Plan Review Details - Permit 17050772
Plan Review Stops For Permit 17050772
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-21 Cont ID  
Sent By pleduc Date 2017-06-21 Time   Rev Time 0.00
Received By pleduc Date 2017-06-20 Time 17:02 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-19 Cont ID  
Sent By pleduc Date 2017-05-19 Time   Rev Time 0.00
Received By pleduc Date 2017-05-19 Time 14:51 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-06 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-19 Time 11:22 Sent To  
Notes
2017-06-20 11:23:00RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-06 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-17 Time 16:27 Sent To  
Notes
2017-05-18 16:27:40ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-07-06 Cont ID  
Sent By ccole Date 2017-07-06 Time 08:26 Rev Time 0.00
Received By ccole Date 2017-07-05 Time 17:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-06 Cont ID  
Sent By ccole Date 2017-06-06 Time 15:44 Rev Time 0.00
Received By ccole Date 2017-06-06 Time 15:44 Sent To  
Notes
2017-06-06 16:40:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050772
 6/6/17
  
 RESULTS: DENIED.
  
 1) THE SUBMITTED MECHANICAL PLANS FROM THE MAIN SET DO
 NOT SPECIFICALLY PROVIDE INFORMATION FOR THE PROPOSED
 KITCHEN EXHAUST HOOD AND SYSTEM. SUBMIT PLANS THAT SHOW
 THE LOCATIONS OF THE OVEN, THE EXHAUST HOOD, THE
 EXHAUST DUCT RUN FROM OUTLET TO TERMINATION, AND THE
 EXHAUST FAN,
  
 2) PROVIDE EQUIPMENT SCHEDULES FOR THE HOOD AND FAN.
 PLEASE NOTE THE FAN SCHEDULE ON M001 IS DESIGNATED "
 FOR REFERENCE ONLY".
  
 3) INDICATE HOW MAKEUP IS BEING PROVIDED FOR THE
 EXHAUST SYSTEM AND PROVIDE VENTILATION AND AIR BALANCE
 CALCULATIONS,
  
 4) PROVIDE CLEARANCE DISTANCE MEASUREMENTS FROM THE
 EXHAUST OUTLET TO MECHANICAL AND GRAVITY AIR INTAKES,
  
 5) THERE ARE PRODUCT DATA SUBMITTALS FOR AN INLINE
 EXHAUST FAN AND A SIDEWALL EXHAUST FAN- WHICH IS TO BE
 USED? THE EQUIPMENT SCHEDULE ON M001 INDICATES THE
 INLINE FAN. IF THAT IS THE CASE, PLEASE CLARIFY THE
 PURPOSE OF THE SIDEWALL FAN.
  
 6) A FL. LICENSED MECHANICAL CONTRACTOR MUST SUBMIT A
 PERMIT APPLICATION TO INSTALL THE EXHAUST HOOD AND
 DUCTWORK- SECTION 489.113(3) FLORIDA STAUTES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  