Date 2017-08-25 Time 10:47 Rev Time 0.00
Received By destabro Date 2017-08-25 Time 10:47 Sent To B
Notes
2017-08-25 10:48:528/25/2017 - CONDITIONAL APPROVAL FOR ZONING: PLEASE
 PROVIDE SEPARATE PERMIT FOR A/C UNIT TO SHOW DEPTH OF
 ENCROACHMENT INTO SIDE SETBACK. REQUIREMENTS OF THE HPB
 DECISION (HPB 16-59B) MET. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-05-25 Cont ID  
Sent By destabro Date 2017-05-25 Time 15:09 Rev Time 0.00
Received By destabro Date 2017-05-25 Time 15:09 Sent To B
Notes
2017-05-25 15:11:215/25/2017 - INCORRECT HORIZONTAL SLIDER WINDOWS
 INSTALLED AND DOES NOT MEET PREVIOUSLY APPROVED PLANS
 FROM HPB. ADDITIONALLY, WINDOW OPENINGS WERE MODIFIED
 TO ACCOMODATE NEW WINDOWS, WHICH WAS NOT APPROVED. CASE
 PENDING REVIEW AT JUNE 27, 2017 HPB MEETING.DLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-10-12 Cont ID  
Sent By cthroop Date 2017-10-12 Time 14:05 Rev Time 0.00
Received By cthroop Date 2017-10-06 Time 14:19 Sent To  
Notes
2017-10-10 14:19:39RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-09-29 Time   Rev Time 0.00
Received By lmarchan Date 2017-09-01 Time 13:05 Sent To  
Notes
2017-09-05 13:05:21R37

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-05 Cont ID  
Sent By lmarchan Date 2017-08-25 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-28 Time 16:08 Sent To  
Notes
2017-07-31 16:08:25R10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-08 Cont ID  
Sent By cthroop Date 2017-06-08 Time 11:28 Rev Time 0.00
Received By cthroop Date 2017-05-17 Time 11:59 Sent To  
Notes
2017-05-18 12:00:37R19

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-09-29 Cont ID  
Sent By ccole Date 2017-09-29 Time 15:43 Rev Time 0.00
Received By ccole Date 2017-09-29 Time 15:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-17 Cont ID  
Sent By ccole Date 2017-08-17 Time 13:59 Rev Time 0.00
Received By ccole Date 2017-08-17 Time 13:59 Sent To  
Notes
2017-08-17 14:03:002ND REVIEW FBC-2014 MECHANICAL
 REVISION #17050813
 MASTER #16090271
 8/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE 1ST REVIEW COMMENT STILL EXISTS. I AM REPRINTING
 IT BELOW- PLEASE COMPLY.
  
 1) REFER TO SECTION G2407 FBC-14 RESIDENTIAL AND
 INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE
 RELOCATED GAS WATER IN THE GARAGE CLOSET. PLEASE
 INCLUDE CALCULATIONS AND MANUFACTURER'S SPECIFICATIONS
 FOR THE APPLIANCE.
  
 2) SUBMITTAL OF PREVIOUSLY APPROVED STAMPED CITY PLANS
 ARE NOT ACCEPTABLE FOR REVISION. PLEASE SUBMIT
 UP-TO-DATE REVISED PLANS SIGNED BY THE DESIGNER OF
 RECORD- SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-05 Cont ID  
Sent By ccole Date 2017-06-05 Time 15:37 Rev Time 0.00
Received By ccole Date 2017-06-05 Time 15:17 Sent To  
Notes
2017-06-05 15:44:411ST REVIEW FBC-2014 MECHANICAL
 REVISION #17050813
 MASTER #16090271
  
 RESULTS: DENIED.
  
 1) REFER TO SECTION G2407 FBC-14 RESIDENTIAL AND
 INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE
 RELOCATED GAS WATER IN THE GARAGE CLOSET. PLEASE
 INCLUDE CALCULATIONS AND MANUFACTURER'S SPECIFICATIONS
 FOR THE APPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-10-11 Cont ID  
Sent By gjohnson Date 2017-10-11 Time 08:16 Rev Time 0.00
Received By gjohnson Date 2017-10-11 Time 07:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-09-22 Cont ID  
Sent By gjohnson Date 2017-09-22 Time 15:45 Rev Time 0.00
Received By gjohnson Date 2017-09-22 Time 16:21 Sent To  
Notes
2017-09-22 15:47:541ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SANITARY RISER IS UNCLEAR IT NEEDS TO CLEARLY
 SHOW HORIZONTAL AND VERTICAL PIPES THE VENTS FROM WASTE
 AND SOIL PIPES SHOW PTRAPS AND IDENTIFY BATHROOM
 GROUPS. PER AMEND TO FBC 107.3.5.3(11)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-08-11 Cont ID  
Sent By gjohnson Date 2017-08-11 Time 14:07 Rev Time 0.00
Received By gjohnson Date 2017-08-11 Time 09:27 Sent To  
Notes
2017-08-11 14:08:112ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: HAS NOT COMPLIED 2ND REQUEST
  
 1. PLEASE PROVIDE REVISED PLUMBING PLAN AND RISER
 DIAGRAM TO INCLUDE THE ADDITIONAL TUB AND BAR SINK. PER
 WPM AMEND TO FBC 107.3.5.3(11)
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-05 Cont ID  
Sent By tklarge Date 2017-06-05 Time 10:07 Rev Time 0.00
Received By gjohnson Date 2017-06-05 Time 08:49 Sent To  
Notes
2017-06-05 10:12:131ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE REVISED PLUMBING PLAN AND RISER
 DIAGRAM TO INCLUDE THE ADDITIONAL TUB AND BAR SINK. PER
 WPM AMEND TO FBC 107.3.5.3(11)
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  